30

MPC Platinum Installation and Operation Manual

HT# 059085-00 

F

Monday through Thursday:

   Vari-Boost begins before 6 am and ends at 6 am

 Day temperature level is maintained from 6 am until before 10 PM

 Early Shutdown starts before 10 PM and ends at 10 PM

 Night temperature level is maintained from 10 PM.

Friday: 

 Vari Boost begins before 7 am and ends at 7 am

 Day temperature level is maintained from 7 am to 11 am

 Night temperature level is maintained from 11 am to 1 PM

 Day temperature level is maintained from 1 PM to 4 PM

 Night temperature level is maintained from 4 PM to 6 PM

 Day temperature level is maintained from 6 PM until before 10 PM

 Early Shutdown starts before 10 PM and ends at 10 PM

 Night temperature level is maintained from 10 PM.

Saturday:

 

 No Vari Boost because the Day#1 is not programmed

 Day temperature level is maintained from 8 am until before 4 PM

 Early Shutdown starts before 4 PM and ends at 4 PM

 Night temperature level is maintained from 4 PM.

Sunday:

 

 Night temperature level is carried over from Saturday and maintained all day Sunday, ending at the 

Vari Boost Monday morning

 ALERT

On an Internet control with Space Average, the Boost can extend to an 

additional hour if Day Target is not reached within the Boost period.

COPY SCHEDULE

SELECT:

 

Settings/Schedules/Copy Schedule

 To reduce the need for setting each day's time schedule, this feature has been made to allow

the copying of Monday schedule to the rest of the week.

------ SCHEDULES ------

Copy Mon Schedules

To All Other Days

(Select to Execute)

VACATION SCHEDULE SETTING

(Used on Internet Communication Controls Only)

 The  vacation  Space Target  and  settings  can  only  be  set  on  the  Internet  ICMS  website

(http://www.htcontrols.com).

 The MPC Platinum offers a Vacation Schedule with an adjustable lower space target that it

 During that time, the MPC Platinum uses the Vacation Schedule Space Target.  However, it

also uses the Night Heat Adjustment and Night Outdoor Cutoff settings.

AUX RELAY SCHEDULE 

Close/Open Schedules Mon #1 - 4  

Default: Empty

SELECT:

 

Settings/Schedules/Aux Schedule

 The Auxiliary (Aux) Clock is an extra Normally Open relay output that energizes based

only on the Aux Schedule.  See "Wiring to Auxiliary Clock" on page 11.

 The relay status is programmable with a 

Close Time

 (Aux Clock relay is energized) and

an 

Open Time

 (Aux Clock relay is de-energized).  There are four Close/Open Time pairs 

available for each day of the week. 

 The Aux Clock relay is not affected by outdoor temperature, but acts as a separate time

clock to turn on lights, fans, dampers, or other equipment.  

 The Aux Clock has a separate schedule program from the Day/Night Schedule, but the times

are set in the same way.  It is important to note that the Copy Schedule function does not 

affect the Aux Schedule.  Each day must be programmed individually.

-AUX RELAY SCHEDULE-

MON # 1

 Close Time 

**:**

  Open Time 

**:**

Summary of Contents for MPC Platinum

Page 1: ...T T Cycle On 13 15 Cutoff 55o F Day OD 31o F SYS 138o F AUTO T T C O R P O R A T I O N R OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX...

Page 2: ...g mode 21 Option Outputs Modes 21 Option relay 1 mode 21 Option 2 Relay Mode 21 Option 3 relay mode 21 DHW Supply and return Defaults 22 Setting the Date and Time 22 Operation 23 System Settings 23 Se...

Page 3: ...GEMENT EQUIPMENT LISTED 99RA SYSTEM AUX CLOCK OPTION 1 OPTION 2 OPTION 3 BURNER 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 LINE NEUTRAL B R W MOTORIZED VALVE OUTPUT SYS OPTION 3 OPTION 2 OPTION 1 AUX...

Page 4: ...28 04 10 43Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK MSI CONNECTION ON BACK PROVE SHUTDOWN SYSTEM TEMP AU...

Page 5: ...through the system or that heat is established Once heat is established the Cycle ON segment of the cycle will begin During the Cycle ON period the MPC Platinum will keep the steam source activated Th...

Page 6: ...Operation Two Pipe Steam Direct Burner Operation For subatmospheric vacuum type steam systems see Heat Timer SRC Platinum Control on the Heat Timer web site http www heat timer com Initial Program Se...

Page 7: ...lly open See Installation on page 8 Boost and Early Shutdown The boost returns the building to its Day Normal heat level after Night Setback heat level It does it by running the burner or valve output...

Page 8: ...ys ALERT Do not install the battery unless you plan to keep the control continuously powered If the control has no power the battery will lose its charge in 100 days Motherboard CPU Board RS485 B Comm...

Page 9: ...r the HSS is on the furthest radiator in the system This radiator is usually the hardest to heat The sensor may be located on the furthest return riser However the sensor MUST be above the boiler wate...

Page 10: ...ontacts only They do not source any power The transformer is the actuator power source WARNING Switching to BYPASS during power outages activates the Output and System MPC Platinum MADE IN U S A PREV...

Page 11: ...T Cycle On 13 15 Cutoff 55o F Day OD 31o F SYS 138o F AUTO T T C O R P O R A T I O N R OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX US...

Page 12: ...ILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA SYSTEM AUX CLOCK OPTION 1 OPTION 2 OPTION 3 B...

Page 13: ...Cutoff 55o F Day OD 31o F SYS 138o F AUTO T T C O R P O R A T I O N R OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLA...

Page 14: ...CAT 5E cables more than 150 Ft CAT 6 cables can have a maximum run of 300 Ft Manual ALERT A BACnet capable Platinum control displays NETWORK PANEL Motherboard CPU Board Communication Board PLATINUM PA...

Page 15: ...wires Connect the Ethernet cable to the Communication Board on the back of the Platinum control See Platinum Internet Setup Manual Motherboard CPU Board Communication Board PLATINUM PANEL CONNECTED TO...

Page 16: ...ccept changes To change a setting s value rotate the knob Depress the button to go back through the menus or to view a setting value without changing it Digital display shows the date heating status a...

Page 17: ...input is Shorted Outputs are not active See Wiring the Shutdown on page 12 Space L O 71 F In Cycle Operation Mode the MPC Platinum is in Space Lockout utilizing space sensors until the space average...

Page 18: ...Day Time 6 00Am Night Time 10 00Pm SCHEDULES TUE 2 Day Time Night Time SCHEDULES TUE 1 Day Time 6 00Am Night Time 10 00Pm Press DAY Press NEXT SCHEDULES Copy Mon Schedules To All Other Days Select to...

Page 19: ...Disabled Manual Vari Vari ESD BOOST ADJUSTMENT Higher More Boost 0min BOOST ADJUSTMENT Higher More Boost 3 0 SEASON pg 23 DAY CUTOFF 55 F REMOTE INTERFACE Network Settings SpaceLockout Disable Day Tar...

Page 20: ...ways available at a constant pressure the time required to fill the heating system with steam will be relatively constant If your steam source is of the later type you may decide to select the Distric...

Page 21: ...elay 1 Mode Option Relay 2 Mode Each of the Option output relays can perform a different function either based on many of the control operating functions These menus assign the functionality to the re...

Page 22: ...behavior when the DHW ES looses communication with the Platinum controlor when the respetive sensor reads a fault condition Short or Open The DHW ES output relay may take up to 1 minute to respond to...

Page 23: ...t to Winter mode When the heating season is over it is a good practice to switch the control to the Summer SEASON Winter Summer ALERT Do not turn the power off to the MPC Platinum when the heating sea...

Page 24: ...low the Cutoffs the length of Cycle ON is adjusted by the Heat Adjustment Settings A gives the shortest duration of heat while P gives the longest duration of heat as shown by the chart Example Heat A...

Page 25: ...the time it takes the MPC Platinum to establish heat For example if the System Set Point is 170 F then set the Differential to 45 F so the Set Point less the Differential is 125 F If the System Set Po...

Page 26: ...reach the System Set Point The MPC Platinum adds the Warm up to the Boost time 3 Vari ESD Early ShutDown This Boost is typically only used in commercial or other buildings where the building is unoccu...

Page 27: ...n reverse The curves cannot be set separately Early Shutdown time decreases with colder outdoor temperatures The maximum time spans for the Early Shutdown are half as long as the Vari Boost ranging fr...

Page 28: ...t Disable SELECT Settings System Settings More Settings remote interface Space Lockout Space Lockout is an energy saving feature that prevents a cycle from starting when the Average Space Temperature...

Page 29: ...any Time setting that reads The 1 Day setting for any Day Time is used by the Boost The last Night Time setting is used by the Early Shutdown ESD features No two settings can have the same time on the...

Page 30: ...he need for setting each day s time schedule this feature has been made to allow the copying of Monday schedule to the rest of the week SCHEDULES Copy Mon Schedules To All Other Days Select to Execute...

Page 31: ...s Maintenance Password The Password is a security measure to prevent unauthorized local control users from making changes to the MPC Platinum settings It consists of four letters It does not protect a...

Page 32: ...pply Settings Setpoint Supply Sensor SELECT Maintenance DHW Settings Return Settings Setpoint Return Sensor The Supply Set Point is the maximum boiler water temperature the DHW Energy Saver will try t...

Page 33: ...schedule to meet this special circumstance and possibly forgetting to restore the correct settings afterward the MPC Platinum is equipped with a Shift option The Shift option will immediately change...

Page 34: ...ctivated Boost can end sooner if the Space Average reached the Day Target In addition Boost can extend up to an hour if the Space Average did not reach the target during the Boost period Fast Cool Dow...

Page 35: ...ERNET ID Solo CUSTOM INTERNET ID IP Msk Gwy DNS WWW Hi Speed Modem Platinum Control WWW Hi Speed Modem Internet Router WWW Hi Speed Modem Server Platinum Control Platinum Control WWW Hi Speed Modem Pl...

Page 36: ...ly if the establishing heat took longer than 1 hour 6001 Is an end alarm that can be set to indicate that the initial alarm status has terminated 1002 1003 Space Temp Exceeds Below Target by More Than...

Page 37: ...IP driver Using a gateway is beneficial when communicating to a proprietary protocol EMS BMS system The gateway must have both drivers the BACnet IP or MSTP and the proprietary protocol NETWORK SETTIN...

Page 38: ...A 2 B 3 C 4 D 5 E 6 F 7 G 8 H 9 I 10 J 11 K 12 L 13 M 14 N 15 O 16 P 700 DCUTOFF Outdoor Day Cutoff AV C 62 F 64 6 38 C 20 100 F 800 DLS Day Light Saving BV 0 Enable 1 Disable 900 FAULTMODE Sensor Fa...

Page 39: ...d by the panel serial number Note All objects with multiple UOM s depend upon the value of INMODE to determine which one to use Note Use XYZMIN when OPMODE is set to District Steam Use XYZTEMP HDIFF a...

Page 40: ...IBB Name DS RP B Data Sharing ReadProperty B DS WP B Data Sharing WriteProperty B DM DDB B Device Management Dynamic Device Binding B DM DOB B Device Management Dynamic Object Binding B DM DCC B Devic...

Page 41: ...e ID within the MODBUS network It must be provided by the MODBUS Network Administrator MAC ADDRESS 1 MODBUS BAUD Options 9600 19200 38400 Default 9600 The Baud determines the speed of communication Bo...

Page 42: ...ting 2 For variables that specify them if a read value is a special value 32000 32005 do not divide by MULT 3 Strings are packed 2 characters per register most significant byte first 4 Multi register...

Page 43: ...high during colder weather the result may be longer Cycle ON periods See Day and Night Outdoor Cutoff on page 24 System Set Point If the control takes a long time to establish heat it will overheat t...

Page 44: ...See Day and Night Outdoor Cutoff on page 24 Shutdown If the control Shutdown input is activated no heat will be provided The display will show Shutdown Active message See Wiring the Shutdown on page 1...

Page 45: ...F Day OD 31o F SYS 138o F AUTO T T C O R P O R A T I O N R OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE O...

Page 46: ...PTION 1 OPTION 2 T T T Cycle On Cut 55 o F Day OD 31 o F SYS 148 o F OUTPUT B BURNER MOTORIZED VALVE SYSTEM OPTION 1 OPTION 2 OPTION 3 AUX CLOCK T T C O R P O R A T I O N R 2 3 4 5 6 7 8 9 11 12 13 14...

Page 47: ...LIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 OPTION 2 T T T Cycle On Cut 55 o F Day OD 31 o F SYS 148 o F OUTPUT B BURNER MOTORIZED VALVE SYSTEM OPTION 1 OPTION 2 OPTION 3 AUX CLOCK T...

Page 48: ...T C O R P O R A T I O N R OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT E...

Page 49: ...S THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 OPTION 2 T T T Cycle On Cut 55 o F Day OD 31 o F SYS 148 o F OUTPUT B BURNER MOTORIZED VALVE SYSTEM OPTION 1 OPTION 2 OPTION 3 AUX CLOCK T T C O R P...

Page 50: ...AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 OPTION 2 T T T Cycle On Cut 55 o F Day OD 31 o F SYS 148 o F OUTPUT B BURNER MOTORIZED VALVE SYSTEM OPTION 1 OPTION 2 OPTION 3 AUX CL...

Page 51: ...TI MOD Platinum MADE IN U S A PREV SAFETY GROUND MUST BE CONNECTED OUT TEMP PROVE DHW STAGE A STAGE B MENU FUNCTIONS SELECT enters menus or accepts changes ADJUST selects menu items or changes setting...

Page 52: ...NEXT PRESS TO SELECT BACK MON 12 01 2010 10 01Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK MSI CONNECTION O...

Page 53: ...required for proper operation of any controls or other equipment installed by Heat Timer Corporation or any contractor Third Party products and services are not covered by this Heat Timer Corporation...

Page 54: ...54 MPC Platinum Installation and Operation Manual HT 059085 00 F...

Page 55: ...MPC Platinum Installation and Operation Manual 55 HT 059085 00 F...

Page 56: ...y Sensor Inputs 3 Auxiliary Temperature Sensor Inputs Network Sensor Input 64 Sensors can be connected Use only Neuron Sensors MIG or Wireless Receiver Day Night Outdoor Cutoffs 20 F 7 C to 100 F 38 C...