059705–00 REV. B
|
53
18
SETTINGS—BASIC HEAT MENU
The Basic Heat Setting Menu is accessed by pressing the right button under Menu once.
BASIC HEAT SETTINGS
SEASON
Selections:
Winter—Summer
Default:
Winter
Description:
The Genesis Heat-Timer
®
will turn the boiler off or close the valve when it
is in Summer setting.
When in Winter, the Genesis Heat-Timer
®
will activate the System Pump relay whenever
the Outdoor temperature (OD) falls to or below the Outdoor start setting.
In addition, it will begin heating whenever the System temperature (SYS) falls below the
calculated temperature. When the heating season is over, it is a good practice to switch
the Genesis Heat-Timer
®
to SUMMER setting.
O/D START (WAKE)
Selections:
20°F–100°F
Default:
55°F
Description:
for a complete description of Outdoor Start setting for
Day (WAKE).
O/D START (SLEEP)
Selections:
20°F–100°F
Default:
55°F
Description:
for a complete description of Outdoor Start setting for
Night (SLEEP).
SEASON
BACK SAVE
Winter
Summer
0/D START (WAKE)
BACK SAVE
F
0/D START (SLEEP)
BACK SAVE
F