Heat-N-Glo 6000TRS-CE Installer'S Manual Download Page 40

40

Standing Pilot Troubleshooting

Symptom

1. After repeated

triggering of the red
or black piezo
button, the spark
ignitor will not light
the pilot.

2. The pilot will not stay

lit after carefully
following the lighting
instructions.

3. The pilot is burning,

there is no gas
burner, the valve
knob is in the ON
position, and the
ON/OFF switch is in
the ON position.

Possible Cause

a. Defective ignitor

b. Defective pilot or

misaligned
electrode (spark at
electrode)

c. No gas or low gas

pressure

d. No LP in the tank

a. Defective

thermocouple

b. Defective valve

a. ON/OFF switch or

wires defective

b. Thermopile may

not be generating
sufficient
millivoltage

Corrective Action

Check the spark at the electrode and
pilot. If no spark and electrode wire is
properly connected, replace the ignitor.

Using a match, light the pilot. If the
pilot lights, turn off the pilot and
trigger the red or black piezo button
again. If the pilot lights, an improper
gas/air mixture caused the bad
lighting and a longer purge period is
recommended. If the pilot will not
light, ensure that the gap at the
electrode and pilot is 0.3 cm to have
a strong spark. If the gap is OK,
replace the pilot.

Check the remote shut-off valves
from the fireplace. Usually, there is a
valve near the gas main. There can
be more than one (1) valve between
the fireplace and the main.

Check the LP (propane) tank. You
may be out of fuel.

Check that the pilot flame impinges
on the thermocouple. Clean and/or
adjust the pilot for maximum flame
impingement.

Ensure that the thermocouple
connection at the gas valve is fully
inserted and tight (hand tighten plus
1/4 turn).

Disconnect the thermocouple from
the valve, place one millivolt meter
lead wire on the tip of the
thermocouple and the other meter
lead wire on the thermocouple
copper lead. Start the pilot and hold
the valve knob in. If the millivolt
reading is less than 15mV, replace
the thermocouple.

If thermocouple is producing more
than 15 millivolts, replace faulty valve.

Check the ON/OFF switch and wires
for proper connections. Place the
jumper wires across the terminals
at the switch. If the burner comes on,
replace the defective switch. If the
switch is OK, place the jumper wires
across the switch wires at the gas
valve. If the burner comes on, the
wires are faulty or connections are
bad.

If the pilot flame is not close enough
physically to the thermopile, adjust
the pilot flame.

Be sure the wire connections from
the thermopile at the gas valve
terminals are tight and that the
thermopile is fully inserted into the
pilot bracket.

5

Trouble-
shooting

With proper
installation,
operation, and
maintenance your
gas fireplace will
provide years of
trouble-free
service.  If you do
experience a
problem, this
troubleshooting
guide will assist a
qualified service
person in the
diagnosis of a
problem and the
corrective action to
be taken. This
troubleshooting
guide can only be
used by a
qualified service
technician.

Summary of Contents for 6000TRS-CE

Page 1: ...tions or concerns For the number of your nearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2004 Heat N Glo a brand of Hearth Home Technologies Inc 20802 Kensington Blvd L...

Page 2: ...ung children should be CAREFULLY SUPERVISED when they are in the same room as the appliance These units MUST use one of the fluing systems described in the Installing the Fireplace section of the Inst...

Page 3: ...em Approvals 12 B Installing Flue Components 20 C Flue Termination 24 Step 4 Positioning Leveling and Securing the Fireplace 29 Step 5 The Gas Control Systems 29 Step 6 The Gas Supply Line 30 Step 7 G...

Page 4: ...list on following page 9 Log Set Assembly NG LP Exploded Parts Diagram Service Parts 6000TRS CE Beginning Manufacturing Date 1 04 Ending Manufacturing Date ______ 2 3 4 6 8 7 15 1 5 10 11 12 13 14 19...

Page 5: ...027 731 18 Right Wall Refractory SRV2027 732 19 Insulation Board 385 401 20 Exhaust Baffle 2049 101 Flue Gasket 2026 114 Pilot Orifice NG 529 512 Insulation Mineral Wool 050 721 ACCESSORIES Extended V...

Page 6: ...ITEM DESCRIPTION SERIAL PART NUMBER 1 Pilot Assembly NG 529 510A 2 Pilot Bracket 2049 105 3 Orifice NG 33 582 833 4 30 5 cm Flex 383 302A 5 Burner Neck Gasket 438 407 6 Valve Plate Gasket 385 402 7 Va...

Page 7: ...STANDARD 6000TRS CE Advantica Gas Fireplace 90 396 EEC Installation Regulations Before installation check that local distribution conditions nature of gas and pressure and adjustment of the appliance...

Page 8: ...ctions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warr...

Page 9: ...accessories devices such as a fan wall switch or remote control are desired If the fireplace is to be installed on carpeting or tile or on any combustible material other than wood flooring the firepl...

Page 10: ...ined by stand offs The minimum clearance to a perpendicular wall extending past the face of the fireplace is 7 62cm The back of the fireplaces may be recessed into combustible construction see Figure...

Page 11: ...HIND THE FRONT HEADER OF THE FIREBOX A B C A B C D E 42 38 1 2 22 26 7 8 41 3 4 106 7cm 97 8cm 55 9cm 68 3cm 106 0cm Figure 4 Framing Dimensions Fireplace framing can be built before or after the fire...

Page 12: ...with this Installers Guide Figure 4 shows flue system components and terminations Identifying Flue Components The flue systems installed on this gas fireplace may include one two or three 90 elbow ass...

Page 13: ...anced Flue Component Specifications 127 mm inner pipe 203 mm outer pipe DVP90ST 31 9cm 28 6cm 18 4cm 3 2cm TYP 1 3cm TYP 21 7cm DVP36 DVP48 121 9cm 61 0cm 91 4cm 10 2cm 15 2cm DVP4 DVP6 30 5cm DVP12 5...

Page 14: ...14 STRAIGHT UP VERTICAL FLUE Figure 7 Straight up Vertical Flue Figure 8 Straight Out Horizontal Flue V CAP H V 11 8 m MAX STRAIGHT OUT HORIZONTAL FLUE H H MIN RUN MAX RUN 13 1 33 2 cm 24 61 0 cm...

Page 15: ...pipe to clear the top standoffs NOTE If a 90o elbow is first attached to the unit the maximum horizontal run is 3 feet 91 4cm V H H V FLUE WITH ONE 1 90o ELBOW V H MIN 30 5 cm MAX 61 0 cm MIN 61 0 cm...

Page 16: ...Two 90 Elbows H1 V H FLUE WITH TWO 2 90 ELBOWS V H H H1 MIN 30 5 cm MAX 61 0 cm MAX 1 22 m MIN 61 0 cm MAX 61 0 cm MAX 2 48 m MIN 91 4 cm MAX 1 22 m MAX 3 72 m MIN 1 22 m MAX 1 8 m MAX 4 9 m MAX 6 1...

Page 17: ...2 Flue with Two 90 Elbows H1 H V V V1 H MIN 30 5 cm MAX 1 22 m MIN 61 0 cm MAX 2 4 m MIN 91 4 cm MAX 3 7 m MIN 1 22 m MAX 4 9 m V H H1 MAX 11 8m H H 1 MAX 4 9m V V1 H1 MAX 12 97m FLUE WITH TWO 2 90 EL...

Page 18: ...m MAX 2 48 m MIN 91 4 cm MAX 1 86 m MAX 3 6 m MIN 1 22 m MAX 2 48 m MAX 4 9 m H MAX 2 48 m MAX 4 9 m NOTE V V1 H H1 MAX 10 97 m V H H H1 V H H H1 H2 MIN 30 5 cm MAX 61 0 cm MAX 1 22 m MIN 61 0 cm MAX...

Page 19: ...MIN 61 0 cm MAX 2 4 m MIN 91 4 cm MAX 3 7 m MIN 1 22 m MAX 4 9 m V V1 H H1 MAX 10 97 m H H1 MAX 4 9 m FLUE WITH THREE 3 90 ELBOWS V H H1 MIN 30 5 cm MAX 1 22 m MIN 61 0 cm MAX 2 4 m MIN 91 4 cm MAX 3...

Page 20: ...STEM IS ATTACHED TO THE REAR STARTING COLLARS SEE FIGURE 15 Venting Out the Top Flue Remove the top flue collar seal cap by cutting the strap on each end Remove both pieces of insulation inside the to...

Page 21: ...o con firm that it has completely locked into place Slide the ceramic fiber pad over the first flue section and place it flush to the fire place Continue to add vent components FIGURE 16 WARNING ENSUR...

Page 22: ...al Runs Firestops are REQUIRED on both sides of a combustible wall through which the flue passes To install firestops heat shield for horizontal runs that pass through either interior or exterior wall...

Page 23: ...drive a nail through this center point Check the floor above for any obstructions such as wiring or plumbing runs Reposition the heater and flue system if necessary to accommodate the ceiling joists...

Page 24: ...of the previously framed hole IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR KIT VPK DV TO THE TOP OF THE EXTERIOR FIRESTOP FOR ALL ROUND TERMINATION...

Page 25: ...through the wall firestops from the exterior of the building Adjust the termination cap to its final exterior position on the building and interlock the flue sections WARNING THE TERMINATION CAP MUST...

Page 26: ...Flashing anchored to the frame must withstand heavy winds Continue to install concentric flue sections up through the roof hole and up past the roof line until you reach the appropriate distance above...

Page 27: ...12 244 TERMINATION CAP WARNING FOLLOW NA TIONAL REGULATIONS AND CODES OF PRACTICE FOR MINIMUM CLEARANCES FROM GAS TERMINALS AND PLACEMENT OF GAS TERMINAL NOTE This also pertains to vertical flue syste...

Page 28: ...en You must follow all side walls over hang and ground clearances as stated in the instructions Heat N Glo assumes no responsibility for the improper perfor mance of the appliance when the venting sys...

Page 29: ...m the fireplace with non combus tible material such as sheet metal as necessary 4 Secure the fireplace to the framing by nailing or screwing Figure 26 Proper Positioning Leveling and Securing of a Fir...

Page 30: ...ding to the Rp 1 2 hook up at the unit This gas inlet connection is ISO 7 Rp 1 2 BSP Rp 1 2 To install the gas supply line When attaching the pipe support the control so that the lines are not bent or...

Page 31: ...__ Natural Gas Propane Butane Natural Gas G20 G31 G30 G25 Inlet Pressure 20mbar 37 or 50mbar 30 or 50mbar 25mbar Manifold Pressure 4 8 7mbar 15 7 25mbar 15 7 25mbar 4 8 7mbar Gas Rate 54 m3 h 24 m3 h...

Page 32: ...tical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace See Figures 2 3 and 4 for other fireplace clearanc...

Page 33: ...E FINISHED W ALLS AND THE FIREPLACE SURROUND TOPAND SIDES ARE SEALED A 150 C MINIMUM SEALANT MATERIAL MUST BE USED THESE JOINTS ARE NOT RE QUIREDTOBESEALED ONLYNONCOMBUSTIBLE MATERIAL USING 150 C MINI...

Page 34: ...lace log 1 at the rear of the unit against the rear grate tabs with the notches on the bottom of the log lining up with the grate bars LOG 2 SRV2049 701 Locate the bottom grooves of log 2 over the sec...

Page 35: ...ove on log 1 with its front next to the left side of the log grate as shown LOG 5 SRV385 722 Push log 5 against the grate tabs on the 5th grate bar and rest its top in the groove on log 1 3 4 5 If soo...

Page 36: ...he Ember Material Figure 33 Glass Assembly LATCHES BOTH TOP AND BOTTOM GLASS ASSEMBLY Place small pieces of ember material on burner top Figure 34 Do NOT press embers into burner ports Cover the top o...

Page 37: ...s to purge themselves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the ga...

Page 38: ...ed Brush or vacuum the control Burner Service compartment and burner areas Controls Technician surrounding the logs Checking Periodically Qualified Make a visual check of your fireplace s Flame Servic...

Page 39: ...39 STANDING PILOT Figure 35 Burner Flame Patterns MAKE SURE THE FLAMES ARE STEADY NOT LIFTING OR FLOATING Figure 36 Pilot Flame Patterns...

Page 40: ...may be out of fuel Check that the pilot flame impinges on the thermocouple Clean and or adjust the pilot for maximum flame impingement Ensure that the thermocouple connection at the gas valve is fully...

Page 41: ...nimum With the pilot in the ON position disconnect the thermopile leads from the valve Take a reading at the thermopile leads The reading should be 325 millivolts minimum Replace the thermopile if the...

Page 42: ...flue cap should slope down only enough to prevent any water from entering the unit The maximum downward slope is 0 6 cm Tighten the corner Replace if necessary Check for proper installation and freed...

Reviews: