Heat & Glo AT-ZC Installer'S Manual Download Page 11

8

Figure 3.

WARNING

THE EXHAUST PIPE MUST ONLY BE

CONNECTED TO THE EXHAUST

STARTING COLLAR OF THE UNIT

AND THE CENTER COLLAR OF THE

TERMINATION CAP.

THE INLET AIR PIPE MUST ONLY BE

CONNECTED TO THE INLET AIR

COLLAR OF THE UNIT AND EITHER

ATTACHED TO THE INLET AIR

COLLAR OF THE TERMINATION CAP

OR TERMINATED IN THE CHIMNEY.

This option shows
both exhaust and
inlet air vent pipes
attached the
adaptor.

TERMINATION CAP

ADAPTOR

EXHAUST VENT PIPE

INLET AIR
VENT PIPE

V= 14FT. MINIMUM
      50FT. MAXIMUM

WARNING: DO NOT BLOCK
PIPE END WITH INSULATION
OR ANY OTHER SEALING
MATERIAL.

Summary of Contents for AT-ZC

Page 1: ...ases unless a certified kit is used Please contact your Heat N Glo Fireplace dealer for any questions or concerns For the number of your nearest Heat N Glo dealer please call 612 890 8367 Printed in U...

Page 2: ...E PLACED on or near the appliance Children and adults should be ALERTED to the hazards of high surface temperature and should STAY AWAY to avoid burns or clothing ignition Young children should be CAR...

Page 3: ...stem Approvals 6 Step 2 Positioning Leveling and Securing the Insert 10 Step 3 The Gas Control Systems 10 Step 4 The Gas Supply Line 11 Step 5 Gas Pressure Requirements 12 Step 6 Wiring the Appliance...

Page 4: ...the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada High Altitude Installations U L Listed gas appliances are tested...

Page 5: ...s The gas logs are packaged separately and must be field installed Read all of the instructions before starting the installation Follow these instructions carefully during the installation to ensure m...

Page 6: ...PARTS HAVE BEEN REPLACED AND THE FIREPLACE HAS BEEN REAPPROVED BY THE AUTHORITY HAVING JURISDICTION 4 The solid fuel fireplace s flue damper must be fully locked in the open position or removed for in...

Page 7: ...ZC TOP VIEW MINIMUM FIREPLACE SIZE FRONT WIDTH 23 3 4 603mm REARWIDTH 15 572mm DEPTH 14 356mm HEIGHT 20 508mm NOTE If exhaust collar on insert and fireplace damper do not line up add 4 inches 102mm to...

Page 8: ...stion air and exhaust vent pipes NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE USED Detailed installation instructions are included with each vent termination kit and should be used in conjunction wit...

Page 9: ...square flashing will allow you to mount the adaptor and cap on metal pipe Additionally the use of kit FLASH DAMP will seal off the damper opening when terminating the inlet air vent pipe just above th...

Page 10: ...PECIFY MINIMUM CHIMNEY AND OR VENT HEIGHT ABOVE THE ROOF TOP THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY FIGURE 2 SHOWS MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST 8 FEE...

Page 11: ...NECTED TO THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLET AIR COLLAR OF THE TERMINATION CAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attac...

Page 12: ...9 Figure 4 Figure 5 EXHAUST STARTING COLLAR INLET AIR STARTING COLLAR...

Page 13: ...as Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The gas control systems used with this model is Standing Pilot Ignition Standing Pilot Ignition System This system includes millivol...

Page 14: ...ping acces sible for test gauge connection should be provided for in the gas supply line leading to the unit s shut off valve Locate the gas line access hole in the outer casing of the insert Open the...

Page 15: ...er to open the needle valve tap Position a rubber hose over the tap to obtain the pressure reading The fireplace and its individual shut off valve must be disconnected from the gas supply piping syste...

Page 16: ...the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace valve pigtails WARNING DO NOT CONNECT 110 120 VAC TO THE REMOTE W...

Page 17: ...ot need to be positioned If the logs have been packaged separately refer to the installation instructions that accompany the logs Save the log instructions with this manual If sooting occurs the logs...

Page 18: ...ng fireplace servicing Replace the glass door Reset the three glass eye bolts be sure they are securely latched Replace the trim door 1 Lift the top trim door up and out of the unit 2 Pull out and rot...

Page 19: ...e wire leads and insert the short wires of the ON OFF switch through the hole at the upper right corner of the surround and push the back of the switch through the hole it will be retained in the hole...

Page 20: ...unit Then push flush on unit and secure by bending three holding tabs downward NOTE PLACE THE THREE INSULATION PIECES INTO THE CAVITIES AT THE BACK OF THE SURROUND BEFORE POSITIONING THE INSERT INTO T...

Page 21: ...all amount of air will be in the gas supply lines When first lighting the appliance it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the appliance...

Page 22: ...e information see Placing Ember Material in the INSTALLERS GUIDE Cleaning Once annually Qualified Brush or vacuum the control Burner Service compartment fireplace logs and Controls Technician burner a...

Page 23: ...20 STANDING PILOT 3 8 10 mm Figure 14 Burner Flame Patterns MAKE SURE THE FLAMES ARE STEADY NOT LIFTING OR FLOATING Figure 15 Pilot Ignitor Flame Patterns...

Page 24: ...24 Accessories Continued ZC 3624 3 DF ZC Carch Trim Door ZC 3627 4 DF ZC Trim Door ZC 4028 3 ZC 3627 3...

Page 25: ...25 DF ZC32 Trim Door DF ZC36 Trim Door DF ZC32 Carch Trim Door DF ZC36 Carch Door Accessories Continued...

Reviews: