CONTROL OVERVIEW
Function 4
Warm Weather Shutoff
WARM WEATHER OFF
4
68 °F
Description: Warm Weather Shut off will disable the heating module and the Total System Control
will then optimize for domestic hot water only. Warm Weather Shut off will occur if the programmed
outdoor temperature is exceeded by the current outdoor sensor temperature. Factory Default of
68 °F (Range 41 °F to 122 °F)
Function 5
Min outdoor Temp
MIN OUTDOOR TEMP
5
5 °F
Description: Allows the user to set the minimum outdoor design temperature for the system. Factory
Default is set to 5 °F (Range -49 °F to 122 °F)
Function 6
Max Supply Temp
MAX SUPPLY TEMP
6
140 °F
Description: Allows the user to set the maximum design supply temperature based on the minimum
outdoor design temperature. Factory Default 140 °F - Range (77 °F to 170 °F)
Function 7
Max Outdoor Temp
MAX OUTDOOR TEMP
7
68 °F
Description: Allows the user to set the maximum outdoor design temperature for the system design.
Factory default 68 °F – Range (32 °F to 95 °F)
Function 8
Min Supply Temp
MIN SUPPLY TEMP
8
120 °F
Description: Allows the user to set the design supply water temperature based on the maximum out-
door design temperature. Factory Default 120 °F – Range (32 °F to 200 °F)
Function 9
Min Tank Temp
MIN TANK TEMP
9
68 °F
Description: Allows the user to set the minimum tank temperature. Factory Default 68 °F – Range (32
°F to 200 °F)