16
Heat-Timer Corp.
059040-00 C
connectIng extensIon panels
• The Mini-MOD is equipped with a 6-pin phone socket (RS485) to connect to extension panels. The Mini-MOD Extension is
equipped with two 6-pin phone sockets to connect to Mini-MOD and an additional Mini-MOD Extension.
• Set each Extension to a different letter (EXT-A or EXT-B). The Mini-MOD will assign the stage letters based on the extension letter
selected.
• Extension A will have its stage and Power LEDs Green. However, Extension B will have the LEDs Red. See "Mini-MOD-
• Configure the Output Types (See "Output Type" on page 17.) after connecting the Extension panels to be able to configure their
outputs.
• Only use the cable provided.
• Connection cable is provided as part of the Mini-MOD Extension package.
Extension Module
Full Modulation Sequencing Extension
F
H
J
Power
CAUTION:
Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PWR
L N
1 2
E
3 4
F
5 6
G
7 8
H
9 10
I
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
E
G
I
Comm
Ext B
K
M
O
L
N
P
17
16
VLT
mA
CUR / VLT
20
19
16
VLT
mA
GND
CUR / VLT
23
22
19
VLT
mA
GND
CUR / VLT
26
25
22
VLT
mA
GND
CUR / VLT
J
13 14
K
M
O
L
N
P
E
F
G
H
K
M
L
N
15
GND
18
GND
21
GND
24
GND
29
28
VLT
mA
CUR / VLT
32
31
16
VLT
mA
GND
CUR / VLT
27
GND
30
GND
I
J
O
P
Mini-MOD Extension A
Extension Module
Full Modulation Sequencing Extension
F
H
J
Power
CAUTION:
Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PWR
L N
1 2
E
3 4
F
5 6
G
7 8
H
9 10
I
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
E
G
I
Comm
Ext B
K
M
O
L
N
P
17
16
VLT
mA
CUR / VLT
20
19
16
VLT
mA
GND
CUR / VLT
23
22
19
VLT
mA
GND
CUR / VLT
26
25
22
VLT
mA
GND
CUR / VLT
J
13 14
K
M
O
L
N
P
E
F
G
H
K
M
L
N
15
GND
18
GND
21
GND
24
GND
29
28
VLT
mA
CUR / VLT
32
31
16
VLT
mA
GND
CUR / VLT
27
GND
30
GND
I
J
O
P
Mini-MOD Extension B
SYSTEM
A
B
C
D
1 2
RUN
PROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3 4 5 6 7 8 9 10 11 12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30 31
L N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
Use Copper Conductors Only.
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
/TSTAT
Mini-MOD
Mini-MOD
Connecting Mini-MOD to
Two Extension Panels
using RS485
Full Modulation Sequencing Control
---
---
alert
To set the Mini-Extension to a specific letter,
remove the wiring cover and switch the Ext A/Ext B
to the desired letter. DO NOT set both extensions
to the same letter as it may cause errors.