Troubleshooting

No Display or LED Lights 

   Check the power to the VSP 

Elite

.  The VSP 

Elite

 requires 120VAC power to the Black wires.  Turn the power off and back on to 

restore the display.  If unsuccessful, make sure the Display Cover of the control is securely mounted to the Base.

System or Outdoor Reads OPEN or SHORT

   If Open, short the sensor input terminals. The display should read 

SHORT

.   If it doesn’t, the VSP 

Elite 

may be damaged.

   If Short, remove the wires from the input terminals.  The display should read OPEN.  If it doesn’t, the VSP 

Elite

 may be damaged.

System or Outdoor Reads an Incorrect Temperature

   Remove the wires from the input terminals.  The display should change to read 

OPEN

.  If it doesn’t, the VSP 

Elite

 may be damaged.  

Take an ohm reading across the detached sensor wires.  The ohm reading should correspond to the Temperature Sensor Chart.  If the 

difference is within 5°F adjust the Trim for the sensor Otherwise, the sensor may be damaged. 

No Heat - All LEDs are OFF

   Check the outdoor temperature and Outdoor Cutoff readings.  If the outdoor temperature is above the Outdoor Cutoff, the VSP 

Elite

 

will not give heat.  If the display shows 

TSTAT OPEN

  then, check the 

EXT±

 terminals.  If the 

EXT±

 terminals are not jumped 

together, the VSP 

Elite

 will not give heat.  See Enable/Disable Inputs on page 

13.  Finally, if the display shows  

MANUAL OFF

  

then, the Pump Mode has been set to Manual with a speed of 0%.  Change Pump Mode to 

AUTO

.  See Pump Mode on page 13.

No Heat - System Pump LED ON - Pump Not Running

   Remove any connections to the Yellow wires for the Heating System Pump.  Test for continuity across the pair of Yellow wires.  If 

the wires are continuous, the VSP 

Elite

 is calling for the Secondary Loop/System Pump to run and the problem is not with the VSP 

Elite

.  Check the power source and the pump to determine why it is not circulating.

No Heat - System Pump LED ON - Pump Running

   Check that the boiler (or other hot water source) is providing hot water to the Boiler Loop and no valve obstruction between the 

Boiler Loop and the Injection Loop.  Check that the Injection Pump is running by measuring the pipe temperatures on the Injection 

Loop and the Secondary Loop.  Check the Minimum Speed Adjustment.  If the Minimum Speed Adjustment is set too low, the pump 

motor might not have the torque to maintain its operation.  See Minimum Speed Adjustment on page 13.

Too Little Heat

   First check that the Outdoor sensor reads a temperature not Short 

or Open.  If it does and Sensor Fault has been set to Output Off, the 

VSP 

Elite

 will try to maintain the Minimum Target temperature.  

Follow the System or Outdoor Reads Open or Short section.  Repair 

or replace the faulty sensor.  Otherwise, if all sensor readings 

are accurate, check if the Target temperature is the same as the 

Maximum Target.  If so, check the Maximum Target has not been 

set too low for the system (DO NOT increase the Maximum Target 

without consulting the installer or tubing/flooring manufacturer).  

Finally, adjust the Reset Ratio or Offset to increase the temperature 

of the circulating hot water.  Note that, depending on the type of 

radiation, it may take several hours before the ambient temperature 

increases.

Too Much Heat

   Check if the Outdoor or System temperature is not reading 

Short

 

or 

Open

.  Follow the System or Outdoor Reads Open or Short 

section.  If Sensor Fault was set to 

Output ON

, the VSP 

Elite

 

will provide excess heat to the building injection zone.  Repair 

or replace the faulty sensor.  Otherwise, if all sensor readings 

are accurate, adjust the Reset Ratio or Offset to decrease the 

temperature of the circulating hot water.

Temperature Sensor Chart

TEMPERATURE 

(in Degrees 

°

F)

Value

(in Ohms)

-30

117720

-20

82823

-10

59076

0

42683

10

31215

20

23089

25

19939

30

17264

35

14985

40

13040

45

11374

50

9944

55

8714

60

7653

70

5941

80

4649

90

3667

TEMPERATURE 

(in Degrees 

°

F)

Value

(in Ohms)

100

2914

110

2332

120

1879

130

1524

140

1243

150

1021

160

842

170

699

180

583

190

489

200

412

210

349

220

297

230

253

240

217

250

187

Summary of Contents for DIGI-SPAN VSP Elite

Page 1: ...for specialized buildings a manual pump speed control to manually adjust the pump speed based on a well balanced system and a minimum pump speed adjustment to allow for pump operation at all heating l...

Page 2: ...ng Type of Radiation in Building Reset Ratio Offset Radiators Steel Cast Iron 1 00 O 1 00 S 0 F Baseboard Finned copper tube Cast Iron 1 00 O 1 00 S 0 F Radiant High Mass Concrete 4 00 O 1 00 S 10 F R...

Page 3: ...h side of the building Be sure the location is away from doors windows exhaust fans vents or other heat or cool sources The sensor should be mounted approximately 10 feet above ground level Adhere the...

Page 4: ...op between the Secondary Loop and the Boiler Loop The VSP Elite will control the Injection Pump up to a maximum output of 1 2 Amp 1 8 HP i e B G NRF 33 Taco 0010 Grundfos 26 64 or equivalent The pump...

Page 5: ...ng The Injection Pump and pipe size selection MUST be done properly by a qualified engineer or trained technician to insure proper operation and prevent excessive or under heat zones as well as hazard...

Page 6: ...n the Default Screen is displayed pressing the SET Button views the MENU When in the Menus and settings the SET Button accepts the selected entry or setting value When in the menus pressing the Up and...

Page 7: ...et SYS Temp 1 100 F CONTROL MODE Outdoor Reset Set Point OUTDOOR RESET Reset Ratio 7 Offset 0 F Cutoff 60 F Min Tgt 120 F Max Tgt 200 F Back Cutoff 70 F Reset Ratio O S Custom 1 8 00 1 00 2 4 00 1 00...

Page 8: ...Output On Output Off Sensor Fault Options Output On Output Off Default Output On SET System Startup Sensor Fault The Sensor Fault will determine the operating status of the output relays when a senso...

Page 9: ...factory defaults all control settings will be over written and will no longer exist Default Display The default display will show the current Secondary Loop System temperature and the Target temperatu...

Page 10: ...election to 1 25 O 1 00 S The Custom option gives the user the capability of creating a specialized Reset Ratio curve Setting two points on the Reset Ratio chart generates the customized curve Each po...

Page 11: ...utdoor Cutoff setting screen will automatically appear after the temperature Set Point has been selected and saved Cutoff 60 F The outdoor and its cutoff temperatures can be viewed from the default sc...

Page 12: ...losing shorting the P terminals using an external timer N O S P S T Output Wiring 120VAC Power Wiring 120VAC Power Source BLACK BLACK Boiler Output Wiring N O YELLOW T1 T2 T3 COM COM T3 EXT EXT P P CO...

Page 13: ...50 Minimum Speed Adjustment Options From 5 to 5 Default 0 T T T T T SET Maintenance Min Speed This is the slowest speed at which the VSP Elite is allowed to run the Injection Pump The VSP Elite will...

Page 14: ...at the boiler or other hot water source is providing hot water to the Boiler Loop and no valve obstruction between the Boiler Loop and the Injection Loop Check that the Injection Pump is running by me...

Page 15: ...Secondary Loop Pump Heat Load Balancing Valve T1 T2 COM COM T3 T3 EXT EXT P P System Sensor Outdoor Sensor Enable Dry Contact Setback Dry Contact Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R...

Page 16: ...ve Maximum 1 8HP at 120VAC 50 60Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Setback from 0 F 0 C to 80 F 44 C Boost Yes 30Mi...

Reviews: