background image

25

A. Chimney Requirements

Measure vertical distances from the base of the fireplace 

as shown in Figure 8.2.

20 ft (6.10 m) max.

pipe between an

offset & return

Ceiling Firestop 

35 ft (10.67 m) 

max. straight 

unsupported  

chimney height 

14.5 ft (4.42 m) min. height/single offset-return 

20 ft. (6.1 m) min. height/double offset-return 

90 ft (27.43 m) max. height 

6 ft (1.83 m) max. 

unsupported chimney 

above roof 

39 1/2 in. (1003 mm)

Effective Height

Figure 8.2  Chimney Requirements

Table 8.1

• Minimum overall straight height

13

(3.96 m)

• Minimum height with offset/return

14.5 ft

(4.42 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset and return

20 ft

(6.1 m)

• Maximum distance between chimney stabilizers

35 ft

(10.67 m)

• Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length between the offset 

and return

6 ft

(1.83 m)

• Maximum unsupported chimney height above the 

fireplace

35 ft

(10.67 m)

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

WARNING! Risk of Fire! You must maintain 2 in. (51 

mm) air space clearance to insulation and other combus-

tible materials around the chimney system. Failure to do 

so may cause overheating and fire.

Determine the chimney components needed to complete 

your particular installation:
•  Measure  the  total  vertical  height  of  the  fireplace 

installation from the base of the fireplace assembly to 

the approximate location of the bottom of the termination 

cap.

•  Subtract the effective height of the fireplace assembly 

(see Figure 8.2) from the total vertical height to determine 

the overall height of the chimney installation.

•  Create a schematic for your application similar to Figure 

8.2  showing  components  required  (referring  to Table 

8.1). Figure 8.1 identifies those components and where 

used.

•  Install a ceiling firestop whenever the chimney penetrates 

a floor/ceiling.

  NOTICE: A maximum of two pairs of offsets and returns 

may be used.

  CAUTION!  Risk  of  Fire  and/or  Asphyxiation!  DO 

NOT connect this fireplace to a chimney flue servicing 

another appliance. 

DO NOT

 connect to any air distribu-

tion duct or system. These actions could cause over

-

heating/fire in the chimney flue, or release of exhaust 

fumes into the living areas.

Heat & Glo • RH-36/RH-42 • 4044-153 • Rev AC • 1/11

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4 

578

SL336

34-3/4 

883

SL348

46-3/4 

1187

* Dimensions reflect effective height.

Summary of Contents for RH-42 Series

Page 1: ...s is not followed exactly a fire may result causing property damage personal injury or death Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING WARNING Hot screen mesh and gl...

Page 2: ...anual unless noted otherwise applies to all models and gas control systems Your new Heat Glo wood burning fireplace will give you years of durable use and trouble free enjoyment Wel come to the Heat Glo family of fireplace products FIREPLACE NO MODEL NO MODEL NO MFG DATE WARNING RISK OF FIRE DAMAGE REPLACE GRATE WITH HEARTH HOME TECHNOLOGIES INC FIRECHAMBER INTENDED FOR USE WITH HEARTH HOME TECHNO...

Page 3: ...eplace Chimney 16 F Tools and Supplies Needed 17 G Fireplace System Requirements 17 H Inspect Fireplace and Components 17 6 Framing Clearances 18 A Select Fireplace Location 18 B Clearances 19 C Sidewalls Surrounds 20 D Frame the Fireplace 20 7 Installation of Fireplace 21 A Things to Consider 21 B Position the Fireplace 21 C Place Protective Metal Hearth Strips 21 D Level Fireplace 21 E Install O...

Page 4: ...nty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty period for parts and labor for covered components ...

Page 5: ...a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from the use of abrasive cleaners or polishes Repair or replacement of parts ...

Page 6: ...Iron Brick Tile Concrete Slate Glass Plasters Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace at 750 C C Combustible Materials Materials made of or surfaced with any of the following materials Wood Compressed paper Plant fibers Plastic Any material that can ignite and burn flame proofed or not plastered or un plastered Heat Glo RH 36 ...

Page 7: ...eep clothing furniture draperies and other flammable materials away HOT SURFACES Glass and other surfaces are hot during operation AND cool down Figure 2 1 General Operating Parts A Your Fireplace If you expect that children may come into contact with this fireplace we recommend a barrier such as a decorative screen See your dealer for suggestions Close Close Open Open Gas Log Set Gas Log Lighters...

Page 8: ...pounds Fill it with a gallon of water put it in the fireplace and try to burn it This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood A tree cut down a year ago and not split is likely to have almost as high a moisture content now as it did when it was cut Please refer to Section 2 M for more detail Caution Odors and vapors released during initial operation may...

Page 9: ...Refer to Figure 2 2 for how to properly use them H Glass Doors 48 in 1219 mm Clear Space Front of Fireplace 12 in 305 mm Clear Space Sides of Fireplace from the FP opening Figure 2 3 Clear Space J Vented Gas Log Sets Gas Log Lighters Optional Vented gas logs or gas log lighters can be installed in this fireplace Follow the instructions provided with the accessory for operation K Optional Component...

Page 10: ... around and through woodpile Elevate wood pile off ground to allow air circulation underneath Smaller pieces of wood dry faster Any piece over 6 in 152 mm in diameter should be split Wood whole or split should be stacked so both ends of each peice are exposed to air More drying occurs through the cut ends than the sides Store wood under cover to prevent water absorbtion from rain or snow Avoid cov...

Page 11: ... to form creosote The creosote vapors condense in the rela tively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes an extremely hot fire Warning Risk of Fire A chimney fire can permanently damage your chimney system and nearby structures In the event of a chimney fire Hearth Home Technolo gies Inc recommends repla...

Page 12: ...the refractory This is normal The refractory will require periodic replacement depending on use The panels should be replaced if Cracks exceed inch 6 mm in width Metal is exposed behind the refractory Large pieces of refractory fall out E Glass Cleaning Frequency As desired By Homeowner Clean glass with a non abrasive commercially available cleaner or ashes Light deposits Use household glass clean...

Page 13: ...o wood fuel section Bed of coals not established before adding wood Start with paper kindling to establish bed of coals refer to starting fire section Flue blockage such as birds nests or leaves in termination cap Have chimney inspected for creosote and cleaned by a certified chimney sweep Down draft or negative pressure Competition with exhaust devices Do not use exhaust fans during start up refe...

Page 14: ...ction 6 B Mantel and surround Section 11 E 11 F Decorative facing and trim Section 11 D Hearth extension Section 11 C Factory built fireplace Protective metal hearth strip s Section 7 C Outside combustion air Section 7 E Combustible framing header on top of V shaped standoffs Section 6 D Chimney system Section 8 Attic insulation shield not shown must be used here to keep insulation away from chimn...

Page 15: ...ice Hearth Home Technologies Inc recommends the use of direct vent fireplaces in basements D Negative Pressure B Design and Installation Considerations Draft is the pressure difference needed to vent fireplaces successfully When a fireplace is drafting successfully all combustion byproducts are exiting the home through the chimney Considerations for successful draft include Preventing negative pre...

Page 16: ...the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the effects of wind loading Locate termination cap away from trees adjacent structures uneven roof lines and other obstructions Minimize the use of chimney offsets Consider the fireplace location relative to f...

Page 17: ...OT install dam aged incomplete or substitute components Keep fire place dry Remove fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum...

Page 18: ...on 13 A H B In an exterior chase or projecting into a garage A Note Measurements are FRAMING dimensions only and do not include drywall either in the cavity or on the interior walls I I A B C D E F G H I inches 42 50 67 7 8 59 1 2 34 14 48 21 1 2 mm 1067 1270 1724 1511 864 356 1219 546 inches 48 56 73 7 8 65 1 2 37 1 4 14 52 1 4 21 1 2 mm 1219 1422 1876 1664 946 356 1327 546 Model RH 36 12 in 305 ...

Page 19: ... standoffs Attic Insulation Shield ceiling attic ceiling Offset Return secured with hanger straps Storm Collar Roof Flashing 1 2 in 13 mm to back sides of appliance Must have 2 in 51 mm minimum clearance to header 0 in to floor 2 in 51 mm min Shaded areas represent 2 in 51 mm min air space clearance required around pipe Combustible Object 48 in 1219 mm Ceiling Firestop Figure 6 2 Clearances to Com...

Page 20: ...extra space needed for outside air connection If outside air duct has no bend this dimension may be reduced as long as minimum clearances are met Model A B C D in 42 21 1 2 39 3 4 8 mm 1067 546 1010 203 in 48 21 1 2 39 3 4 8 mm 1219 546 1010 203 RH 36 RH 42 If interior of chase will be drywalled add the thickness to Adjust header height for a raised floor under fireplace Figure 6 4 Framing the Fir...

Page 21: ...ed DO NOT cover metal strips with com bustible materials Sparks or embers may ignite flooring Refer to Figures 7 1 and 7 2 Locate the two protective metal hearth strips measuring approximately 26 in x 4 in 660 mm x 102 mm included with this fireplace Slide each metal strip 2 in 51 mm under front edge of fireplace Overlap strips in the middle of fireplace opening by 1 in 25 mm minimum Metal strips ...

Page 22: ...lace Use only duct materials specified by manufacturer preferably with short run or mainly straight duct except small dip for cold air trap which will help prevent flow of cold air Figure 7 4 Outside Combustion Air Placement 3 ft min from top of uppermost chimney section to air inlet Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 Figure 7 3 Possible Outside Air Inlet Locations Note Chimney air kit is n...

Page 23: ...er to Figure 5 2 Install as shown in Figures 7 3 7 4 and 7 5 The air duct may be run vertically The outside air hood must be at least 3 ft 91 m below the top of the uppermost chimney section Caution Risk of Fire or Asphyxiation Do not draw outside combustion air from wall floor or ceiling cavity or enclosed spaces such as an attic or garage Do not place outside air hood close to exhaust vents or c...

Page 24: ...ent Ceiling firestops are required where chimney passes through ceiling or floor Support straps for returns must be secured to adequate framing Termination Cap Storm Collar Offsets and returns must be secured with the screws provided outer pipe only Figure 8 1 Typical Chimney System Guidelines for Chimney System Installation 8 Chimney Assembly Notice Chimney performance may vary Trees buildings ro...

Page 25: ...ents needed to complete your particular installation Measure the total vertical height of the fireplace installation from the base of the fireplace assembly to the approximate location of the bottom of the termination cap Subtract the effective height of the fireplace assembly see Figure 8 2 from the total vertical height to determine the overall height of the chimney installation Create a schemat...

Page 26: ... 1 4 718 1 1 10 1 4 260 27 686 6 152 29 3 8 746 1 11 1 2 292 29 737 7 1 4 184 34 864 2 13 1 4 337 32 1 8 816 7 3 4 197 36 1 8 918 1 14 1 2 368 34 1 8 867 8 3 4 222 39 3 4 1010 1 1 16 1 4 413 37 3 8 949 10 3 8 264 45 5 8 1159 2 19 1 4 489 42 1 2 1080 10 5 8 270 46 3 4 1187 1 20 1 2 521 44 5 8 1133 11 7 8 302 51 3 8 1305 1 1 22 1 4 565 47 3 4 1213 13 1 2 243 57 1 4 1454 2 25 1 4 641 52 7 8 1343 13 3...

Page 27: ...r 8 sheet metal screws no longer than 1 2 in 13 mm to fasten chimney sections together Do NOT penetrate inner flue Warning Risk of Fire You MUST use screws pro vided to fasten offset returns to chimney sections to keep the chimney parts from twisting Failure to do so could cause fire Fasten offset returns to chimney sections Insert the screws provided through the predrilled holes Do NOT penetrate ...

Page 28: ...lation shield if the ceiling is insulated The ceiling firestop may then be attached above or below the joists E Install Ceiling Firestops Caution Risk of Fire Ceiling firestops must be used whenever the chimney penetrates a ceiling floor Chase construction requires ceiling firestops at each floor or every 10 ft 3 05 m of clear space The ceiling firestop slows spread of fire and reduces cold air in...

Page 29: ...en the chimney and the attic insulation shield Failure to keep insulation and other materials away from chimney pipe could cause fire Do NOT offset chimney inside insulation shield If you wish to make a custom shield or barrier follow these guidelines Metal is preferred although any material stiff enough to hold back the insulation can be used Warning Risk of Fire Use of cardboard or other materia...

Page 30: ...lashing plate on the lower side of a sloped roof and over the flashing plate on the sides and top Nail the flashing to the roof Keep gaps between the flashing plate and the roof to a minimum Caulk the flashing plate and roof junction as well as the vertical seam on the flashing All nail heads must be caulked with a roofing sealant Caulk the overlap seam of any exposed pipe sections that are locate...

Page 31: ...corative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative cap cover In a staggered installation with both gas and wood terminations the wood termination cap must be higher than the gas termination cap Figure 8 10 Multiple Chimney Locations J Chimney Termination Requirements Install a cap approved and listed for this fireplace sy...

Page 32: ...chase is a vertical boxlike structure built to enclose the fireplace and or its vent system Vertical chimneys that run on the outside of a building must be installed inside a chase Construction of the chase may vary with the type of build ing These instructions are not substitutes for the require ments of local building codes Local building codes MUST be checked A chase should be constructed in th...

Page 33: ...UST use a chase top in a chase installation Chase tops are available from your Heat Glo dealer or may be field constructed Include a turndown and drip edge to prevent water from seeping into the chase Include a 2 in 51 mm soldered caulked or spun collar around pipe opening to keep water out Provide a 1 8 in 3 mm gap around the flue pipe Slope the chase top downward away from the opening Caution Do...

Page 34: ...ore termination cap pipe is snapped into the chimney pipe Figure 9 4 Installing a TR344 Round Termination Cap Storm Collar Chimney Pipe Chase Top Termination Cap Chase 14 1 2 in 368 mm Maximum Collar 2 in 51 mm Minimum Height Caulk gaps between storm collar pipe and storm collar chase top Do NOT block air holes 3 clip brackets Slip over chase collar and attach with screws provided Termination cap ...

Page 35: ... 121 mm below the top of the chase Figure 9 7 Installing a TS345 TS345P Square Termination Cap TS345 TS345P Square Termination Cap Chimney Pipe Chase Top Termination Cap Chase Collar 2 in 51 mm Minimum Height Remove 2 screws from front back to lift the top off Termination cap pipe and chimney section must overlap 1 1 2 in 38 mm Place waterproof sealer under each flange of the termination cap and o...

Page 36: ...e shrouds must be constructed from a minimum 018 in 26 ga thick aluminized steel A Radiation Shield Some shrouds require a radiation shield Use where specified Radiation shield must be constructed of minimum 26 ga sheet metal 3 in 76 mm minimum Min Base Dim Min Base Dim Min Top Dim Min Top Dim Min Opening Width Min Opening Width Figure 10 2 Open Top Shroud Dimensions B Field Constructed Shrouds Th...

Page 37: ...d Dimensions Roofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield required Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 TS345 TR342 TR342 344TV Min Base Dims in N A 26 1 2 x 28 28 x 30 mm N A 673 x 711 711 x 762 Min Height Above Radiation Shield in N A 21 1 4 20 1 2 mm N A 540 521 Min Opening Width in N A 20 1 2 x 22 22 x 24 mm N A 521 x 559 559 x 610 TS345 445 TR342 34...

Page 38: ... Total minimum R Value must equal 1 03 Material k per inch thick r per inch thick Minimum thickness required Hearth Home HX3 HX4 Micore 300 0 49 2 06 1 2 in USG Micore 160 0 39 2 54 1 2 in USG Durock Cement Board 1 92 0 52 2 in Cement Mortor 5 0 0 20 5 1 8 in Common Brick 5 0 0 20 5 1 8 in Ceramic Tile 12 50 0 08 12 1 4 in Armstrong Privacy Guard Plus 0 46 2 18 1 2 in Marble 14 3 20 0 0 07 0 05 14...

Page 39: ... When creating the platform allow for the thickness of the non combustible finishing materials Figure 11 5 Non combustible Framing Material 1 2 in Micore or equivalent insulation Figure 11 4 Raised Platform Hearth Extension Framing Materials 2 in 51 mm of the Protective Metal Hearth Strip is required under the front of the fireplace Tile stone or other non combustible material Floor constructed of...

Page 40: ...ble Sealant After completing the framing and applying the facing materials over the framing a bead of non combustible sealant must be used to close off any gaps at the top and sides between the fireplace hearth Non combustible Sealant Figure 11 6 Place Non combustible Sealant Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 ...

Page 41: ...between the fireplace and facing to prevent cold air leaks Large gaps can be bridged with fiberglass rope gasket Only non combustible materials may be used to cover the metal fireplace front These surfaces may be covered with non combustible material Non combustible sealant Figure 11 7 Non combustible Facing Metal strips are placed 2 in 51 mm under the front of the fireplace and must extend beyond...

Page 42: ... 12 in 305 mm from the top of the fireplace opening Combustible trim must not cover the metal surfaces of the fireplace Mantel clearance is in accordance with Section 7 3 3 3 of ANSI NFPA211 7 ft 2134 mm minimum base of fireplace to ceiling Combustible Wall 2 x 4 stud wall Standoffs Measured from top of fireplace opening 12 in 305 mm 1 1 2 in 38 mm maximum 12 in 305 mm minimum 6 in 152 mm minimum ...

Page 43: ...lls may be constructed per Figure 11 10 A Fireplace Opening B Outside Dimensions in 36 41 mm 914 1041 in 42 47 mm 1067 1194 Model RH 36 RH 42 B A 9 3 4 in 248 mm 12 in 305 mm 12 in 305 mm 11 1 4 in 286 mm FLUSH FRONT 4 in 102 mm BRICK FRONT 5 0 a n g l e 3 9 a n g l e Figure 11 10 Mantel Leg or Wall Projections acceptable on both sides of opening Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 ...

Page 44: ...llation in Vented Fireplaces Must be installed in accordance with the National Fuel Gas Code ANSI Z223 1 A gas log set must incorporate a gas shutoff Gas Log set requires the damper to be locked fully open A listed automatic damper system with safety interlock may be used in this fireplace with only compatible listed gas log sets See damper system manufacturer s insturctions Knockouts are provided...

Page 45: ...7 1 2 in 191 mm 9 1 4 in 235 mm 7 1 2 in 191 mm Gas Knockout Outside Air 9 1 4 in 235 mm Gas Knockout 7 1 2 in 191 mm 39 1 2 in 1003 mm C D B 21 3 8 in 543 mm 7 3 8 in 187 mm A B C D in 36 41 23 3 4 11 7 8 mm 914 1041 603 302 in 42 47 29 3 4 14 7 8 mm 1067 1194 756 378 RH 36 RH 42 Model Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 ...

Page 46: ...d Glass Doors DM1036 DM1042 AK24 Outside Air Kit ID4 Insulated Duct UD4 Uninsulated Duct 42 in 1067 mm 4 in 102 mm i d 42 in 1067 mm 4 in 102 mm i d 2 Wire Ties Fastener Pack 4044 036 Air Kit Parts Outside Air Hood Outside Air Plate Assembly Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 See your Heat Glo dealer for a complete listing of optional components ...

Page 47: ... TR344 Round Termination Cap TR342 Round Telescoping Termination Cap ST375 Square Termination Cap TS345 Square Termination Cap TS345P Square Termination Cap Painted TCT375 Terra Cotta Termination Cap CT35 Chase Top DTO134 Short Octagon Decorative Cap DTO146 Tall Octagon Decorative Cap DTS134 Short Square Decorative Cap DTS146 Tall Square Decorative Cap LDS33 Decorative Shroud 3 ft x 3 ft 91 m x 91...

Page 48: ...imney Joint Band 2 in 51 mm 10 1 2 in 267 mm 24 5 8 in 625 mm 27 3 8 in 695 mm 12 in 305 mm 31 in 787 mm 24 5 8 in 625 mm 12 in 305 mm SL315 SL330 Offset Return Inside Diameter 8 in 203 mm Outside Diameter 10 1 2 in 267 mm Effective Height 4 3 4 in 121 mm 26 in 7 3 4 in CT 3A TR344 Round Termination Cap ST375 Square Termination Cap 15 3 4 in 400 mm 23 in 584 mm 19 in 483 mm 15 5 8 in 397 mm Catalo...

Page 49: ...ination Cap TS345 TS345P Square Termination Cap 72 in 1829 mm 36 in 914 mm 2 in 51 mm 10 7 8 in 276 mm CT35 Chase Top 34 3 4 in 883 mm 32 1 2 in 826 mm 13 1 4 in 337 mm 18 in 457 mm 16 1 4 in 413 mm 26 1 2 in 673 mm 28 5 8 in 727 mm TCT375 Terra Cotta Cap 22 1 2 in 572 mm 9 1 2 in 241 mm 16 1 2 in 419 mm 9 1 2 in 241 mm A B C B A C DTS134 DTS146 DTO134 DTO146 Decorative Caps DTO134 A B C in 34 20 ...

Page 50: ...Part number list on following page RH 36 RH42 Beginning Manufacturing Date Jan 2005 Ending Manufacturing Date Active 17 11 12 10 13 14 15 2 1 4 5 6 7 3 8 22 21 Duct sold separately 16 Air Handle 18 9 20 19 Air Kit 1Piece Rod 2 Piece Rod Heat Glo RH 36 RH 42 4044 153 Rev AC 1 11 ...

Page 51: ... req 4044 111 8 Door Track used for upper 15425 9 Smoke Shield 1 ea 4044 131 10 Refractory Retainer Qty 3 req 11847 11 Side Refractory Qty 2 req 4044 114 12 Back Refractory 4044 130 13 Grate GR41 Y 14 Hearth Refractory 4044 129 15 Hearth Retainer 4044 128 16 Firescreen Assembly Qty 2 req 4044 028 Y 17 Firescreen Rod 1 piece 4044 175 2 Piece Qty 2 req 11866B Y 18 Firescreen Handle 1 ea 10002 19 Out...

Page 52: ...4044 120 10 Refractory Retainer Qty 3 req 11847 11 Side Refractory Qty 2 req 4044 114 12 Back Refractory 4044 113 13 Grate GR40 Y 14 Hearth Refractory 4044 112 15 Hearth Retainer 4044 109 16 Firescreen Assembly Qty 2 req 4044 027 Y 17 Firescreen Rod 1 piece 4044 172 2 Piece Qty 2 req 12052 Y 18 Firescreen Handle 1 ea 10002 19 Outside Air Replacement Kit 4044 036 Y 20 Outside Air Shield 33271 Y 21 ...

Page 53: ...nance instructions included Leave this manual with party responsible for use and operation Read understand and follow these instructions for safe installation and operation D O N O T D I S C A R D Please contact your Heat Glo dealer with any questions or concerns For the number of your nearest Heat Glo dealer please visit www heatnglo com ...

Reviews: