22
d##
Function
Values
Definition
Default
d00
Select °C/°F
0
°C
0
1
°F
d01
Heating Control
0
PWM (pulse width modulation)
0
1
On-Off 0.9°F (±0.45°F)
On-Off: 0.5°C (±0.25°C)
2
On-Off 1.8°F (±0.9°F)
On-Off: 1.0°C (±0.5°C)
d02
Room Temp Offset
26.5°F to 37.5°F
(-5.5°F to 5.5°F)
-3.0°C to +3.0°C
Offset room temp measuring error (in 0.9°F /
0.5°C)
32°F
(0°F)
0.0°C
d03
Remote Sensor
(S1/S2)
0
Remote sensor not connected
0
1
Remote sensor connected
d04
Remote Sensor Type
(d03 must be set to 1)
0
The remote sensor is used to read the air or floor
temperature. The thermostat's internal sensor will
no longer operate.
0
1
The remote sensor is used for floor protection,
and the air temperature is measured by the
thermostat's internal sensor.
d05
Cooling Control
1
On-Off 0.9°F (±0.45°F)
On-Off: 0.5°C (±0.25°C)
2
2
On-Off 1.8°F (±0.9°F)
On-Off: 1.0°C (±0.5°C)
11. Functions explained