For all side wall horizontally vented gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7)

feet above finished grade in the area of the venting, includ-

ing but not limited to decks and porches, the following re-

quirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter

shall observe that a hard wired carbon monoxide detector

with an alarm and battery back-up is installed on the floor

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gasfitter shall observe that a

battery operated or hard wired carbon monoxide detector

with an alarm is installed on each additional level of the

dwelling, building or structure served by the side wall hori-

zontal vented gas fueled equipment. It shall be the respon-

sibility of the property owner to secure the services of qual-

ified licensed professionals for the installation of hard wired

carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, the

hard wired carbon monoxide detector with alarm and bat-

tery back-up may be installed on the next adjacent floor

level.

In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply with

the above requirements; provided, however, that during said

thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance

with the above provisions shall comply with NFPA 720 and

be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently

mounted to the exterior of the building at a minimum height

of eight (8) feet above grade directly in line with the ex-

haust vent terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall read, in

print size no less than one-half (1/2) inch in size, 

“GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally

vented gas fueled equipment shall not approve the installa-

tion unless, upon inspection, the inspector observes carbon

monoxide detectors and signage installed in accordance with

the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1

through 4:
• The equipment listed in Chapter 10 entitled “Equipment

Not Required To Be Vented” in the most current edition

of NFPA 54 as adopted by the Board; and

• Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure sepa-

rate from the dwelling, building or structure used in whole

or in part for residential purposes.

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall hor-

izontally vented gas equipment provides a venting system

design or venting system components with the equipment,

the instructions provided by the manufacturer for installa-

tion of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting

system design or the venting system components; and

• A complete parts list for the venting system design or

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall

horizontally vented gas fueled equipment does not provide

the parts for venting the flue gases, but identifies “special

venting systems”, the following requirements shall be sat-

isfied by the manufacturer:
• The referenced “special venting system” instructions shall

be included with the appliance or equipment installation

instructions; and

• The “special venting systems” shall be Product Approved

by the Board, and the instructions for that system shall

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equipment,

all venting instructions, all parts lists for venting instruc-

tions, and/or all venting design instructions shall remain

with the appliance or equipment at the completion of the

installation.

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

NOTE:

The following requirements reference various

Massachusetts and national codes not contained in

this document.

G. Requirements for the Commonwealth of

Massachusetts

Summary of Contents for LCOR-HV-IPI

Page 1: ...her flammable materials away DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included This appliance may be installed as an OEM installation in manufactured home US...

Page 2: ...f the fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will vo...

Page 3: ...3 A Vent System Approvals 23 B Installing Vent Components 30 C Vent Termination 32 Step 4 Positioning Leveling and Securing the Fireplace 35 Step 5 The Gas Control System 35 Step 6 The Gas Supply Line...

Page 4: ...R COR HV IPI 2005 900 Rev M 9 08 4 3 2 5 4 6 1 Log Set Assembly Service Parts Diagram Service Parts Pier HV IPI Beginning Manufacturing Date June 2003 Ending Manufacturing Date ______ 8 9 10 11 7 Par...

Page 5: ...bly GLA MS X Ember Mesh Assembly 2006 008 Exhaust Baffle 385 128 Fiberglass Rope 060 455 Glass Latch Assembly 386 122A X Junction Box 4021 013 X Lava Rock 2005 790 Mineral Wool 050 721 Non Combustible...

Page 6: ...be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas appliances are tested and approved with out requiring changes for...

Page 7: ...hall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented...

Page 8: ...ensure maximum safety and benefit Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any...

Page 9: ...5mm 42 5 8 1082mm 8 205mm 12 305mm ELECTRICAL ACCESS GAS LINE ACCESS 34 3 4 883mm 4 1 16 102mm 4 1 2 114mm 4 3 4 121mm 2 5 16 58mm 37 7 16 950mm 17 15 16 455mm 24 610mm 21 9 16 547mm 32 5 16 820mm 21...

Page 10: ...183mm 42 1067mm 32 5 16 821mm 21 9 16 548mm 36 3 16 919mm 2 5 16 58mm 4 3 4 121mm 4 1 16 102mm 4 1 2 114mm ELECTRICAL ACCESS GAS LINE ACCESS 12 305mm 4 1 2 114mm 2 9 16 64mm 24 610mm 8 1 2 216mm 34 3...

Page 11: ...5mm 8 205mm 34 3 4 882mm 10 254mm 7 1 4 184mm 4 3 4 121mm 32 5 16 821mm 37 7 16 950mm ELECTRICAL ACCESS GAS LINE ACCESS 42 5 8 1083mm 2 9 16 64mm 2 5 16 58mm 17 15 16 455mm 21 9 16 547mm 24 1 8 612mm...

Page 12: ...t the face of the fireplace is one inch 25 mm The metal ends of the fireplace may NOT be recessed into combustible construction Note Refer to Figure 4B for dimensions and appliance locations if instal...

Page 13: ...ceiling is measured from the top of the unit excluding the standoffs see Figures 37 38 The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the...

Page 14: ...23 35 3 4 48 ST HV IPI 47 5 8 42 1 2 23 35 3 4 48 L RCOR HV IPI 42 1 8 42 1 2 28 3 4 35 3 4 48 Figure 5 Framing Dimensions NOTE DIMENSIONS SHOWN IN INCHES Shows center of 10 x 12 vent framing holes fo...

Page 15: ...AP 1 1 4 INCHES AT EACH JOINT Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4...

Page 16: ...iguration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in v...

Page 17: ...ctor into two pieces Do this by bending the part back and forth until it breaks see Figure 10 1 2 3 4 5 SETTINGS 1 2 3 4 5 5 Center the Flue Restrictor on vent and secure in place using two self tappi...

Page 18: ...2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H 50 MAX 15 2m NATURAL GAS VENTING WITH ONE 90 ELBOW V FT H FT 900...

Page 19: ...10mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m NATURAL GAS VENTING WITH TWO 90 ELBOWS V V1 FT H FT 900 E...

Page 20: ...610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m H H1 12 MAX 3 6m H H1 18 MAX 5 5m NATURAL GAS VENTING W...

Page 21: ...4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V V1 H H1 H2 50 MAX 15 2m H H1 H2 12 MAX 3 6m H H1 H2 18 MAX 5 5m NATURAL GAS VENTING WITH TH...

Page 22: ...AX 914mm 2 MIN 610mm 6 MAX 1 83m 3 MIN 914mm 9 MAX 2 7m 4 MIN 1 22m 12 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 83m 18 MAX 5 5m V V1 H H1 50 MAX 15 2m PROPANE VENTING WITH THREE 90 ELBOWS V V1 FT H H1...

Page 23: ...f the unit horizontally the elbow cover plate must first be removed from the unit see Figure 20 The elbow can be removed from the unit by aligning the seams of the elbow to the arrows on the surroundi...

Page 24: ...each succeed ing component into place Ensure that each succeeding vent component is secure ly fitted and locked into the preceding component in the vent system Securing pipe sections with a maximum o...

Page 25: ...s To attach and secure the termination to the last section of horizontal vent refer to the Cinch Pipe and Termination Cap installation instructions Push on and snap lock as described at the beginning...

Page 26: ...en only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical...

Page 27: ...ECESSARY IN THE INTER EST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP ISAT LEAST 20 INCHES FROMAVER TICAL WALLAND 2 FEET BELOWAHORIZONTAL OVERHANG NOTE This a...

Page 28: ...the base pan for securing the unit to the floor The diagram below shows how to properly position level and secure the fireplace Figure 31 Proper Positioning Leveling and Securing of a Fireplace Step...

Page 29: ...exceed 2 in diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attach...

Page 30: ...rity when wiring the junc tion box Figure 34 Intermittent Pilot Ignition IPI Wiring Diagram Operation using Battery Power This fireplace has an optional battery operation The sys tem is fully function...

Page 31: ...cessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently installed NOTE If any of the original wire as...

Page 32: ...ed switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 inch insulated female connector to the...

Page 33: ...ther combustible mate rial such as wood can be placed on the top edge and sides of the fireplace Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGA tes...

Page 34: ...l Type PIER HV IPI TEMPERED ST HV IPI TEMPERED L RCOR HV IPI TEMPERED Heat Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined...

Page 35: ...should cover the remaining base pan area see Figure 46 Do not put lava rock on top of the glass teco sil Figure 46 Turn on the electric ember lights and paint the glass to a darkness as desired see Fi...

Page 36: ...ember materials for use during fire place servicing The bag of embers provided is sufficient for 3 to 5 applications Replace the glass door and a front trim door on the unit Figure 50 Placement of the...

Page 37: ...ng is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been tur...

Page 38: ...logs Cleaning Flame Sensor Rod IPI Systems Frequency Periodically By Qualified service technician Task Make a visual check of the straight flame sensor rod Use emery cloth to carefully remove any exis...

Page 39: ..._________________________________________________________ _______________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Important operating and mai...

Reviews: