background image

 

5

 

 

HD25Bi 22/09/15 

 

4.0

 

Installation Information 

 
Chimney 

The chimney height and the position of the chimney terminal should conform to Building Regulations. 
Minimum chimney height is 4.5m. Check that the chimney is in good condition, dry, free from cracks and 
obstructions. The diameter of the flue should not be less than 150mm and not more than 200mm. If any of 
these requirements are not met, the chimney should be lined by a suitable method. The chimney must be 
swept before connection to the stove. 
 
Where the chimney is believed to have previously served an open fire installation, it is possible that the 
higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with 
the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a second time 
within a month of regular use after installation. 
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist or chimney 
specialist. If there is no existing chimney then either a solid fuel compatible prefabricated block chimney or 
a twin-walled insulated stainless steel flue to BS 4543 can be used. These chimneys must be fitted in 
accordance with the manufacturer’s instructions and Building Regulations. 
 

Ventilation 

No purpose provided ventilation is required for stoves rated under 5KW. For each KW above 5KW, 550 sq 
mm of fixed ventilation is required – i.e. a stove rated at 8KW would require 3 x 550 sq mm = 1650 sq mm 
of fixed ventilation. If more than one appliance is installed in the same room, the ventilation requirements 
for each appliance must be added together.  
 

Flue Draught  

A flue draught of minimum 1.6mm to a maximum 2.5mm water gauge (16 to 25 Pascals) is required for 
satisfactory appliance performance. The flue draught should be checked under fire at high output and, if it 
exceeds the recommended maximum, a draught stabiliser must be fitted so that the rate of burning can be 
controlled to prevent over-firing. 
 

Connection to the Chimney

 

This appliance is 

not

 suitable for use in a shared flue. This appliance requires a direct flue connection to the 

spigot. It is 

essential

 that all connections between the stove and chimney-flue are sealed and made airtight 

with sealing rope, clamping rings and/or fire cement or heat resisting cement where required. 
 
Both the chimney and flue pipe must be accessible for cleaning and if ANY parts of the chimney cannot be 
reached through the stove (with baffle removed), a soot door must be fitted in a suitable position to enable 
this to be done. 
 
In adverse weather conditions, downdrafts may occur causing smoke or fumes to spill into the room. If this 
occurs the appliance should be shut down as much as possible by closing the air controls and the room 
should be ventilated to clear the fumes.  If the problem persists seek the advice of a chimney sweep. 
 

Material Clearances 

 

Safety Distances from Combustible Surfaces: 
Model  

 

 

 

Side 

 

 

Shelf 

HD25Bi 

 

 

 

150mm 

 

550mm 

In addition it is strongly recommended that any furniture or other combustible materials are kept at least 
1000mm clear from the front of the stove. 
 

 
 

Summary of Contents for HD25Bi

Page 1: ...ser in the correct use of the appliance and operation of controls Important This product must be installed by a suitably qualified installer Heat Design Ltd 30 60 Hawthorn Road Western Industrial Esta...

Page 2: ...Material Clearances 5 Hearths 6 Commissioning Handover 6 5 Technical Data 6 6 Plumbing 7 7 Operating Instructions 10 Air controls 10 Cleaning 11 Fuels 13 Notes on Wood Burning 13 Notes on Burning Sol...

Page 3: ...in a similar manner Note the orientation of both baffles before removal Access to the chimney through the front door of the stove is now possible Now proceed to install the stove according to these in...

Page 4: ...connector is fully clear at regular intervals The chimney and flue connector must be swept at least annually more often when used with sooty fuels or damp wood Any loose broken or leaking joints or fl...

Page 5: ...ment are caustic and should not be allowed to come into contact with the skin In case of skin contact wash immediately with plenty of water Asbestos This stove contains no asbestos If there is a possi...

Page 6: ...550 sq mm 1650 sq mm of fixed ventilation If more than one appliance is installed in the same room the ventilation requirements for each appliance must be added together Flue Draught A flue draught of...

Page 7: ...stallation allow a suitable period of time for any fire cement and mortar to dry out A small fire may then be lit and checked to ensure the smoke and fumes are taken from the stove up the chimney and...

Page 8: ...open to the atmosphere Below are several diagrams representing different plumbing circuits These are not working drawings Designs and calculations for individual systems should always be carried out b...

Page 9: ...sed to prevent corrosion or formation of limescale in the heating system Gravity Circuit Do Not Under any circumstances connect the stove to a sealed pressurised heating system or an unvented HW cylin...

Page 10: ...en to the stronger flow typically the pumped circuit Pipe Thermostats A HIGH LIMIT thermostat should be fitted to the gravity flow pipe close to the boiler and set at 90 C This should override any pum...

Page 11: ...ng shut right down for a long period Moving the sliding control towards the wide side of the arrow increases the burn rate whilst moving it towards the narrow side reduces it Multifuel Grate This High...

Page 12: ...nding on the fuel quality and burning rates used Never clean glass when the stove is hot Always use stove glass cleaner or ceramic hob cleaner which is available from your stove retailer As an alterna...

Page 13: ...d hence the burn rate of the stove Firstly remove the thermostat knob by pulling it gently away from the thermostat and then remove the Left Side Casing by undoing the two fixing screws Then clean any...

Page 14: ...of the stack to enable it to dry out Burning wet or unseasoned wood will create tar deposits in the stove and chimney and will not produce a satisfactory heat output Wood that is not properly dry dry...

Page 15: ...f glowing embers and ash that the new fuel charge will ignite in a reasonable period If there are too few embers in the fire bed add suitable kindling to prevent excessive smoke Fuel Overloading Four...

Page 16: ...brackets and pads Carefully replace the broken glass Ensure the sealing rope around the glass is fully intact replace if necessary Replace the glass with genuine high quality stove glass from Heat De...

Page 17: ...ver persistent fume emission is potentially dangerous and must not be tolerated If fume emission does persist then the following immediate action should be taken 1 Open doors and windows to ventilate...

Page 18: ...17 HD25Bi 22 09 15 8 0 Stove Dimensions Fig 7 Heat Design Insert Boiler Stove All dimensions in mm unless otherwise stated Dimensions are approximate and are subject to change without prior notice...

Page 19: ...r attends any stove problem that is not related to product failure 6 Where can I get spare parts Your local Heat Design Stove retailer will be pleased to supply spare parts and to provide any other in...

Page 20: ...9A 47 Rope 5 Y1HDI25B55A 17 Baffle Plate Upper Y1HDI25B20A 60 Grate Bars Y1HDI25B68A 18 Airwash slider plates Y1HDI25B21A 61 Grate bars joining bar Y1HDI18B69A 22 Ashpan Y1HDI25B28A 62 Riddle Handle A...

Page 21: ...20 HD25Bi 22 09 15 Heat Design 30 60 Hawthorn Road Western Industrial Estate Naas Road Dublin 12 T 01 408 9192 F 01 408 9193...

Reviews: