7
Installation Manual
PART 3: SOLAR WATER HEATER INSTALLATION
Location:
• Sufficient room to service water heater
• Provisions made to protect area from
water damage
• Centrally located to fixtures
• Protected from freezing temperatures
• Area free of flammable vapors
Potable Water Supply:
• All related piping is free from leaks.
• Thermal Expansion tank installed
• Water heater and fixtures have been
properly purged of air.
Relief Valve:
• Temperature and Pressure Relief Valve
properly installed and discharge line
runs to open drain.
• Discharge line is not exposed to freezing
temperatures.
• Discharge line is constructed of copper.
Wiring; SE Models:
• Power supply voltage agrees with the
water heater rating plate.
• Branch circuit wire fusing or circuit
breaker properly sized.
• Electrical connections tight and unit
properly grounded.
Wiring; SB Models:
• Water heater control is secure in control
well.
• Boiler back-up control is wired back to
the boiler control or relay center.
Solar Heat Exchanger to Solar Panel; SE
and SB Models:
• Anti-Freeze if required, is added and is
rated as non-toxic with copy of MSDS
sheet for homeowner.
• Solar Heat Exchanger is completely
purged of air.
• Expansion tank and pressure
temperature gauge are operating
properly.
• Solar control shows circulators
operating properly on the solar panels.
Boiler Heat Exchanger; SB Models Only:
• Heat Exchanger is completely purged of
air.
• Expansion tank and pressure
temperature gauge are operating
properly.
• Boiler control is operating circulator for
the boiler back-up heat exchanger.
Anti-Freeze Fluid:
• Make sure freeze protection fluids are
certified as non-toxic.
• Glycol percentage must be calculated
per local area freeze level.
• Provide glycol MSDS sheet to end user.
INSTALLATION CHECK LIST
SOLAR WATER HEATER LOCATION
Choose a location for your solar water heater centralized to the piping system. You must also locate
the SuperStor Contender Solar Water Heater and related domestic piping where it will not be
exposed to freezing temperature. All piping should be insulated. The Solar Water Heater should be
installed so there is access to the element and thermostat for future service. If you do not provide
minimum clearances, it might not be possible to service the water heater without removing it from
the space. The solar water heater should also be placed in a location where T&P discharge or a leak
will not result in damage to the surrounding area. If you do not have this location requirement avail-
able, you must use an auxiliary catch pan.