STARTUP MENU—HOT WATER
O/D START (WAKE)
Selections:
20°F–100°F
Default:
55°F
Description:
When the outdoor temperature falls to the adjustable Outdoor start
temperature, the Genesis Heat-Timer
®
will control the boiler or valve to maintain the
calculated system temperature. When the outdoor temperature rises to the O/D Start
(WAKE) plus a 2°F differential, the Genesis Heat-Timer
®
will turn off the boiler or close
the valve. The System Pump relay will remain energized for the Run-On delay and
then de-energize.
This setting is for the Day level (WAKE/RETURN) of heating when the building is
occupied and people are active.
O/D START (SLEEP)
Selections:
20°F–100°F
Default:
55°F
Description:
When the outdoor temperature falls to the adjustable Outdoor start
temperature, the Genesis Heat-Timer
®
will control the boiler or valve to maintain the
calculated system temperature. When the outdoor temperature rises to the O/D Start
(SLEEP) plus a 2°F differential, the Genesis Heat-Timer
®
will turn off the boiler or close
the valve. The System Pump relay will remain energized for the Run-On delay and
then de-energize.
This setting is for the Night level (AWAY/SLEEP) of heating when the building is
unoccupied and people are inactive or asleep.