Hearth Technologies R-5500TRHC Installer'S Manual Download Page 17

19

Figure 18.

B.  Installing Vent Components

After determining which set of starting collars will be used
(top or rear), follow venting instructions accordingly.

Venting Out the Rear Vent

Remove the installed rear seal cap from the rear starting
collars by cutting the strap at each end. (see Figure 18).
Follow the vent configuration tables accordingly.

Remove the insulation from the 

REAR

 five inch flue, pull

the heat shield out from outside of the firebox.

WARNING: THE TOP HEAT SHIELD (INSIDE THE
FIREBOX) MUST REMAIN ATTACHED IF THE
VENT SYSTEM IS ATTACHED TO THE REAR
STARTING COLLARS. SEE FIGURE 18.

Venting Out the Top Vent

Remove the two screws in the top vent collar seal cap and
remove the top vent collar seal cap and the two pieces of
insulation inside the top two starting collars (See Figure 18).

Remove the heat shield from inside the 

TOP

 five inch flue

from outside of the firebox.

You have to take the glass off again for positioning the logs
when the unit is finally installed in place and finished around
it. Re-install the glass door.  Attach vent system to the top
starting collars.

WARNING: FAILURE TO REMOVE  INSULA-
TION IN THE SET OF COLLARS YOU ARE US-
ING COULD CAUSE A FIRE.

WARNING:  THE REAR VENT COLLAR SEAL
CAP MUST REMAIN ATTACHED TO THE REAR

VENT COLLARS IF THE VENT SYSTEM IS ATTACHED
TO THE TOP STARTING COLLARS.  SEE FIGURE 18.

WARNING: YOU MUST LEAVE THE INSULA-
TION IN PLACE IN THE SET OF COLLARS YOU
ARE NOT USING.

If your vertical vent component is over 10 feet, you may
want to install the included vertical baffle to improve flame
appearance. Vertical baffle is located in the bag containing
the instruction manual. Center the vertical baffle on the five
inch flue being used, and with self tapping screws secure
the baffle to the inside of the firebox.

!

!

!

!

1.  Attach the First Vent Component to Starting Collars

To attach the first vent component to the starting collars
of the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the 5 inch (127mm) fireplace starting collar.

• Make sure that the fiberglass gasket supplied with the

fireplace seals between the first 8-5/8 inch (219mm) vent
component and the outer fireplace wrap.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior
beads into the fireplace collar or previously installed com-
ponent end with four (4) equally spaced indented sections.

• When the internal beads of each 8-5/8 inch (219mm)

outer pipe line up, rotate the pipe section clockwise
about one-quarter (1/4) turn. The vent pipe is now locked
together.

• The first 90° elbow installed in the vent system of a

rear venting fireplace 

MUST BE

 in a vertical position.

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

 3/8”

(9.5mm)

Cut the seal cap

strap and remove white

gasket material.

CUT

HERE

Venting Out Rear

Venting Out Top

HEAT

SHIELD

DISCARD

 INSULATION

and

HEAT SHIELD

HEAT

 SHIELD

INSULATION

DISCARD  BOTH

PIECES and

HEAT SHIELD

SEAL 

CAP

SEAL

CAP

Figure 19.
Attaching First Vent Component to Starting Collars

‹

Summary of Contents for R-5500TRHC

Page 1: ...TURE REFERENCE 1 This appliance may be installed in an af termarket permanently located manufac tured mobile home where not prohibited by local codes 2 This appliance is only for use with the type of...

Page 2: ...instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this applia...

Page 3: ...stalling the Vent System 12 A Vent System Approvals 12 B Installing Vent Components 19 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 26 Step 5 The Gas Control System 26...

Page 4: ...ited States or to the CSA C22 1 Canadian Electric Code in Canada This model may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U...

Page 5: ...Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Hearth Technologies Warranty will be voided by and Hearth Technologies disclaims any responsibili...

Page 6: ...879mm 8 5 8 219mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323mm 3 1 2 90mm GAS LINE ACCESS 2 1 8 55mm 6 7 8 174mm 14 1 4 362mm 8 5 8 219mm VENT COLLARS 21 1 2 548mm 11 5 8 297mm 28 1 2 724...

Page 7: ...ng the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not requir...

Page 8: ...ng material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 12 x 12 vent...

Page 9: ...36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm...

Page 10: ...d Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in vent configura...

Page 11: ...385 128 See flue restrictor installation in structions CAP V Figure 8 Exhaust Shield FLUE RESTRICTOR EXHAUST SHIELD Figure 6 Flex Vent The flex vent must be supported with the spacing between support...

Page 12: ...two self tapping screws on setting 2 see Figure 10 45 DEGREE ELBOW 90 DEGREE ELBOWS H Figure 9 Flue Restrictor BREAK HERE 4 Break the Flue Restrictor into two pieces Do this by bending the part back a...

Page 13: ...3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX 6 2m Figure 13 Venting with One 90 Elbow NOTE If a 90o elbow is first attached to the unit the maximum horizontal run i...

Page 14: ...with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H H1 40 MAX 12 4m H H1 20 MAX 6 2m V V...

Page 15: ...40 MAX 12 4 m H 8 MAX 2 48 m H H 1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m 10 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20...

Page 16: ...1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m H H1 20 MAX 6 2m NOTE V V1 H H1 40 MAX 12 4m Figure 17 Venting with th...

Page 17: ...S YOU ARE NOT USING If your vertical vent component is over 10 feet you may want to install the included vertical baffle to improve flame appearance Vertical baffle is located in the bag containing th...

Page 18: ...ion with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 21 CORRECT INCORRECT 2 Fasten the shield in place using the pilot holes provided in the part The shield shoul...

Page 19: ...ontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the center of the hor...

Page 20: ...g using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 28 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic p...

Page 21: ...POSITIONED SO THAT THE ARROW IS POINTING UP For trapezoidal cap termination kit Using screws secure the cap to the exterior wall through the flanges in the cap Figure 30 Trapezoid Termination Cap WARN...

Page 22: ...air inlet to any other ap pliance K 3 ft U S A 6 ft Canada clearance to a mechanical air supply inlet L 7 ft clearance above paved sidewalk or a paved drive way located on public property M 18 cleara...

Page 23: ...EE FIGURE 22 FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in sta...

Page 24: ...nd secure the fireplace Figure 33 Proper Positioning Leveling and Securing of a Fireplace Figure 34 Gas Control System STANDING PILOT Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WIT...

Page 25: ...r grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line...

Page 26: ...position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 1 10 120 VAC TO THE REMOTE W ALL...

Page 27: ...The joints between the finished wall and the fireplace top and sides can only be sealed with a 300 F 149 C minimum sealant WARNING WHEN FINISHING THE FIREPLACE NEVER OBSTRUCT OR MODIFY THE AIR IN LET...

Page 28: ...rned to the OFF position in which case the air would have to be purged NOTE The fireplace should be run 3 to 4 hours on the initial start up Turn it off and let it cool completely Remove and clean the...

Page 29: ...atterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the flames are steady not lifting or floati...

Reviews: