HST-38 SERIES INSTALLATION INSTRUCTIONS
14. Install the Outside Air Kit
This fireplace is equipped to accept outside
combustion air if desired or required by local code. It
is recommended that the outside air system be used
whenever practical. The AK-225 Outside Air Kit consists
of one house vent, two plastic ties and one starting
collar.
UL Listed Class I, 4 in. flexible air duct should be
installed to bring outside air from the exterior of the
structure to the fireplace. The house vent should be
installed on the exterior of the structure. It must not
draw air from attic spaces, garage spaces, or other
areas that may contain combustible fumes.
The outside air kit inlet thimble should be positioned
at least 4 ft above the ground level, in a manner that
will not allow snow, leaves, etc. to block the inlet.
15. Install the Fan Kit
An optional fan kit, Model # FK-200 is available for the
HST-38 Series fireplace. Detailed installation
instructions are provided with the FK-200 Fan Kit.
A 110 volt AC switch electrical service must be
connected to the fan kit system by a licensed
electrician. See Figures 14-15 for the wiring diagram
and fan mounting illustration.
Note:
An HST-38 series fireplace installed in a
manufactured home requires 6 in. duct for outside
WARNING!
All electrical wiring and connections must con-
form to local codes and/or with the National
Electric Code, ANSI/NFPA No. 70-(current). All
electrical connections must be made by a li-
censed electrician.
Figure 14 - Blower Wiring
Figure 15 - Fan Mount
Note:
A 12 in. x 12 in. hole must be provided in the
adjacent finished wall to access the FK-200 Fan
Kit. See Figure 3, Framing the Fireplace.
Note:
The electrical junction box is mounted on
the fan.