
Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. M • 5/12
42
11
Gas Information
A. Gas Pressure Requirements
Pressure requirements for XLR-AU fireplaces are shown
in Table 11.1 below.
Two taps are provided on the right hand side of the gas
control for a test gauge connection to measure the inlet
and outlet pressures.
The fireplace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 6 kPa.
If the fireplace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)
threaded gas inlet connection on the manual shutoff valve.
Table 11.1
B. Gas Connection
Note:
Have the gas supply line installed in accordance with
local building codes by a qualified installer approved and/or
licensed as required by the locality.
Note:
Before the first firing of the appliance, the gas supply
line should be purged of any trapped air.
Note:
Consult local building regulations to properly size the gas
supply line leading to the (Rp 1/2 in.) hook-up at the unit.
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 6 kPa.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 6 kPa.
Figure 11.1. Valve Components
GAS VALVE
CONTROL
MODULE
ON/OFF/REMOTE
SWITCH
DC ADAPTER
Natural Gas
Propane
Butane
Gas Inlet Pressure
1.13 - 3.40 kPa
2.75 - 3.40 kPa
2.75 - 3.40kPa
Outlet (Manifold) Gas Pressure
.80 - .95 kPa
2.36 - 2.61 kPa
2.36 - 2.61 kPa
Gas Rate
.405
m3
/
h
.134
m3
/
h
.111
m3
/
h
Maximum Gas Consumption
26 MJ/h
26.0 MJ/h
22 MJ/h
Burner Injector
DMS 42 (2.350 mm)
DMS .057 (1.450 mm)
DMS 55 (1.325)
Pilot Injector
51
30
30
Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum
inlet pressure of
3.40 kPa
. For pressures over
3.40 kPa
, an in line pressure regulator must be installed
upstream from the gas control valve.
Leak test all gas line points and the gas control valve prior
to and after starting the gas appliance.
IMPORTANT NOTICE:
(Items 1, 2 and 3 applies to
ALL Heat & Glo gas appliances)
1. 1/2 in. GAS LINE:
Run through cavity 70 mm
above finished hearth level,
NOT RIGID, NOT
CLIPPED,
with minimum 500 mm into cavity and
120 mm back from plaster face.
2. PVC (COMPOSITE) GASLINE
must terminate
minimum 500 mm short of gas heater. Copper pipe
MUST
be the final connection to the gas heater.
3. ISOLATING SWITCH:
Location within 1 metre
of fireplace, subject to mantelpiece etc. Check to
ensure it remains clear of any mantelpiece instal-
lation.