background image

1 4

TROUBLESHOOTING

Note :

    All          troubleshooting

items    are    listed    in  order    of
operation.

WARNING:

  Only    a   qualified

service  person  should  service and
repair  heater.

CAUTION:

 Never  use  a  wire,

needle,  or  similar  object   to  clean
ODS/pilot.    This    can    damage
ODS/pilot  unit.

OBSERVED  PROBLEM

When  ignitor  button  is  pressed  in,
there  is  no  spark  at  ODS/pilot.

When   ignitor   button   is   pressed  in,
there  is  a  spark  at  ODS/pilot  but  no
ignition.

ODS/pilot    lights   but flame   goes out
when   control   knob is released.

POSSIBLE  CAUSE

1.   Ignitor electrode is positioned
      wrong.
2.   Ignitor electrode is broken.
3.   Ignitor electrode is not connected
       to ignitor cable.
4.   Ignitor cable  pinched  or wet.

5.   Broken ignitor cable.
6.   Bad piezo ignitor.

1.  Gas  supply    is  turned    off    or
    equipment  shutoff  valve is closed.
2.    Control  knob  not fully  pressed  in
       while  pressing  ignitor  button.
3.    Air  in  gas  lines  when  installed.

4.    ODS/pilot  is  clogged.

5.    Gas regulator  setting is not correct.
6.   Control  knob not in  PILOT  position.
7.   Depleted gas supply.

1.   Control knob is not fully pressed in.
2.   Control  knob  is not  pressed  in
      long enough.
3.   Equipment  shutoff  valve  is not
      fully open.
4.   Thermocouple   connection   loose
      at  control  valve.
5   P i l o t   f l a m e   i s   n o t   t o u c h i n g
    t h e r m o c o u p l e .     T h i s   a l l o w s
    thermocouple to cool, causing pilot
    flame  to  go  out. This  problem
    could  be  caused  by  one  or  both
    of  the  following:
   A)  Low gas pressure
   B)  Dirty or partially clogged ODS/pilot
6.   Thermocouple   damaged.
7.   Control valve   damaged.

REMEDY

1.   Replace ignitor.

2.   Replace ignitor.
3.   Reconnect ignitor cable.

4.   Free  ignitor  cable  if  pinched  by
       any       metal     or     tubing.    Keep
      ignitor   cable  dry.
5.   Replace   ignitor  cable.
6.   Replace   piezo  ignitor.

1.   Turn    on    gas    supply    of   open
      equipment  shutoff  valve.
2.  Fully   press   in   control   knob
      while  pressing  ignitor  button.
3.   Continue   holding    down    control

knob.  Repeat  igniting  operation

      until  air  is  removed.
4.   Clean   ODS/pilot   (see    Cleaning
      and  Maintenance.  Page  13)  or

replace   ODS/pilot  assembly

5.   Replace  gas regulator.
6.   Turn  control  knob  to  pilot  position.
7.   Contact local propane/LP gas

campany.

1.   Press in control knob fully.
2.   After  ODS/pilot lights, keep control
      knob  pressed  in  30  seconds.
3.    Fully  open equipment shutoff valve.

4.  Hand   tighten   until   snug,   then
      tighten 1/4  turn more.
5.   A)  Contact  local  propane/LP  gas
      company.
      B)    Clean   ODS/pilot (see  Cleaning
     and   Maintenance.  Page 13)   or
      replace  ODS/pilot  assembly.

6.   Replace   thermocouple.
7.   Replace  control  valve.

Summary of Contents for HB20ML-1

Page 1: ...ust be performed by a qualified installer service agency or gas supplier HB20TL 1 HB30TL 1 HB20ML 1 HB30ML 1 Table of Contents ImportantSafetyInformation 2 Product Features 3 ProperVentilation FreshAi...

Page 2: ...e of heater becomes very hot when running heater Keep children and adults away from hot surface to avoid burns or clothing ignition Heater will remain hot for a time after shuting down Allow surface t...

Page 3: ...tion Inc Batterymarch Park Quincy MA 02269 QUALIFIED INSTALLING AGENCY Installation and replacement of gas piping gas utiliza tion equipment or accessories and repair and servicing of equipment shall...

Page 4: ...of the methods described in the National Fuel Gas Code ANS Z223 1 Section 5 3 or applicable local codes Unusually Tight Construction The air that leaks around doors and windows may provide enough fre...

Page 5: ...uel burning appliances in the space Vent free heater Btu Hr Gas water heater Btu Hr Gas furnace Btu Hr Vented gas heater Btu Hr Gas Fireplace logs Btu Hr Other gas appliances Btu Hr Total Btu Hr Do no...

Page 6: ...pment shutoff valve ground joint union test gauge connection sediment trap tee joint pipe wrench A CSA AGA design certified equip ment shutoff valve with 1 8 NPT tap is an acceptable alternative to te...

Page 7: ...s near bottom corners of lower front panel 2 Pull bottom of lower front panel forward then down see Figure 7 Methods For Attaching Mounting Bracket To Wall Only use last hole on each end of mounting b...

Page 8: ...mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firmly f...

Page 9: ...re regulator with wrench when connecting it to gas piping and or fittings CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP gas Figure 14 Gas Connection The installer must supply...

Page 10: ...ve to control valve see Figure 16 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater pages 10 and 11 for t...

Page 11: ...ounterclockwise to desired heating Level The main burner should light Set control knob to any heat level between HI and LO This increases or decreases the burner flame height At times the room may exc...

Page 12: ...near the floor If you smell gas STOP Follow B in the safety information on the side of heater If you can t smell gas go to the next step 5 Push in and turn control knob counterclockwise to PILOT posit...

Page 13: ...sembly see Figure 25 With the unit off lightly blow air through the air inlet hole You may blow through a drinking straw if compressed air is not available Figure 25 Pilot Inlet Air Hole CLEANING HEA...

Page 14: ...ff valve is not fully open 4 Thermocouple connection loose at control valve 5 Pilot flame is not touching thermocouple This allows thermocouple to cool causing pilot flame to go out This problem could...

Page 15: ...ile heating or contracting while cooling 1 When heated vapors from furniture polish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance pa...

Page 16: ...ctions Page 10 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections Page 10 1 This is common with most heaters if noise...

Page 17: ...optional fan kit part HAB01 fits all models noted in this manual The fan has 3 settings ON OFF Auto The thermostatically controlled HAB01mproves heater efficiency and includes installation and operat...

Page 18: ...1 8 ILLUSTRATED PARTS BREAKDOWN THERMOSTAT MODELS HB20TL HB30TL...

Page 19: ...ass Retainer Lower Glass Retainer Self Tapping Screw Thermostat Valve Assembly Screws Thermostat Valve Base Ignitor Assembly Ignitor Line Pressure Regulator Washer Self Locking Screw Main Inlet Tube A...

Page 20: ...2 0 ILLUSTRATED PARTS BREAKDOWN NON THERMOSTAT MODELS HB20ML HB30ML...

Page 21: ...g Screw Control Valve Ignitor Line Control Knob Assembly Control Valve Fixed Nut Pressure Regulator Washer Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Lower Gas Outline Tube Assembly...

Page 22: ...2 2...

Page 23: ......

Page 24: ......

Reviews: