Vent-Free Gas Stove User’s Manual  

Installation (cont.)

CONNECTING TO A GAS SUPPLY

The installer must supply an external regulator for liquid propane. For natural gas, the gas supplier supplies 

the external regulator. The external regulator reduces incoming gas pressure, and the pressure must be 

reduced to between 

11" and 14" of water column for propane and between 5" and 10.5" of water column 

for natural gas

. Heater regulator damage could occur if the pressure of the incoming gas is not reduced. 

Install the external regulator with the vent pointing down as shown in Fig. 12. The purpose of pointing the 

vent down is to protect it from freezing rain or sleet.

*The equipment shutoff valve can be purchased from your local home center store.

A qualified service technician must connect heater to gas supply. Follow all local codes.

WARNING

Never connect the heater directly to the gas supply. This heater requires an external 

regulator (not supplied). The external regulator between the gas supply and heater 

must be installed. Your gas supplier provides the external regulator for natural gas.

CAUTION

Never  connect  the  heater  to  private/non-utility  gas  wells  (commonly  known  as

wellhead gas).

WARNING

Equipment Shutoff Valve With 

1/8" NPT Tap*

Approved

Flexible

Gas Line

or 1/2"

Black Pipe

3" Minimum

Sediment Trap

Propane

 

From 

External 

Regulator (11" 

W.C. to 14" W.C. 

Pressure) 

Natural

From Gas Meter

Fig. 13—Gas Connection

External

Regulator

with Vent

Pointing

Down

Propane

Supply

Tank

Fig. 12—Regulator Conversion

IMPORTANT: 

Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for 

turning on or shutting off the gas to the heater. Apply pipe joint sealant lightly to the male threads. This 

prevents excess sealant from going into the pipe. The heater valves may become clogged if excess 

sealant gets into the pipes.

Use only new black iron or steel pipe. Internally tinned copper tubing may be used 

in certain areas, depending on your local codes. Use pipe of 1/2" diameter or greater 

to allow proper volume gas to heater. If the pipe is too small, loss of pressure will occur. Installation must 

include  an  equipment  shutoff  valve,  union,  and  plugged  1/8"  NPT  tap.  The  NPT  tap  must  be  located 

within reach for the test gauge hook up and be upstream from heater (see Fig. 13).

CAUTION

Pipe Nipple    Cap    Tee Joint

(5" W.C. to 

10.5" W.C. Pressure)

Summary of Contents for HRSQ25MV

Page 1: ...ry or loss of life This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type gas i...

Page 2: ...g instructions before operating this heater IMPORTANT Read all instructions and warnings carefully before starting installation Failure to follow these instructions may result in possible injury to pe...

Page 3: ...injury Read the following instructions and precautions in User s Information Manual provided with this heater WARNING CALIFORNIA PROPOSITION 65 Fuels used in gas fired heaters and the products of com...

Page 4: ...ter has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See AIR FOR COMBUSTION AND VENTILATION page 8 If the heater keeps shutt...

Page 5: ...g QUALIFIED INSTALLING AGENCY Only a qualified agency should install and replace gas piping gas utilization equipment or accessories and or repair and service such equipment Qualified agency means any...

Page 6: ...nough fresh air and cuts off the main burner gas in the event of flame out LEG KIT Four 4 support legs and twelve 12 support leg screws are included with Stove See page 14 Optional FAN KIT The fan has...

Page 7: ...f Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall...

Page 8: ...er 1 000 BTU hr 4 8 m3 per kW of the total input rating of all appliances installed in that space An unconfined space has a volume not less than 50 cu ft per 1 000 BTU hr 4 8 m3 per kW of the total in...

Page 9: ...heater 40 000 BTU hr Other gas appliances ____BTU hr Vent free heater 30 000 BTU hr Total ____BTU hr Total 70 000 BTU hr Do not include direct vent gas appliances Direct vent appliances draw combustio...

Page 10: ...ect directly to the outdoors or spaces that open to the outdoors Such spaces may include attics or crawl spaces Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 for the required size of ventilatio...

Page 11: ...ot install the heater Contact the place where this heater was purchased for a heater appropriate for your gas supply NOTICE State or local codes may only allow operation of this appliance in a vented...

Page 12: ...d burner are at least 18 above the floor and b locate the heater where moving vehicles will not hit it CAUTION Fig 3 Clearances as Viewed from the Front of the Heater Inches Minimum Clearance to Combu...

Page 13: ...g the Blower Fig 4 Grounded Three Prong Receptacle Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after...

Page 14: ...Legs to the heater base ensure you have the following items 4 Support Legs 12 Support Leg Screws 1 To prevent scratching place a blanket on the floor where the heater will be placed for leg installat...

Page 15: ...e numbers listed below Number of Logs 5 1 Place log 1 on pins between burners and log 2 and 3 on pins in front of burner 2 Place log 4 onto pins in log 1 and 2 Fig 10 Failure to position the parts in...

Page 16: ...for natural gas CAUTION Never connect the heater to private non utility gas wells commonly known as wellhead gas WARNING Equipment Shutoff Valve With 1 8 NPT Tap Approved Flexible GasLine or1 2 BlackP...

Page 17: ...ible Gas Line 24 Min or 1 2 Black Pipe 90 Deg 3 8 NPT x 3 8 Flare Fitting or 3 8 Street Elbow Sealant Resistant to natural or propane gas Shutoff Valve 1 Depending on where your gas supply line is loc...

Page 18: ...nt shutoff valve see Fig 17a 17b 4 Use a mixture of liquid soap and water in the gas joints to check for leaks bubbles may indicate a leak 5 Immediately correct all leaks Pressure Testing Heater Gas C...

Page 19: ...he gas supplier s instructions If you cannot reach your gas supplier call the fire department C Push in or turn the gas control knob using only your hand Never use tools If the knob will not push in o...

Page 20: ...e pilot lights Release the control knob If the control knob does not pop up when released stop and immediately call a qualified service technician or gas supplier 8 Turnthecontrolknobcounterclockwise...

Page 21: ...me is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut down If pilot flame pattern is incorrect as shown in Figure 21 Turn the he...

Page 22: ...should not be dark or have an orange reddish tinge NOTE When using the heater the first time the flame will be orange for approximately one hour If the burner flame pattern is incorrect as shown in F...

Page 23: ...st fans WARNING A vent free heater draws room air to support combustion Lightweight particles suspended in the air including dust carpet fibers candle or tobacco smoke and pet hair will be drawn towar...

Page 24: ...is off and lightly blow air through the air inlet hole If you do not have compressed air blowing through a drinking straw will also work Fig 33 Pilot Air Inlet Hole Verify proper operation after servi...

Page 25: ...ed 5 Gas regulator setting is incorrect 6 Control knob not in PILOT position 7 Depleted gas supply propane 1 Turn on the gas supply or the open equipment shutoff valve 2 Fully press in the control kno...

Page 26: ...layed ignition of the burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner see CARE AND MAINTENANCE pages 22 24 or contact customer service Th...

Page 27: ...resentonwindows 1 Not enough combustion ventilation air is provided 1 Refer to AIR FOR COMBUSTION AND VENTILATION requirements pages 8 10 There is slight smoke or odor during initial operation 1 Resid...

Page 28: ...28 Vent Free Gas Stove User s Manual Parts List...

Page 29: ...29 Vent Free Gas Stove User s Manual NOTES...

Page 30: ...30 Vent Free Gas Stove User s Manual NOTES...

Page 31: ...or labor when provided by the company Warranty part s MUST be obtained through authorized dealers of this product and or the company who will provide original factory replacement parts Failure to use...

Page 32: ...vice or repair question please contact your dealer Empire Comfort Systems Inc Belleville IL www empirecomfort com SINCE 1932 If you have a general question about our products please e mail us at info...

Reviews: