Heat & Glo ST-550T-IPI Owner'S Manual Download Page 39

Heat & Glo  •  ST-550T-IPI  •  2126-900  Rev. H   •  3/13

39

SCREWS

CAULK

STORM 
COLLAR

(1 of 3)

Figure 10.15   

Figure 10.15   

TERMINATION CAP

H.  Install Vertical Termination Cap

•  Attach the vertical termination cap by sliding the inner 

collar of the cap into the inner fl ue of the pipe section  
while placing the outer collar of the cap over the outer 
fl ue of the pipe section.

•  Secure the cap by driving three self-tapping screws 

(supplied) through the pilot holes in the outer collar of the 
cap into the outer fl ue of the pipe (see Figure 10.15).

I.  Install Decorative Wall Components

A decorative wall thimble can be installed on wall through 
which the vent passes. The decorative wall thimble is used 
to cover the wall shield fi restop. 

• 

Slide the decorative wall thimble over the last section of 
horizontal pipe before connecting the termination cap to 
the pipe. 

• 

Once the pipe section and the termination cap have been 
connected, slide the wall thimble up to the interior wall 
surface and attach with screws provided. See Figure 
10.16.

Important Notice:

  Heat shields may not be fi eld constructed.

J.  Heat Shield Requirements for  Horizontal 

Termination

WARNING! Risk of Fire! To prevent overheating and fi re, 
heat shields must extend through the entire wall thick-
ness.

•  DO NOT remove the heat shields attached to the 

wall shield fi restop and the horizontal termination cap 
(shown in Figure 10.21).

• Heat shields must overlap 1-1/2 in. (38 mm) mini-

mum.

There are two sections of the heat shield. One section 
is factory-attached to the wall shield fi restop.  The  other 
section is factory-attached to the cap. See Figure 10.17.

If the wall thickness does not allow the required 1-1/2 in. 
(38 mm) heat shield overlap when installed, an extended 
heat shield must be used.

•  If the wall thickness is less than 4-3/8 in. (111 mm), the 

heat shields on the cap and wall shield fi restop must be 
trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST 
be maintained.

•  Use an extended heat shield if the fi nished wall thickness 

is greater than 7-1/4 in. (184 mm).

•  The extended heat shield may need to be cut to length 

maintaining suffi cient length for a 1-1/2 in. (38 mm) 
overlap between heat shields.

•  Attach the extended heat shield to either of the existing 

heat shields using the screws supplied with the extended 
heat shield.  Refer to vent components diagrams in the 
back of this manual.

•  Rest the small leg on the extended heat shield on top 

of the pipe section to properly space it from the pipe 
section.

Figure 10.16  Wall Thimble

Summary of Contents for ST-550T-IPI

Page 1: ...n the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read unders...

Page 2: ...se utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 in in the the USA USA or or CAN CGA CAN CGA B149 B149 installation installation codes codes Installer Installer l appareil l appareil selon s...

Page 3: ...ppliance and Components 17 5 Framing and Clearances A Selecting Appliance Location 18 B Constructing the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 20 6 Termination Locations A Vent Termination Minimum Clearances 21 B Continue Adding Vent Components 23 C Install Support Brackets 23 7 Vent Information and Diagrams A Approved Pipe 24 B Vent Table Key 24 C Use of Elbows 24 D Mea...

Page 4: ... 50 D Accessories 50 E Lava Rock Mystic Embers and Glowing Ember Placement 50 F Install the Log Assembly 51 G Fixed Glass Assembly 53 H Install Trim Kits and Surrounds 53 I Air Shutter Setting 53 15 Troubleshooting A Intellifire Ignition System 54 16 Reference Materials A Appliance Dimension Diagram 56 B Vent Components Diagrams 57 C Service Parts List 62 D Contact Information 64 ...

Page 5: ...hase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty per...

Page 6: ...IED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other exter...

Page 7: ... surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in reside...

Page 8: ...ating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in accord...

Page 9: ...all one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing f...

Page 10: ...ow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions CLEAR SPACE 3 FT IN FRONT OF FIREPLACE H Before Lighting Fireplace Before operating this fireplace for the first time have a qualified ser...

Page 11: ...building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this appliance This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air ...

Page 12: ...n will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the fireplace is al lowed to burn for 20 to 40 minutes Odor from fireplace When first operated this fireplace may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finishing materials and adhesives used near t...

Page 13: ...red due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Front...

Page 14: ...re is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Logs Frequency Annually By Qualified Service Technician Tools needed Protective gloves Inspectfordamagedormissinglogs Replaceasnecessary Refer to Section 14 for log placement instructions Verify correct log plac...

Page 15: ...tery failure or leaking Check for smooth lighting and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 14 for required air shutter setting Verify air shutter is clear of dust and debris Inspect orifice for soot dirt and corrosion Verify orifice size is correct See Service Parts List ...

Page 16: ...TOP ON FLOOR OF ATTIC SECTION 8 C VERTICAL TERMINATION CAP SECTION 10 C VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 C MANTEL AND MANTEL LEG SECTION 5 D VENT PIPE SECTION 8 and 10 STORM COLLAR SECTION 10 C NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 C FRAMING...

Page 17: ...d parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check solution Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits...

Page 18: ...ngs and for service access Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations 36 in 914 mm 36 in 914 mm ST 550T IP...

Page 19: ...iance on hard metal or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other com...

Page 20: ...3 1 4 in Min 1 2 in Min Unlimited FIREPLACE OPENING D Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear ances as specified Framing or finishing material closer than the minimums listed must be constructed entirely of noncom bustible materials i e steel studs concrete board etc Figure 5 3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Note All measur...

Page 21: ...IN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using decorative cap co...

Page 22: ... A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered Alcove Applications Spac...

Page 23: ...e 6 6 Cut the tabs as shown and bend down Secure the heat shield to the pipe maintaining 3 inch to 4 inch between the pipe and shield Refer to Cinch Pipe and Termination Cap installation in structions Continue adding vent components locking each suc ceeding component into place Ensure that each succeeding vent component is securely fitted and locked into the preceding component in the vent system ...

Page 24: ...ween two 45º elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams Figure 7 2 SLP Pipe Effective Length Symbol Description V1 First section closest to appliance of vertical length V2 Second section of vertical length H1 First section closest to appliance of horizontal length H2 Subsequent se...

Page 25: ...required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 7 3 requires only enough sup port to maintain the necessary clearance to combustibles However the vent attachment point and the firestop loca tion are considered to be supports 1 in CLEARANCE FLEX VENT 3 in CLEARANCE TERM...

Page 26: ...em as long as the first 90 elbow is a starter elbow When penetrating a combustible wall a wall shield firestop must be installed When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level H1 V1 Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out i...

Page 27: ...zontal Termination continued INSTALLED HORIZONTALLY H1 H2 V1 Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow When using DVP TB1 termination...

Page 28: ...ons on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m See Warning Below H2 H1 V2 V1 Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow W...

Page 29: ...tal vertical of 15 50 feet an exhaust restrictor may be needed The exhaust restrictor can be located in the appliance manual bag Exhaust restrictor Instructions 1 Center the exhaust restrictor in the open end of the ex haust outlet and secure through the slots on the exhaust restrictor with the 2 1 4 in self tapping screws provided in the appliance manual bag Note Use SLP Series components only V1...

Page 30: ...x 15 ft 4 6 m V1 V2 H Max 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m V1 Minimum H1 H2 Maximum V2 V1 V2 Min 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H MAX 14 ft 4 6 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value...

Page 31: ...m clearance at wall shield firestops 1 in 25 mm clearance bottom and sides Heat Shields Wall Shield Firestop WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections Figure 8 1 Horizontal venting clearances to combustible materials B Wall Penetration Framing Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firestop ...

Page 32: ...installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 8 3 Installing Ceiling Firestop Figure 8 4 Installing the Attic Shield 3 FASTENERS PER SIDE INSTALL AT...

Page 33: ...used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit your ceiling pitch Snip ...

Page 34: ...tion making sure to maintain proper clearance to combustibles 3 Level the appliance from side to side and front to back It is acceptable to use wood shims under the appliance 4 Fasten the appliance to the floor using the pilot holes located at the bottom of the appliance 5 Bend out nailing tabs on each side making sure to keep the nailing tabs flush with the framing 6 Using a framing square make s...

Page 35: ...ent Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise applications All outer pipe joints must be sealed with silicone with a minimum of 300ºF continuous exposure rating including the slip section that connects directly to the horizontal termina tion cap Apply a bead of ...

Page 36: ...l be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 10 4 Figure 10 5 Securing Vertical Pipe Sections Figure 10 6 Securing Horizontal Pipe Sections C Secure the Vent Sections Vertical runs originating off the top of the appliance w...

Page 37: ...the provided screws Adecorative cathedral ceiling support box can be installed on a cathedral ceiling through which the vent passes Use a plumb bob to mark the center line of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or other roof c...

Page 38: ...g Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Connect both halves of the storm collar with two screws see Figure 10 13 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure the collar is tight ag...

Page 39: ...NING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 21 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other sec...

Page 40: ...the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching th...

Page 41: ... DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulato...

Page 42: ... switched circuit Incorrect wiring will override IPI safety lockout Refer to Figure 12 2 Intellifire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an Intellifire control valve which operates on a 3 volt system Plug the 3 volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery pack before use N...

Page 43: ...C is required at junction box unless equipped with battery back up TRANSFORMER 3 VAC PLUG IN BLACK RED BATTERY PACK WIRE ASSEMBLY WIRES TO BROWN ORANGE GREEN VALVE HOT NEUTRAL GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR I S TRANSFORMER 3 VAC PLUG IN PLUG IN BLACK RED BATTERY PACK REMOTE WIRES TO BROWN ORANGE GREEN VALVE GROUND TO FIREPLACE CHASSIS HOT ...

Page 44: ... NOT wire 110 120 VAC to wall switch Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junction Box Knockout Figure 12 5 Junction Box Wired to Wall Switch E Junction Box Installation The junction box must be wired from the INSIDE of the appliance Determine which side of the appliance the junction box is located on Pu...

Page 45: ...Top Flap Step 3 Crease flaps on left and right sides of splatter guard using the scored line as the guide See Figure 13 2 Step 4 Center the splatter guard in front of the unit as shown in Figure 13 3 Place the splatter guard in the unit by guiding the top flap into proper position and then con tinuing to guide the tabs on the side flaps into the top slot on the left and right sides of the applianc...

Page 46: ...ight bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard carefully bend them down See Figure 13 9 To Close the Lower Access Panel Carefully disengage the tabs from the square holes and bend the access panel to its original position Bend the center bottom flap and insert it into the bottom of the ap pliance To Remove the Splatter Guard...

Page 47: ...ibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of doors and louvers 0 in 0 in 0 in Finish wall material may be combustible Top and Sides High Temperature Sealant 300 F 149 C min Top and Side Seal Joint Figure 13 15 Noncombustible Facing Diagram 5 6 7 8 9 10 3 4 5 12 11 10 9 8 7 6 TOP OF HOOD OR FIREPLACE OPENING MIN MAX 4 12 13 11 32 C...

Page 48: ...he finishing material thickness allowed For an inside fit there is an available template to assist with siz ing the finishing material Stop finishing material flush with opening DOOR FINISHING MATERIAL FINISHING MATERIAL Outside door width Includes 1 8 in opening each side of door 37 in 37 1 4 in Finishing materials between 1 and 4 inches thick Finishing material between 1 and 4 inches thick FINIS...

Page 49: ...d Rough Opening Height Figure 5 2 Note 2 Verify Marble Cut Lengths on site prior to cutting Note 3 Dimensions assume use of a 3 4 in Hearth Pad MODEL DESCRIPTION PART ELEVATED APPLIANCE DIMENSION See Note 1 MARBLE LEG CUT LENGTH See Note 2 KENWOOD MANTEL AFKDMPA 0 See Note 3 27 3 8 in KENWOOD MANTEL W BASE AFKDMPA W HTKDMPA 9 1 4 in 29 3 8 in LAURENT SURROUND LAURENT 32 1 1 2 in N A CAMDEN SURROUN...

Page 50: ...ce ember material annually Improperly placed embers interfere with proper burner operation Placing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing Embers onto the burner care should be taken so that the po...

Page 51: ...of the appliance verify that the pilot is on the left side See Figure 2 Log Set Assembly LOGS 2126 Models ST 550T IPI GDST3831I STEP 2 Log 1 SRV2126 700 Place Log 1 so that the large cutout on the bottom of the log fits over the pilot shield as shown in Figure 4 The hole in the bottom of Log 1 interlocks with the head of the shoulder screw on the burner 1 1 3 3 2 2 PILOT PILOT 1 1 2 2 STEP 3 Log 2...

Page 52: ...P 5 Log 3 SRV2126 702 Place the remaining Log 3 2 of 2 identical logs into the fireplace so that the bot tom of the log rests in the notch on the ledge on the front side of the basepan Then place the top of Log 3 on top of Log 1 so that the flat spot is hidden The complete log set assembly is shown in Figure 11 See the fireplace Owner s Manual for instructions on how to place the Mystic Embers and...

Page 53: ...s or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Air Shutter Settings H Install Trim Kits and Surrounds Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap between the sheet rock and the appliance if desir...

Page 54: ...ed sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transformer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 a...

Page 55: ...rifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumu lated on flame sensing rod c Module is not grounded Verify module is securely grounded to metal chassis of appliance Verify that wire harness is firmly connected to the module d Damaged pilot assembly or contami nated flame sensing rod Ve...

Page 56: ...ensions and clearances refer to Section 5 Figure 16 1 See Through Dimensions B C FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A J K D F G H N i L M E Location Inches Millimeters H 4 1 4 108 I 1 1 2 38 J 8 203 K 8 3 4 222 L 34 1 2 876 M 16 406 N 31 1 4 794 Location Inches Millimeters A 31 1 8 791 B 37 5 8 956 C 21 533 D 30 1 4 768 E 1 25 F 2 1 8 54 G 4 1 8 105 ...

Page 57: ...gth SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm EFFECTIVE HEIGHT LENGTH SLP FLEX PIPE Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 ...

Page 58: ...Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 in 367 mm 2 5 16 in 59 mm 3 15 16 in 101 mm 6 11 16 in 169 mm 8 in 203 mm 3 15 16 in 101 mm 3 13 16 in 97 mm 5 1 16 in 128 mm 6 3 8 in 163 mm 4 3 16 in 106 mm 4 5 8 in 117 mm 5 1 16 i...

Page 59: ... mm 12 1 2 in 318 mm 12 in 305 mm SLP FLEX TRAP Horizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Horizontal Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm B Vent Components Diagram...

Page 60: ...267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm SLP HRC SS SLP HRC ZC SS HORIZONTAL TERMINATION CAP DVP TB1 HORIZONTAL TERMINATION CAP When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical ventsectionisrequired before installing first elbow SLP90 SL 2DVP DVP TB1 DVP TB1 ASSEMBLY B Vent Components Diagrams continued PV...

Page 61: ... PV Wire Harness PVI WH80 100 ft PV Wire Harness PVI WH100 PVI SLP Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 m...

Page 62: ...2 req SRV2126 702 4 Sheetrock Ledge 2126 118 5 Refractory Qty 2 req 2127 017 6 Burner NG LP 2126 007 Y 7 Base Pan 2126 115 8 Glass Door Assembly GLA 550TR Y 9 Junction Box 4021 013 Y 10 Junction Box Bracket 2128 128 11 Pilot Shield 2126 124 Exhaust Restrictor 530 299 Fiberglass Rope Ring 045 455 Gasket Assembly 2128 081 Contains Vent Seal Cap Burner Neck Shutter Bracket and Valve Plate Gaskets Gla...

Page 63: ...ck 593 594A Y 12 2 3 Volt Transformer 593 593A Y 12 3 Module Wire Assembly 593 590A Y 12 4 Module 593 592 Y 12 5 Valve Bracket 2118 104 12 6 Valve NG 750 500 Y Valve LP 593 501 Y 12 7 Flex Ball Valve Assembly 302 320A Y 12 8 Flexible Gas Connector 530 302A Y 12 9 Orifice NG 44C 582 844 Y Orifice LP 55C 582 855 Y 12 10 Pilot Assembly NG 2090 012 Y Pilot Assembly LP 2090 013 Y 2 in Jumper Wire 2012 ...

Page 64: ..._________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2013 DO NOT DISCARD THI...

Reviews: