background image

Heat & Glo  •  SL-5/5LP-IFT, SL-7/7LP-IFT, SL-9/9LP-IFT Installation Manual  •  2632-980 Rev. E  •  4/21

36

Rear Vent  - Vertical Termination - (continued)

Figure 4.26

Three Elbows

V

2

V

1

H

2

H

1

ALL MODELS

H

1

 Maximum

V

1

 Minimum

H

2

H

1

 + H

2

 Maximum

1-1/2 ft. 457 mm

Back to Back 

Elbows

1 ft.

305 mm 2-1/2 ft. 762 mm

3-1/2 ft.

1.1 m

1 ft.

305 mm

3 ft.

914 mm 6-1/2 ft.

2.0 m

5-1/2 ft.

1.2 m

2  ft.

610 mm

5 ft.

1.5 m

10-1/2 ft.

3.2 m

7-1/2 ft.

2.3 m

3 ft.  914 mm

7 ft.

2.1 m

14-1/2 ft.

4.4 m

H

1

 Maximum = 7-1/2 ft. (2.3 m)

V

1

 + V

2

 + H

1

 + H

2

  Maximum = 40 ft. (12.2 m)

Note

: Use DVP Series 

components only.

Summary of Contents for SL-5-IFT

Page 1: ...FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Models SL 5 IFT SL 5LP IFT SL 7 IFT SL 7LP IFT SL 9 IFT SL 9LP IFT This appliance may be installed as an OEM installation in manufactured home USA only or mobile home and must be installed in accordance with the manufacturer s instructions and the Manufactured Home Constructio...

Page 2: ...n A Approved Pipe 20 B Vent Termination Minimum Clearances 20 C Vent Terminal Clearances 22 D Use of Elbows 23 E Use of Flex Vent SLP FLEX Series 6 5 8 Inch 24 F Vent Diagrams 25 5 Vent Clearances and Vent Framing A Vent Clearances to Combustibles 39 B Wall Penetration Framing Firestops 40 C Ceiling Firestop Floor Penetration Framing 41 D Install Attic Insulation Shield 41 6 Appliance Preparation ...

Page 3: ...appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure veri ed ___________________________ Veri ed proper air shutter setting for installation type ___________________________ Finishing Section 10 Pg 61 64 Combustible materials not installed in non combustible areas ___________________________ Veri ed all c...

Page 4: ...ion for installations at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size B Glass Specifications Hearth Home Technologies appliances manufactured with tempered glass may be installed in hazardous lo cations such as bathtub enclosures as defined by the Consumer Product Safety Commission CPSC The tempered glass has been tested and certified to the ...

Page 5: ...not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit i...

Page 6: ...ly vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signa...

Page 7: ...raming material Manometer Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Gloves Wrenches Reciprocating saw 1 4 in nut driver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws Caulking material 300 ºF minimum continuous exposure rating Improper installation adjustment alteration service or maintenance can cause injury or property dama...

Page 8: ... Carefully remove the appliance and components from the packaging The vent system components and decorative barrier fronts may be shipped in separate packages If packaged separately the log set and appliance grate must be installed Report to your dealer any parts damaged in shipment Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions I...

Page 9: ...A 36 914 41 1041 48 1219 B 31 1 8 791 36 1 8 918 43 1092 C 27 3 16 691 32 1 16 814 39 1 16 992 D 18 1 16 459 21 1 2 546 23 9 16 599 E 34 1 16 865 37 5 8 956 39 9 16 1005 F 3 9 16 90 3 9 16 90 3 9 16 90 G 6 7 8 175 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 28 7 8 733 I 34 3 8 873 37 7 8 962 39 7 8 1013 J 36 7 16 926 39 15 16 1014 41 15 16 1065 K 8 203 8 203 8 203 L 8 13 16 224 8 13 16 224 8 13 16...

Page 10: ...1 4 mm 864 730 913 41 67 778 819 SL 9 IFT FS 9 in 40 7 8 30 5 8 43 1 5 8 2 5 8 32 5 8 34 1 4 mm 1038 778 1092 41 67 829 870 IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Decorative barrier front must be ordered at time of fireplace purchase If decorative barrier fron...

Page 11: ... 28 15 16 3 1 2 4 9 16 mm 800 564 910 681 735 89 116 SL 9 IFT CF 42 in 38 1 2 24 1 16 42 3 4 28 11 16 30 13 16 3 1 2 4 9 16 mm 978 611 1086 729 783 89 116 CLEAN FACE DECORATIVE BARRIER KIT IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Decorative barrier front must be...

Page 12: ...29 148 746 832 783 SL 7 IFT CHA 36 in 32 7 16 20 1 2 37 3 16 1 1 8 7 7 8 32 7 8 37 3 8 34 3 8 mm 824 521 945 29 200 835 949 873 SL 9 IFT CHA 42 in 39 7 16 22 7 16 44 3 16 1 1 8 7 7 16 34 3 4 44 3 8 36 3 8 mm 1002 570 1122 29 189 883 1127 924 IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with...

Page 13: ...7 3 16 1 1 8 6 1 4 32 7 8 37 3 8 34 3 8 mm 824 540 945 29 159 835 949 873 SL 9 IFT HAL 42 in 39 7 16 23 1 8 44 3 16 1 1 8 6 1 4 34 3 4 44 3 8 36 3 8 mm 1002 587 1122 29 159 883 1127 924 Figure 3 5 Decorative Barrier Front Dimensions Halston IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with ...

Page 14: ... 8 1 3 16 7 9 16 32 7 8 37 3 8 34 3 8 mm 813 527 943 30 192 835 949 873 SL 9 IFT CHAF 42 in 39 22 5 8 44 3 16 1 1 8 7 5 8 34 3 4 44 3 8 36 3 8 mm 991 575 1122 29 194 883 1127 924 Note See Section 10 for hearth mantel and finishing requirements Figure 3 6 Decorative Barrier Front Dimensions Chateau Forge IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct conta...

Page 15: ...46 832 783 SL 7 IFT SL 7LP IFT ARC 36 in 32 7 16 20 1 2 37 3 16 1 1 4 7 11 16 32 7 8 37 3 8 34 3 8 mm 824 521 945 32 195 835 949 873 SL 9 IFT SL 9LP IFT ARC 42 in 39 7 16 22 7 16 44 3 16 1 1 4 7 7 16 34 3 4 44 3 8 36 3 8 mm 1002 570 1122 32 189 883 1127 924 Note See Section 10 for hearth mantel and finishing requirements IMPORTANT This fireplace requires an installed decorative barrier front to pr...

Page 16: ...6 3 4 32 7 8 34 1 8 37 3 8 34 3 8 mm 695 587 945 32 172 835 867 949 873 SL 9 IFT FSI 42 in 34 3 8 25 3 16 44 3 16 1 1 4 6 3 4 34 13 16 36 1 16 44 3 8 36 3 8 mm 873 640 1122 32 172 884 916 1127 924 Note See Section 10 for hearth mantel and finishing requirements IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operat...

Page 17: ...Figure 3 9 Appliance Locations J C A K H B F D I I F A E G L Refer to Section 10 for mantel and wall projection information Consider the mantel or cabinet system to be installed and comply with the necessary requirements for elevated hearth Refer to instructions included with cabinet system E M C A K SL 5 5LP IFT and SL 7 7LP IFT ONLY For reference see Figure 4 21 E E Models A B C D E Min F G H I ...

Page 18: ... appliance is mounted at floor level MINIMUM FRAMING DIMENSIONS Models A B C D E F G H I J DVP Pipe SLP Pipe Rough Opening Height DVP Pipe SLP Pipe Rough Opening Width Clearance to Room Ceiling Combustible Floor Minimum Hearth Required Behind Appliance Sides of Appliance Front of Appliance Rough Opening Width Rough Opening Width Rough Opening Depth Rough Opening Depth SL 5 IFT in 10 8 5 8 34 3 4 1...

Page 19: ...eld and ceiling firestops should be sealed with caulk with a minimum of 300 ºF continuous exposure rating to seal gaps Gas line holes and other openings should be sealed with caulk with a minimum of 300 ºF continu ous exposure rating or stuffed with unfaced insulation If the appliance is being installed on a cement surface a layer of plywood may be placed underneath to prevent conducting cold up i...

Page 20: ...DVP or SLP venting systems Refer to Sec tion 12 A for vent component information and dimensions Only use listed decorative termination caps shrouds with Hearth Home Technologies approved venting systems DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement for inspection openings at each joint within t...

Page 21: ...der proximity to doors traffic areas or where people may pass or gather sidewalk deck patio etc Listed cap shields available Contact your dealer Local codes or regulations may require different clearances Hearth Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements Vinyl protection kits are suggested for u...

Page 22: ... mm H clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in min 229 mm min 12 in min 305 mm min I clearance to a mechanical powered air supply inlet All mechanical air intakes within 10 feet of a horizontal termination cap must be a minimum of 3 feet below termination 3 ft 914 mm 6 ft 1 8 m J On pub...

Page 23: ...E E F F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DVP12A 3 to 12 76 to 305 2 1 8 8 1 2 54 216 Vent Type X Inches Millimeters DVP 16 1 4 413 SLP 11 1 4 286 Figure 4 7 ...

Page 24: ...orts A support is required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 4 8 requires only enough support to maintain the necessary clearance to combustibles However the vent attachment point and the firestop loca tion are considered to be supports Figure 4 8 Flex Vent Pipe G...

Page 25: ...p must be installed When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released See Figure 4 9 Measuring Standards Vertical and horizontal measurements listed in the vent diagrams and clearance...

Page 26: ...st elbow WARNING V1 Minimum H1 Maximum SL 5 IFT SL 7 IFT SL 9 IFT 90 Elbow 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 1 2 ft 152 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 5 ft 1 5 m 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 7 ft 2 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m H MAX 14 ft 4 3 m V H MAX 40 ft 12 2 m ...

Page 27: ...irst elbow WARNING V Minimum H1 H2 Maximum SL 5 IFT SL 7 IFT SL 9 IFT 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 0 ft 0 mm 1 2 ft 152 mm 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 6 ft 1 8 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m H H1 MAX 14 ft 4 3 m V H H1 MAX 4...

Page 28: ...Maximum SL 5 IFT SL 7 IFT SL 9 IFT V2 V1 V2 Min 90 Elbow 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 2 ft 152 mm 6 ft 1 8 m 6 ft 1 8 m 6 ft 1 8 m 1 1 2 ft 457 mm 10 ft 3 0 m 10 ft 3 0 m 10 ft 3 0 m 2 1 2 ft 762 mm 12 ft 3 7 m 12 ft 3 7 m 12 ft 3 7 m 3 1 2 ft 1 1 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H ...

Page 29: ...ter exhaust restrictor installation Exhaust restrictor Instructions Exhaust restrictors are recommended for these verti cally terminated products which have excessive draft Exhaust restrictors will compensate for high draft and restore visual flame height If the vent configuration has a total vertical of 15 60 feet an exhaust restrictor may be used The exhaust restrictor can be located in the ap p...

Page 30: ... mm 1 ft 305 mm 1 2 ft 152 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 5 ft 1 5 m 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 7 ft 2 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m 15 ft 4 6 m 15 ft 4 6 m H MAX 15 ft 4 6 m V1 V2 H MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m Note When ...

Page 31: ... ft 152 mm 0 ft 0 mm 1 2 ft 152 mm 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 6 ft 1 8 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m H MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 cannot exceed 40 ft 12 2...

Page 32: ...in H2 Max V3 Min 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only Figure 4 19 Top Vent Vertical Termination continued V1 H1 V2 V3 H2 Note When using SLP FLEX 6 5 8 in venting there MUST be a 25 reduction in total H when using flex vent See Figure 4 8 ...

Page 33: ...mm SL 7 IFT 24 in 610 mm SL 9 IFT 18 in 457 mm CAUTION For SL 9 IFT H1 Maximum can be up to 24 inches ONLY if the Optional Refractory Kit BRICK 9 is NOT used H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45º Elbow For corner installation of models SL 5 IFT and SL 7 IFT ONLY Note Do not use a 45º elbow for SL 9 IFT Use two 90º elbows for corner installation on SL 9 IFT Note Use DVP Se...

Page 34: ... ft 1 5 m 10 ft 3 0 m 7 ft 2 1 m 5 ft 1 5 m 7 ft 2 1 m 14 ft 4 3 m H1 MAX 7 ft 2 1 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m Figure 4 23 Three Elbows Note Use DVP Series components only H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 1 2ft 2 9 m...

Page 35: ...ts only V1 MIN H1 MAX 1 ft 305 mm 3 1 2 ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m INSTALLED HORIZONTALLY H1 H2 V2 H1 H2 MAX V1 MIN 1 2 ft 152 mm Back to back elbows 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 ft 914 mm H MAX 6 1 2 ft 2 m V H H1 MAX 40 ft 12 2 m H1 V1 Note Use DVP Series components only ...

Page 36: ...ALL MODELS H1 Maximum V1 Minimum H2 H1 H2 Maximum 1 1 2 ft 457 mm Back to Back Elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 3 ft 914 mm 6 1 2 ft 2 0 m 5 1 2 ft 1 2 m 2 ft 610 mm 5 ft 1 5 m 10 1 2 ft 3 2 m 7 1 2 ft 2 3 m 3 ft 914 mm 7 ft 2 1 m 14 1 2 ft 4 4 m H1 Maximum 7 1 2 ft 2 3 m V1 V2 H1 H2 Maximum 40 ft 12 2 m Note Use DVP Series components only ...

Page 37: ...s appliance Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the direction of certi fied professionals conduct a minimum of a NFPA 211 Level 2 inspection of the chimney Replace component parts of the chimney and fireplace as specified by the professionals Ensure...

Page 38: ...pipe to the inlet collar on top of the DV 46DVA GCL adapter with three self tapping screws To minimize cold air drafts seal around the flex vents at the damper inside the chimney with non combustible unfaced fiberglass or rock wool insulation The DV 46DVA GCL adapter must be recessed into existing masonry fireplace This measurement is taken from the top of the fireplace opening See Table 1 and Fig...

Page 39: ...n 25 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in a DVP HSM B will be required SLP heat shield designed to be used on a wall 4 3 8 in to 7 5 8 in 111 mm to 194 mm thic...

Page 40: ...ernal walls A wall shield firestop must be pur chased and installed The opening must be framed on all four sides using the same size framing materials as those used in the wall construction SLP pipe A wall shield firestop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be main tained DVP pipe A wall shield firestop is required on one s...

Page 41: ...pack insu lation around the vent Maintain clearances to vent to prevent overheating A ceiling firestop MUST be used between floors and attics DVP pipe only Frame an opening 10 in by 10 in 254 mm by 254 mm whenever the vent penetrates a ceiling floor see Figure 5 3 SLP pipe only Frame opening 9 in x 9 in 229 mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 5 3 Frame the area with...

Page 42: ...ns for the minimum initial vertical requirements The following provisions must be followed 1 The elbow heat shield is not required if combustible materials or combustible chases are installed a mini mum of 6 inches above the top of the elbow See Fig ure 6 2 2 If the combustible materials are to be installed between 3 inches and 6 inches above the top of the elbow the elbow heat shield is required ...

Page 43: ... preceding component in the vent system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an elbow does not end up in a locked position with the preceding component attach with a minimum of two 2 sheet metal screws CORRECT INCORRECT COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 6 3 Figure 6 6 Rotate the top heat shield to the ver...

Page 44: ...ction of vent pipe make sure to use the fiberglass gasket to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap 2 SCREWS Figure 6 9 Remove the insulation basket and white insu lation from the center vent pipe Figure 6 8 Remove the seal cap NOTICE Once the seal cap has been removed it CANNOT be reattached ...

Page 45: ...e insulation gasket Figure 6 13 Generic Fireplace Shown Cut the metal retaining band and fold the sides out Figure 6 14 Generic Fireplace Shown Fold the center parts of the retaining band out and use to remove the seal cap Figure 6 15 Generic Fireplace Shown Discard the seal cap remove and discard the insulation basket Figure 6 16 Generic Fireplace Shown Attach the first vent section it will snap ...

Page 46: ... or plastic Framing and other combustible materials WARNING DO NOT remove standoffs or notch the framing around the appliance standoffs Failure to maintain air space clearance could cause overheating and fire Block openings into the chase to prevent entry of blown in insulation Make sure insulation and other materials are secured Figure 6 17 Heat Management Port Locations HEAT MANAGEMENT PORTS LEF...

Page 47: ...e 7 1 OR Apply a bead of silicone sealant 300 ºF minimum con tinuous exposure rating to the outside of connecting joint after joining sections OR Apply aluminum foil tape 300 ºF minimum continuous exposure rating to the outside of connecting joint after joining sections On horizontal pipe runs it is recom mended that the tape seam is positioned on the bottom side of the vent pipe Only outer pipes ...

Page 48: ... one of the meth ods below including the slip section that connects directly to the horizontal termination cap Apply a bead of silicone sealant 300 ºF minimum con tinuous exposure rating inside the female outer pipe joint prior to joining sections See Figure 7 1 OR Apply a bead of silicone sealant 300 ºF minimum con tinuous exposure rating to the outside of connecting joint after joining sections ...

Page 49: ... the slip section See Figure 7 7 120º Figure 7 8 Securing Vertical Pipe Sections 120º Figure 7 9 Securing Horizontal Pipe Sections C Secure the Vent Sections WARNING Risk of Fire Explosion or Asphyxiation Improper support could allow vent to sag and separate Use vent run supports and connect vent sections per in stallation instructions DO NOT allow vent to sag below connection point to appliance V...

Page 50: ... E 4 21 50 D Disassemble Vent Sections Rotate either section see Figure 7 10 so the seams on both pipe sections are aligned as shown in Figure 7 11 Pull carefully to separate the pieces of pipe Figure 7 11 Align and Disassemble Vent Sections Figure 7 10 Rotate Seams for Disassembly ...

Page 51: ...re 7 12 Seal the exposed pipe section seams that are located above the roof SEAL Figure 7 12 Figure 7 12 Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Slide the storm collar onto the exposed pipe section and align brackets Insert a bolt provided through the brackets and in...

Page 52: ...ure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 15 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 ...

Page 53: ... Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 4 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NO...

Page 54: ...the junction box receptacle to the outer shell A General Information WARNING Risk of Shock DO NOT wire 110 120 VAC to the ignition module or to the appliance wall switch IPI Incorrect wiring will damage controls NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the...

Page 55: ...mponent Tray The electrical components are installed on the component tray If it becomes necessary to remove the components use the information in Figure 8 2 to remove them and reinstall them correctly on the component tray The IFT ECM is held in position by two placement tabs front and rear on the component tray To remove the IFT ECM bend the front or rear placement tab back slightly and tip the ...

Page 56: ...he event of an emergency power outage Batteries should not be used as a primary long term power source Batteries tend to corrode over time When using batteries as a power source the 6 volt transformer must be unplugged from the receptacle Do not store batteries in the battery pack when the appliance is powered by the 6 volt transformer connected to permanent electrical service Figure 8 3 IntelliFi...

Page 57: ...he junction box and connect to the top fan switch connector 1 4 inch male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junction Box Knockout Figure 8 4 Junction Box Wired to Wall Switch RHEOSTAT SWITCH TEMPERATURE SENSOR Figure 8 5 Fan Wiring with Rheostat BLUE RHEOSTAT SWITCH TEMPERATURE SENSOR SWITCH ...

Page 58: ... valve if line pressure is greater than 1 2 psig 9 9 Gas Information Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Manifold pressure 3 5 in w c 10 0 in w c Note Have the gas supply line installed in accordance with local codes if any If not follow ANSI Z223 1 Installation should be done by a qualified installer approve...

Page 59: ...e shutter opening to adjust for short horizontally terminating or vertically terminating vent configurations prior to the initial fire up Propane P installations As a general rule if the flames appear blue after 30 minutes of operation it is acceptable to close the shutter slightly Reduce shutter with caution to avoid soot potential Air Shutter Adjustment The air shutter may be adjusted by locatin...

Page 60: ...tification Verification The burner may be accessed for identification and veri fication purposes This task should be performed by a qualified service technician The logs and burner must be removed to see these identification marks Disconnect the pilot from the burner before removal See Figure 9 2 for burner identification chart Notch patterns are located on bottom side of burner ...

Page 61: ...ials only Facing and or finishing materials must not interfere with air flow through decorative barrier fronts removal of decorative barrier fronts or access for service Facing and or finishing materials must never overhang into the glass opening Observe all clearances when applying combustible materials Seal gaps between the finished wall and appliance top and sides using a 300 ºF minimum sealant...

Page 62: ... 6 32 CEILING 1 5 6 7 8 9 10 4 12 11 13 3 13 14 15 16 14 15 16 17 TOP OF HOOD OR FIREPLACE OPENING See Dimension V on Appliance Dimension Diagram Figure 3 1 12 11 10 9 8 7 6 32 CEILING 8 9 10 12 11 13 13 14 15 16 15 16 17 14 Figure 10 4 Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening Combustible Mantel Legs or Wall Projections Non Combustible Mantel Legs or Wall Proj...

Page 63: ...tion Manual 2632 980 Rev E 4 21 3 1 2 IN MIN 12 IN MINIMUM WITH ELBOW HEAT SHIELD INSTALLED 15 INCH MINIMUM WITHOUT ELBOW HEAT SHIELD INSTALLED Figure 10 7 Rear Vent Non Combustible Zone Above Appliance Figure 10 8 Top Vent Non Combustible Zone Above Appliance ...

Page 64: ...on Combustible Finishing materials 1 inch maximum thick Stop finishing material flush with opening X Includes additional clearances to sides and top of decorative front Y Figure 10 12 Overlap Fit Decorative Barrier Front ARC CHA CHAF HAL IRON AGE Non Combustible finishing material between 1 and 6 inches thick Refer to Section 3 for X and Y dimensions Inside Fit Firescreen Front 0 6 Inch Finishing ...

Page 65: ...ve before in stalling the splatter guard to prevent accidental lighting Remove the splatter guard before lighting the appliance B Clean the Appliance Clean vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity C Install the Optional Refractory Kit An optional reflective black glass or brick refractory kit is available for use with these models Install ...

Page 66: ... Figure 11 4 Lift Center Hearth Component While Placing Right Hearth Component 1 Locate the left hearth component shown in Figure 11 2 Place it as shown in Figure 11 2 ensuring that the outer edge of the hearth component firmly contacts the firebox side and the front edge contacts the firebox front lip Gently push down on the indentation to force the bottom side of the hearth component to engage t...

Page 67: ...OG PINS EMBERS SL 7 SL 7 IFT SL 9 SL 9 IFT Figure 1 Log Pin and Glowing Ember Locations CAUTION Logs are fragile handle with care Install Logs Figure 2 Example of Log Pin Holes Figure 3 Log Assembly Components Log Placement Tips The rear left log rear right log and small burner log utilize holes in the bottom side of the logs that correspond to the locator pins on the burner Reference Figure 1 and...

Page 68: ... SL 7 SL 7 IFT and SL 9 SL 9 IFT Models There will be about a 1 inch rear gap between the left rear log and the back wall of the firebox There will be about a 1 1 2 inch side gap between the left end of the log and the left side of the firebox See Figure 4 SL 5 SL 5 IFT Models There will be about a 1 inch rear gap from the left rear log to the back wall of the firebox There will be about a 1 inch ...

Page 69: ...e right rear log which cradles the right top log The indentation is highlighted in Figure 6 The burnt end of the log will engage a notch in the middle hearth component See Figure 9 Figure 9 Top Right Log Installed Log Set Complete 5 Remove small burner log from packaging This log has two holes on the bottom These holes correspond to two log pins located on the burner top Place log on the two log p...

Page 70: ...le fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Figure 11 7 Fixed Glass Assembly GLASS ASSEMBLY LATCHES BOTH BOTTOM AND TOP Removing Fixed Glass Assembly Remove decorative barrie...

Page 71: ...tive barrier fronts could cause fireplace to overheat IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one For more information refer to the instructions ...

Page 72: ...mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm DVP WS Wall Shield Fires...

Page 73: ...nimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield 5 in 127 mm Center of the horizontal vent pipe to the vertical measuring surface A Vent Components Diagra...

Page 74: ...in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield 12 IN 305 mm 7 IN 178 mm 4 15 16 IN A A A 1 2 IN 13 mm 7 8 IN 22 mm 125 mm 7 IN 178 mm TRAP VSS Vinyl Siding Shield A Vent Comp...

Page 75: ...5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap 6 in 152 mm A Vent Components Diagrams continued Figure 12...

Page 76: ...n 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS Figure 12 5 Vent Components DECORATIVE TERMINATIONS SHROUDS Only use listed decorative termination caps shrouds with Hearth Home Technologies approved venting systems This applies to both DVP and SLP venting systems Decorative Terminations Caps Shrouds DTO134 DTO146 DTS134 DTS146 LDS33 LDS4...

Page 77: ...48 A Vent Components Diagrams continued PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and connect it to the appliance It is ordered separately from the PVV SLP Contact your dealer to order Note The PVV SLEEVE 12 and or PVV SLEEVE 48 is required to be installed with the PVV SLP It is ordered separately from the PVV SLP Contact your dealer to order Note The PVV SLP...

Page 78: ... 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 mm MIN 35 IN 889 mm MAX Note The PVI SLP B requires one of the following options to be installed on this appliance Option A IFT RC400 OR Option B IFT RC150 and IFT ACM These accessories are purchased separately from the PVI SLP B Conta...

Page 79: ...56 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View Note A PVLP HS heat shield is available and sold separately Use if the PVLP SLP is installed in a high traffic area PVLP BEK Brick Kit PVLP SLP Power Vent Low Profile Note The PVLP...

Page 80: ...ve Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 ...

Page 81: ...s greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 in 367 mm 2 5 16 in 59 mm 3 15 16 in 101 mm 6 11 16 in 169 mm 8 in 203 mm 3 15 16 in 101 mm 3 13 16 in 97 mm 5 1 16 in 128 ...

Page 82: ...rmination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Horizontal Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basement Vent Cap 4...

Page 83: ...oaxial Colinear Appliance Connector 768 380A Required Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 13 Coaxial to Colinear Vent Components SLP HHW2 Horizontal High Wind Termination Cap 15 IN 381 mm 12 IN 305 mm 8 IN 203 mm Figure 12 12 SLP series Vent Components A Vent Components Diagrams continued ...

Page 84: ... if you have questions Note Optional heat management systems kit must be installed while the sides of the appliance are accessible Install approved accessories per instructions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed...

Reviews: