HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A
R e v. : 0 3 A u g u s t , 2 0 1 2
Heat Controller, Inc. Water-Source Heating and Cooling Systems
40
Functional Troubleshooting
No Fault Code Shown
X
X
No compressor operation
See 'Only Fan Operates'
X
X
Compressor overload
Check and replace if necessary
X
X
Control board
Reset power and check operation
Unit Short Cycles
X
X
Dirty air filter
Check and clean air filte r
X
X
Unit in 'Test Mode'
Reset power or wait 20 minutes for auto exit
X
X
Unit selection
Unit may be oversized for space - check sizing for actual
load of space
X
X
Compressor overload
Check and replace if necessary
Only Fan Runs
X
X
Thermostat position
Insure thermostat set for heating or cooling operation
X
X
Unit locked out
Check for lockout codes - reset power
X
X
Compressor overload
Check compressor overload - replace if necessary
X
X
Thermostat wiring
Check thermostat wiring at DXM2 - put in Test Mode and
ESD - ERV Fault (DXM Only)
Green Status LED Code 3
X
X
ERV unit has fault
(Rooftop units only)
Troubleshoot ERV unit fault
jumper Y1 and R to give call for compressor
IFC Fault Code 13
Internal Flow
Controller Fault
X
Improper output setting
Verify the AO-2 jumper is in the PWM position
X
No pump output signal
Check DC voltage between A02 and GND - should be
between 0.5 and 10 VDC with pump active
Low pump voltage
Check line voltage to the pump
No pump feedback signal
Check DC voltage between T1 and GND. Voltage should
be between 3 and 4 VDC with pump OFF, and between
0 and 2 VDC with the pump ON
Bad pump RPM sensor
Replace pump if the line voltage and control signals are
present at the pump, and the pump does not operate
Fault
Htg Clg Possible Cause
Solution