background image

2

INSTALLATION

Mounting the Controller

• The Digi-Span is designed to mount on a 1900 (4”x4”) electrical box.
• If the Digi-Span is to be panel mounted, or if additional room is needed for wiring, an extension skirt is available

*

.

• Locate the Digi-Span in a convenient location near the unit to be controlled.
• Mount the Digi-Span away from excessive heat or cold.  Ambient operating temperature is from 20 to 120°F.
• After completing all the wiring connections (see below) use the two screws provided to mount the Digi-Span to the 1900 box.

Installing the Pressure Sensor

•

Attach a 1/4” brass isolation tube (pigtail) to the steam header.

• Screw the pressure sensor to the pigtail.  The sensor has 1/4"NPT tapered threads.
• The BLACK and RED sensor wires can be extended up to 500’ by splicing with 18 gauge shielded wire.  Any other sensor

wires (green, white, or shield) and the tube are not used and do not need to be extended.

• Do not run wires in conduit with line voltage.
• The Digi-Span will operate based on the pressure it reads at the sensor location.  Therefore, select a sensor location which is

representative of the entire system.

Wiring the Sensor

• The BLACK wire from the pressure transducer should be connected to the terminal marked 

SENSOR -

.

• The RED wire from the pressure transducer should be connected to the terminal marked 

.

• The transducer wires can also be connected to the back of the Digi-Span using the Rear Wire connector

*

.  Connect the

BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire.

Wiring the Power - Digi-Span can use either 120VAC or 24VAC

120VAC

• Attach line voltage to the two blue wires extending from the back of the Digi-Span.
• Use wire nuts, or wrap the connections with electrical tape.
• Class 1 voltages must enter the enclosure through a different opening from any Class 2 wiring.

24VAC

• Use a dedicated transformer with at least a 5VA output.
• Bring 24VAC to the two screws on the front of the Digi-Span marked 

24VAC.

• 24VAC can also be connected to the rear of the Digi-Span using the Rear Wire connector

*

.  Connect the 24VAC to the violet

and gray Rear Wires.

WARNING

The Digi-Span can accept only one source of power: 120VAC or 24VAC.  If more than one power source is
applied, the unit may be damaged.

Wiring the Output

• The Digi-Span has two SPST (single pole single throw) relay outputs rated at 10A, 1/8 HP.
• The outputs are dry contacts only.  They do not source any power.
• The Black wires are the N.O. (normally open) contacts for Output 1.
• The Red wires are the N.O. (normally open) contacts for Output 2.
• If the outputs are carrying any Class 1 voltages, then they must enter the enclosure through a different opening from any

Class 2 wiring.

*

 The Optional Mounting Kit includes the extension skirt, the Rear Wire connector with four wires (orange, yellow, violet, and

gray) and an input terminal cover.  Order separately as HT #908520.

Summary of Contents for Digi-Span TSC Pressure

Page 1: ...nstallation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer wa...

Page 2: ...cer wires can also be connected to the back of the Digi Span using the Rear Wire connector Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire Wiring the...

Page 3: ...TSC TSR only If the display shows H then the Digi Span will be in a heating mode The relays will close when the pressure is below the set point see Example on pg 6 If the display shows C then the Digi...

Page 4: ...2 is energized or open as shown in the Example When Output 2 is energized the Red output wires will be continuous When Output 2 is open the Red output wires will be open To adjust Set Point 2 use the...

Page 5: ...e display will flash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice for the sensor pressure to b...

Page 6: ...ed and will switch again every 24 hours To adjust Set Point 2 use the following steps 1 Digi Span should be displaying sensor pressure 2 Press the center button twice and release it The display will c...

Page 7: ...ash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice to display sensor pressure immediately Offset...

Page 8: ...UTPUT Red Light does not indicate desired stages are active Check the set points and differential values In a heating application the stage will not come on until the pressure drops below the set poin...