background image

15

3

Installing the Fireplace

Step 1. Locating the Fireplace

Space and clearance requirements for locating a fireplace
within a room (see Figure 4).

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ................................... 36 ........ 914
Floor .............................................. 0 .......... 0
Rear ............................................. 1/2 ........ 13
Sides ............................................ 1/2 ........ 13
Top  (SL-550TR-C) ....................... 1 1/2 ....... 38
       (SL-750TR-C & SL-950TR-C) . 3 1/4 ....... 83
Ceiling* ......................................... 31 ........ 787

For minimum clearances, see the direct vent termination
clearance diagrams in Figures 29 and 30 in this manual.

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. ............ 1 ............... 25

Horizontal Sections

Top .................................. 3 ............... 75

Bottom ............................. 1 ............... 25

Sides ............................... 1 ............... 25

At Wall Firestops

Top ................................ 2 1/2............ 63.7

Bottom ............................ 1/2 .............. 13

Sides ............................... 1 ............... 25

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure  38).

The distance from the unit to combustible construction is to
be measured from the unit outer wrap surface to the com-
bustible construction, 

NOT

 from the screw heads that se-

cure the unit together.

1/2 “ MIN. (13mm)

C

3” MIN. (76mm)

A

B

D

E

Clearance Requirements

The top and back of the fireplace are defined by stand-offs.
The minimum clearance to a perpendicular wall extending
past the face of the fireplace is 3 inches (76mm). The back
of the fireplace may be recessed 16 1/4 inches (413mm)
into combustible construction.

   Figure 4.    Fireplace Dimensions, Locations,
                     and Space Requirements

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the
gas fireplace and/or its vent system. Vertical vents that run
on the outside of a building may be, but are not required to
be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND
CONSTRUCTION OF THE CHASE MAY VARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-
ING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in the
manner of all outside walls of the home to prevent cold air
drafting problems. The chase should not break the outside
building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever
floor of the chase should be insulated. Vapor and air infiltra-
tion barriers should be installed in the chase as per regional
codes for the rest of the home. Additionally, Heat-N-Glo rec-
ommends that the inside surfaces be sheetrocked and taped
for maximum air tightness.

To further prevent drafts, the firestops should be caulked to
seal gaps. Gas line holes and other openings should be
caulked or stuffed with insulation. If the unit is being in-
stalled on a cement slab, we recommend that a layer of
plywood be placed underneath to prevent conducting cold
up into the room. Be sure to include spark arrestors for
woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL
CLEARANCES  TO THE FIREPLACE  ARE  MAINTAINED
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

NOTE: For SL-950TR-C ONLY: 

When venting with a 90

0

elbow as the first vent component, an area 3” above the
horizontal vent, the entire width and depth of the firebox
must be free of combustibles (see Figure 5).

*

NOTE

:

  If venting with (2) 90

0

 elbows off rear of unit

                 the dimensions C, D, and E, will change.

MODEL

VENTING

A

B

C

D

E

SL-950TR-C

Top

49

16-1/4

35-3/8

50

70-3/4

Rear

49

16-1/4

40-1/8

57

80-1/4

SL-750TR-C

Top

42

16-1/4

31-7/8

45

63-3/4

Rear

42

16-1/4

36-5/8

52

73-1/4

SL-550TR-C

Top

37

16-1/4

29-3/8

41-1/2

58-3/4

Rear

37

16-1/4

34-1/8

48-1/2

68-1/4

*

*

*

Summary of Contents for SL-550TR-C

Page 1: ...TH APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use w...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...t System Approvals 19 B Installing Vent Components 29 C Vent Termination 32 Step 4 Positioning Leveling and Securing the Fireplace 35 Step 5 The Gas Control Systems 35 Step 6 The Gas Supply Line 36 St...

Page 4: ...o Quality Systems registered by SGS ICS Appliance Certification The Heat N Glo fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the applica...

Page 5: ...nefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the fo...

Page 6: ...8 1007mm 22 559mm 43 1092mm 48 1218mm 41 7 8 1063mm 43 1092mm 2 3 16 55mm 5 1 16 129mm 6 5 8 168mm 37 5 8 956mm0 18 7 8 478mm 1 2 13mm 16 1 4 414mm 8 3 4 223mm 15 11 13 402mm RATING PLATE LABELS GAS...

Page 7: ...391mm 15 7 8 403mm 36 1 8 917mm 40 7 8 1039mm 3 9 16 90mm ELECTRICAL ACCESS 37 7 8 961mm 8 203mm 6 5 8 168mm 16 3 8 416mm 8 13 16 224mm 1 2 13mm 20 3 4 526mm 6 7 8 174mm 40 1016mm RATING PLATE LABELS...

Page 8: ...1 1 8 790mm 2 3 16 55mm 5 1 16 129mm GAS LINE ACCESS 31 790mm 36 913mm 6 7 8 174mm ELECTRICAL ACCESS 32 9 16 828mm 8 203mm 6 5 8 168mm 17 1 4 438mm 3 9 16 90mm 36 7 16 925mm BOTTOM GRILLE COVER ELECTR...

Page 9: ...TION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMI...

Page 10: ...C Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace facing material T...

Page 11: ...T Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6 12 DVP12 2 MIN D...

Page 12: ...nner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3 4 23...

Page 13: ...d with each vent termination kit and should be used in conjunction with this Installers Guide Figure 8 shows vent system components and terminations The vent systems installed on this gas fireplace ma...

Page 14: ...tion Figure 9 requires only enough support to main tain the necessary clearance to combustibles However the vent attachment point and the firestop location are consid ered to be supports 3 CLEARANCE T...

Page 15: ...MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52m 16 FT 4 8m VENTING WITH ONE 1 90o ELBOW PROPANE H MAX 16 FT 4 8m...

Page 16: ...MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 8m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 16 MAX 4 8m Figure 14 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 91...

Page 17: ...FT 2 48m 8 FT 2 48m 16 FT 4 8m 16 FT 4 8m MODEL SL 550TR C V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT...

Page 18: ...FT 2 48m 8 FT 2 48m 16 FT 4 8m 16 FT 4 8m MODEL SL 550TR C V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52...

Page 19: ...m 8 MAX 2 48m 16 MAX 4 8m V1 V H H1 40 MAX 12 4m H 8 MAX 2 48m H H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3...

Page 20: ...m VENTING WITH THREE 3 90o ELBOWS NATURAL GAS V H V1 H1 MAX 40 FT 12 2m VENTING WITH THREE 3 90o ELBOWS PROPANE MODEL SL 550TR C MODEL SL 750TR C MODEL SL 950TR C V MIN H MAX H H1 MAX H MAX H H1 MAX H...

Page 21: ...T 1 22m 6 FT 1 86m 6 FT 1 86m 8 FT 2 48m 8 FT 2 48m 16 FT 4 8m 16 FT 4 8m MODEL SL 550TR C V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1...

Page 22: ...AND PROPANE GAS V H V2 V1 H1 NOTE There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installa tion see Figure 9 Use SL D Series components only V MIN...

Page 23: ...CHED TO THE TOP STARTING COLLARS SEE FIGURE 21 WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD NEGATIVELY AFFECT FIREPLACE PERFORMANCE WARNING YOU MUST LEAVE THE INSULA...

Page 24: ...install support brackets for horizontal runs Place the pipe supports around the vent pipe Nail the pipe supports to the framing members WALL BRACKET WALL STUD 1 INCH MIN 25 4mm 8 FT 2 4m FLUE OUTLET I...

Page 25: ...ition the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the firestops MUST BE placed to wards the top of the hole Continue the v...

Page 26: ...pezoid Termination Cap 7 1 4 184mm WARNING THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINT ING UP WARNING VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SID ING VENT TERMINAT...

Page 27: ...one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes...

Page 28: ...THE TERMI NATION CAP IS AT LEAST TWO 2 FEET 20 INCH ES FOR DVP PIPE FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outs...

Page 29: ...IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with this model Standing Pilot Ignition and Intermittent Pilot Ignition IPI Standing Pilot Ignition System This system includes...

Page 30: ...ebox Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the control so that the lines are not bent or torn...

Page 31: ...y installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch...

Page 32: ...I Wiring Diagram Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Wall Switch Position the wall switch in the desired position...

Page 33: ...ce CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON...

Page 34: ...r ports Cover the top of the burner with a single layer of ember material For best performance do NOT place embers on the ports at the rear of the burner see Figure 42 Save the remaining ember materia...

Page 35: ...o whom the product is delivered Some local building codes require the use of tempered glass with permanent marking in such locations Glass meeting this requirement is available from the factory Please...

Page 36: ...an Task Make a visual check of the straight flame sensor rod Use steel wool or fine sandpaper to carefully remove any existing white deposits Checking Flame Patterns Flame Height Frequency Periodicall...

Reviews: