background image

25

Figure 27.  Ceiling Firestop (Ceiling Side)

If the area above the ceiling 

IS

 an attic, position and secure

the firestop on top of the previously framed hole.

NOTE: Keep insulation away from the vent pipe at least
1 inch (25mm).

Figure 28.    Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

Figure 29.  Trapezoid Termination Cap

7 1/4”

(184mm)

!

C.  Vent Termination

Refer to Cinch Pipe and Termination Cap installation in-
structions.

Horizontal Termination

The termination kit should pass through the wall firestops
from the exterior of the building.

Adjust the termination cap to its final exterior position
on the building and interlock the flue sections.

!

WARNING:  VENTING TERMINALS SHALL
NOT BE RECESSED INTO A WALL OR SID-

ING.  VENT TERMINATION CLEARANCES MUST
BE FOLLOWED TO  AVOID FIRE DANGER. SEE
VENT TERMINATION MINIMUM CLEARANCES DI-
AGRAM ON FOLLOWING PAGE.

WARNING:  THE TERMINATION CAP MUST BE
POSITIONED SO THAT THE ARROW IS POINT-
ING UP.

Summary of Contents for 8000TRD

Page 1: ...This appliance may be installed in an af termarket permanently located manufac tured mobile home where not prohibited by local codes 2 This appliance is only for use with the type of gas indicated on...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...m 14 A Vent System Approvals 14 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 The Gas Control Systems 28 Step 6 The Gas Supply...

Page 4: ...sence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting...

Page 5: ...Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the followin...

Page 6: ...26mm 43 1091mm 48 3 8 1229mm 26 7 8 681mm 36 3 4 932mm 8 3 8 212mm 3 1 2 89mm 29 1 8 740mm 8 203mm ELECTRICAL ACCESS 8 203mm 21 1 2 548mm 11 3 4 297mm 35 1 2 902mm 17 3 4 450mm TOP STANDOFFS TOP VENT...

Page 7: ...ucture built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be installed inside a chase CAUTION TREATMENT OF FI...

Page 8: ...cing material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 10 x 12 ven...

Page 9: ...cations 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHES AT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6 12 DVP12 2 MIN DVP12A...

Page 10: ...ing Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in vent configura tions usi...

Page 11: ...ng the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces Do this by bending the part...

Page 12: ...chart to find the appropriate position to set the Flue Restrictor see Figure 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 4 Center the Flue Restrictor on vent and secure in place by using two self tappin...

Page 13: ...BOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX 6 2m Figure 13 Venting with One 90...

Page 14: ...AX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 20 MAX 6 2m Figure 15 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H1 FT 1 MIN...

Page 15: ...enting with Two 90 Elbows V H H1 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8 MAX 2 48 m H H1 8 MAX 2 48 m V H H...

Page 16: ...X 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m 10 MAX 3 1...

Page 17: ...mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m H...

Page 18: ...te gasket material 1 Attach the First Vent Component to the Starting Collars To attach the first vent component to the starting collars of the fireplace Make sure that the fiberglass gasket supplied i...

Page 19: ...airspace between the shield and the combustible surface See Figure 22 HEAT SHIELD 3 MIN 76mm COMBUSTIBLE SURFACE COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 23 If the combustible m...

Page 20: ...must be NO INSULATION or other combustibles inside the framed firestop opening 10 12 INTERIOR WALL SHIELD For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which...

Page 21: ...re 29 Trapezoid Termination Cap 7 1 4 184mm C Vent Termination Refer to Cinch Pipe and Termination Cap installation in structions Horizontal Termination The termination kit should pass through the wal...

Page 22: ...one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes...

Page 23: ...d to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it meets the roof Attach a storm col...

Page 24: ...valve standing pilot thermopile thermocouple flame sensor and piezo ignitor WARNING 1 10 120 V AC MUST NEVER BE CONNECTED T O A CONTROL VALVE IN A MILLIVOLT SYSTEM Intermittent Pilot Ignition IPI Sys...

Page 25: ...bustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe...

Page 26: ...switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 1 10 120 V...

Page 27: ...o black The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional remote control kits require tha...

Page 28: ...BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL...

Page 29: ...ave the log instructions with this manual If sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs and Ember Material Placing...

Page 30: ...e the products used in the paint and logs Glass Specifications 8000TRD TEMPERED Heat N Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclo sur...

Page 31: ...ght flame sensor rod see Figure 33 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician H...

Reviews: