background image

1

Hearth & Home Technologies  •  B36S-AU Installation Manual  •  2563-980  •  10/19

 

 NOTE:  NOT INTENDED FOR FIREPLACE  

  INSERT. PRIMARILY A DECORATIVE AND  

  NOT A HEATING APPLIANCE.

Installation Manual

Installation and Appliance Setup

Models:

NOTICE: DO NOT

 discard this manual!

DANGER

HOT GLASS 

WILL 

CAUSE BURNS.

DO NOT TOUCH 

GLASS 

UNTIL COOLED.

NEVER 

ALLOW CHILDREN

 TO TOUCH GLASS.

A barrier designed to reduce the risk of 

burns from the hot viewing glass is provided 

with this appliance and shall be installed for 

the protection of children and other at-risk 

individuals.

• 

DO NOT

 store or use gasoline or other flam

-

mable vapors and liquids in the vicinity of this 

or any other appliance.

•  What to do if you smell gas   

DO NOT

 try to light any appliance.

DO NOT

 touch any electrical switch. 

DO 

NOT

 use any phone in your building.

-  Leave the building immediately.
-  Immediately call your gas supplier from 

a neighbor’s phone. Follow the gas sup-

plier’s instructions.

-  If you cannot reach your gas supplier, call 

the fire department.

•  Installation and service must be performed 

by a qualified installer, service agency, or the 

gas supplier.

WARNING: 

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly 

could result in serious injury, death, or 

property damage. 

B36S-AU

DO NOT PLACE ARTICLES ON OR AGAINST THIS 

APPLIANCE.
DO NOT USE OR STORE FLAMMABLE MATERIALS 

NEAR THIS APPLIANCE. 
DO NOT SPRAY AEROSOLS IN THE VICINITY OF 

THIS APPLIANCE WHILE IT IS IN OPERATION.  
DO NOT MODIFY THIS APPLIANCE.

Ref No GMK10598

AS/NZS 5263.1.8

CAUTION!  Risk of Fire!  DO NOT

 store instruction manuals inside fireplace cavity.                                 

High temperatures could cause a fire.       

INSTALLER:  Leave this manual with the appliance, not inside the appliance. 

CONSUMER:  Retain this manual for future reference.  Do not store inside the appliance.

Contact your dealer with questions regarding installation, operation or service.

Summary of Contents for B36S-AU

Page 1: ...immediately Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property...

Page 2: ...n Location and Vent Information A Vent Termination Minimum Clearances 13 B Chimney Diagram 14 C Approved Pipe 15 D Use of Elbows 15 E Vent Diagrams 16 F Measuring Standards 17 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 30 B Wall Penetration Framing Firestops 31 C Ceiling Firestop Floor Penetration Framing 32 D Install Attic Insulation Shield 32 6 Appliance Preparation A Vent C...

Page 3: ... Was a conversion performed ___________________________ Leak check performed and inlet pressure verified ___________________________ Verified proper air shutter setting for installation type ___________________________ Finishing Section 10 Pg 47 49 Combustible materials not installed in non combustible areas ___________________________ Verified all clearances meet installation manual requirements ...

Page 4: ... limit NG inlet pressure to 2 49 kPa and Propane inlet pressure to 3 25 kPa to ensure optimum product performance The inline fuel pressure regula tor may be needed if any of the following symptoms exist pilot jetting a highly visible pilot flame flame variation etc The inline pressure regulator should be installed in the gas line upstream of the appliance gas valve either at the appliance or in th...

Page 5: ...consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered non combustible materials F Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plasti...

Page 6: ...Plumb line Safety glasses gloves Wrenches Reciprocating saw 1 4 in nut driver Non corrosive leak check solution 1 2 3 4 in 13 19 mm length 6 or 8 Self drilling screws Caulking material 300 ºF 149 ºC minimum continuous exposure rating Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified se...

Page 7: ...RNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation oth...

Page 8: ...refer to Section 5 Figure 3 1 Appliance Dimensions Location Inches Millimeters Location Inches Millimeters A 36 914 L 16 5 16 414 B 31 1 8 791 M 1 2 13 C 27 3 16 691 N 25 3 4 654 D 18 1 16 459 O 12 7 8 327 E 34 5 16 872 P 15 7 8 403 F 31 787 Q 6 5 8 168 G 6 7 8 175 R 30 762 H 2 3 8 60 S 2 3 16 56 I 36 7 16 926 T 6 152 J 8 203 U 1 1 16 27 K 8 13 16 224 V 23 3 8 594 N O P T S R GAS LINE ACCESS K L M...

Page 9: ...E F Figure 3 2 Decorative Front Dimensions IMPORTANT This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Decorative barrier front must be ordered at time of fireplace purchase If decorative barrier front is not present contact dealer Note See Section 10 for mantel and finishing requ...

Page 10: ...1067 940 1511 25 13 1117 1581 413 1232 1746 383 191 181 B Appliance Location and Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls and allow suf ficient clearance for heat management systems venting See Figure 3 3 and Figure 3 4 WARNING Risk of Fire or Burns Provide adequate clearance around air openings and for serv...

Page 11: ... one 90º elbow MINIMUM FRAMING DIMENSIONS Models A B C D E F G H I J DVP Pipe SLP Pipe Rough Opening Height DVP Pipe SLP Pipe Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of Appliance Rough Opening Width Rough Opening Width Rough Opening Depth Rough Opening Depth B36S AU in 10 8 5 8 34 3 4 16 1 4 16 1 4 37 32 0 0 1 2 1 2 ...

Page 12: ...sprinkler activation temperature classified as Extra High Keep sprinkler head away from vent and chimney Chases should be constructed and insulated in the same manner as the thermal envelope of the home based on the code requirements for that climate zone to prevent air leakage and draft problems The chase is an extension of the building thermal envelope To further prevent drafts and air leakage t...

Page 13: ...IS X 305 mm LOWEST DISCHARGE OPENING 510 mm MIN 610 mm MIN Angle H Min mm 0 26 6 500 26 6 30 3 500 30 3 33 7 500 33 7 36 9 610 36 9 39 8 760 39 8 42 5 990 42 5 45 0 1 220 45 0 49 4 1 520 49 4 53 1 1 830 53 1 56 3 2 130 56 3 59 0 2 290 59 0 60 3 2 440 H minimum may vary depending on regional snowfall Refer to local codes Figure 4 2 Staggered Termination Caps Wood or Fuel Oil Termination Cap B Gas T...

Page 14: ...355 Appliances from 32 MJ h to 53 MJ h 300 410 Appliances 53 MJ h and above 300 460 c From a return wall or external corner 500 300 d From a gas meter M 1000 1000 e From an electricity meter or fuse box P 500 500 f From a drain or soil pipe 150 75 g Horizontally from any building structure unless appliance approved for closer installation or obstruction facing a terminal 500 500 h From any other f...

Page 15: ...DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DVP12A 3 to 12 76 to 305 2 1 8 8 1 2 54 216 SLP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters SLP4 4 102 2 3 4 70 SLP6 6 152 4 1 4 108 SLP12 12 305 8 1 2 216 SLP24 24 610 17 432 SLP36 36 914 25 1 2 648 SLP48 48 1219 34 864 SLP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 SLP12...

Page 16: ...nted Amaximum of three 90º elbows or six 45º elbows may be used in any vent configuration Some elbows may be installed horizontally See Figure 4 23 and 4 25 Top Vented Amaximum of four 90º elbows or eight 45º elbows may be used in any vent configuration Some elbows may be installed horizontally See Figure 4 16 Elbows may be placed back to back anywhere in the system Any 90º elbow may be replaced w...

Page 17: ...rizontal terminations are measured to the outside mounting surface flange of termination cap See Figure 4 7 Vertical terminations are measured to top of last section of pipe See Figure 4 8 Horizontal pipe installed level with no rise MEASURE TO SHADED SURFACE OUTSIDE MOUNTING SURFACE Figure 4 7 Measure to Outside Mounting Surface Figure 4 8 Measure to Top of Last Section of Pipe Figure 4 9 Measure...

Page 18: ... V1 H1 MAX 40 ft 12 2 m See Warning Figure 4 10 One Elbow Fire Risk Install required minimum vertical venting to prevent overheating and fire When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow Installation of the elbow heat shield is required when the clearance to combustible material above the first ven...

Page 19: ...05 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING Note Use SLP Series components only INSTALLED HORIZONTAL...

Page 20: ... 914 mm 6 ft 1 8 m 2 1 2 ft 762 mm 5 ft 1 5 m 10 ft 3 0 m 3 1 2 ft 1 1 m 7 ft 2 1 m 14 ft 4 3 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m No specific restrictions on this value EXCEPT V1 V2 H CANNOT exceed 40 ft 12 2 m V1 V2 H1 H2 MAX 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section i...

Page 21: ...liance manual bag Note Be sure to rein stall the exhaust baffle after exhaust restrictor installation Exhaust restrictor Exhaust restrictor Exhaust restrictor Instructions 1 Install the exhaust restrictor over the center of the ex haust outlet in the firebox See Figure 4 14 2 Center the exhaust restrictor in the open end of the exhaust outlet and secure through the slots on the ex haust restrictor...

Page 22: ...nued H1 V1 V2 V1 Minimum H1 Maximum V2 V1 V2 Minimum 90 Elbow Only 1 1 2 ft 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H1 MAX 15 ft 4 6 m No specific restrictions on this value EXCEPT V1 V2 H CANNOT exceed 40 ft 12 2 m V1 V2 H1 H2 MAX 40 ft 12 2 m V1 V2 H1 MAX 40 ft 12 2 m ...

Page 23: ...y INSTALLED HORIZONTALLY H1 H2 V1 V2 V1 Minimum H1 H2 Maximum V2 V1 V2 Minimum 90 Elbow Only 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m No specific restrictions on this value EXCEPT V1 V2 H CANNOT exceed 40 ft 12 2 m V1 V2 H1 H2 MAX 40 ft 12 2 m ...

Page 24: ... 10 19 24 Figure 4 17 Top Vent Vertical Termination continued Four 90º Elbows V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only V1 H1 V2 V3 H2 ...

Page 25: ... Installation Manual 2563 980 10 19 Rear Vent Horizontal Termination Figure 4 18 Figure 4 19 No Elbow One 45º Elbow H1 H1 24 in Max 610 mm H1 9 in 229 mm Maximum Note Use DVP Series components only Note Use DVP Series components only H1 ...

Page 26: ... m 5 ft 1 5 m 7 ft 2 1 m 14 ft 4 3 m H1 MAX 7 ft 2 1 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 1 2 ft 2 9 m 7 1 2 ft 2 3 m 3 ft 914 mm 6 ft 1 8 m 13 1 2 ft 4 1 m H1 MAX 7 1 2 ft 2 3 m H1 H2 H3 MAX ...

Page 27: ... m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m H1 H2 MAX V1 MIN Back to back elbows 1 2 ft 152 mm 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 ft 914 mm H MAX 6 1 2 ft 2 m V H H1 MAX 40 ft 12 2 m Note Use DVP Series components only Note Use DVP Series components only H1 V1 INSTALLED HORIZONTALLY H1 H2 V1 ...

Page 28: ...1 H2 MAX V2 V1 V2 Minimum Back to back elbows 1 1 2 ft 457 mm 1 ft 305 mm 2 1 2 ft 762 mm 1 ft 305 mm 3 1 2 ft 1 1 m 3 ft 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft 914 mm 7 1 2 ft 2 3 m 7 ft 2 1 m 14 1 2 ft 4 4 m H1 MAX 7 1 2 ft 2 3 m H1 H2 MAX 14 1 2 ft 4 4 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H CANNOT exceed 40 ...

Page 29: ... V1 H1 H2 H3 V1 Minimum H1 H2 H3 Maximum 8 ft 2 44 m 6 ft 1 83 m 9 ft 2 74 m 7 ft 2 13 m 10 ft 3 05 m 8 ft 2 44 m 10 ft 3 05 m 8 ft 2 44 m V1 H1 H2 H3 32 ft 9 75 m Maximum No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 32 ft 9 75 m Maximum H1 H2 H3 8 ft 2 44 m Maximum Note Use DVP Series components only ...

Page 30: ...l be required DVP SLP Pipe Shown 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections SLP Pipe DVP Pipe WARNING Risk of Fire Elbow heat shield MUST be installed if ...

Page 31: ...d installed The opening must be framed on all four sides using the same size framing materials as those used in the wall construction SLP pipe A wall shield firestop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be main tained DVP pipe A wall shield firestop is required on one side only on interior walls If your local inspector re qu...

Page 32: ... are not insulated See Figure 5 6 Secure in place with nails or screws Figure 5 5 Installing Ceiling Firestop Generic Appliance Shown Figure 5 6 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING ATTIC ABOVE A PIPE DVP SLP A 10 in 254 mm 9 in 229 mm A D Install At...

Page 33: ...Rotate the top heat shield to the vertical position as shown above The heat shield must remain in the vertical position Figure 6 5 Remove the seal cap Figure 6 2 For top vent remove the two screws holding the top heat shield in place Note Actual unit may look different than the fireplace shown in this section Figure 6 4 Replace the two screws as shown WARNING Risk of Fire Do not remove heat shield...

Page 34: ...nter of the fire plug 90º and remove the insulation gasket Figure 6 10 Cut the metal retaining band and fold the sides out Figure 6 8 To attach the first section of vent pipe make sure to use the fiberglass gasket to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap Note Once the seal cap has been removed it cannot b...

Page 35: ...ntain air space clearance could cause overheating and fire The diagram shows how to properly position level and secure the appliance See Figure 6 14 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Plum square and level the appliance from side to side and front to b...

Page 36: ...oining sections See Figure 7 1 OR Apply a bead of silicone sealant 300 ºF 149 C mini mum continuous exposure rating to the outside of connecting joint after joining sections OR Apply aluminum foil tape 300 ºF 149 C minimum continuous exposure rating to the outside of connect ing joint after joining sections On horizontal pipe runs it is recommended that the tape seam is positioned on the bottom si...

Page 37: ...nfiltration Caulk with a minimum of 300 ºF 149 ºC continuous exposure rating may be used to hold the part in place Continue adding vent components locking each succeeding component into place Ensure that each succeeding vent component is securely fitted and locked into the preceding component It is acceptable to use screws no longer than 1 2 in 13 mm to hold outer pipe sections together If predril...

Page 38: ... slip section is too long the inner and outer flues of the slip section can be cut to the desired length Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 7 7 NOTICE When installing a vent system with an HRC termination cap all pipe system ...

Page 39: ...ted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 7 8 and 7 9 Wall shield firestops may be used to provid...

Page 40: ... the pipe section Seal around the top of the storm collar See Figure 7 14 E Vertical Termination Requirements Install and Seal Metal Roof Flashing See minimum vent heights for various pitched roofs Section 4 Figure 4 1 to determine the length of pipe to extend through the roof Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 7 12 Use an elastomeric or si...

Page 41: ...ni mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 15 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP or 4 3 8 in 111 mm SLP the heat shield...

Page 42: ...n caps with factory supplied heat shield attached no additional wall shield firestop is required on the exterior side of a combustible wall NOTICE For certain exposures which require superior resistance to wind driven rain penetration a flashing kit and HRC caps are available When penetrating a brick wall a brick extension kit is available for framing the brick Termination Cap Specification Chart ...

Page 43: ... same wall box 8 Electrical Information Electrical Service and Repair WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 ºC rated wire Wire must have high temperature insulation Accessories Requirements This app...

Page 44: ...ency power outage Batteries should not be used as a primary long term power source Battery polarity must be correct when installing batteries When using batteries as a power source the 6VDC power adapter must be unplugged from the receptacle Do not store batteries in the battery pack when the appliance is powered by the 6VDC power adapter connected to permanent electrical service Figure 8 1 Intell...

Page 45: ...han 1 2 psig WARNING E High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 ft 610 m elevation Reduce input rate 4 for each 1000 ft 305 m above 2000 ft 610 m Note This appliance does include a manual gas shutoff valve that is located in the valve c...

Page 46: ... shutter to adjust Tighten the 1 4 in 6 mm screw Air shutter settings should be adjusted by a qualified ser vice technician at the time of installation Factory Pre Set Air Shutter Settings F Air Shutter Setting NOTICE Flames should not appear orange or stretch to the top refractory If flames are dark orange with dark smoky tips provide more primary air to the burner by opening the air shutter acco...

Page 47: ...es Comply with all minimum clearances to combustibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of decorative barrier fronts and fireplace openings Figure 10 1 Non combustible Facing Diagram 0 IN 0 IN 0 IN DRYWALL SUPPORT HIGH TEMPERATURE 300º F 149º C MIN TOP SIDE SEAL JOINT 3 IN FACING MATERIAL UP TO 1 2 IN THICK MAY BE COMBUSTIBLE TO...

Page 48: ...in 1 2 in NON COMBUSTIBLE ZONE 89 mm 13 mm Figure 10 5 Non Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening Non Combustible Mantel Legs or Wall Projections UNLIMITED TOP VIEW FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram Figure 3 1 3 IN MIN 6 IN MAX 152 mm 76 mm Note Clearance from opening to perpendicular wall Combustible Mantel Legs or Wall Projec...

Page 49: ... determined what kind of decorative front and finish ing material is going to be used on the appliance use the information below which shows the decorative barrier front models and the non combustible finishing material thickness allowed Inside Fit Firescreen Front 1 4 in 0 102 mm Finishing Note Refer to Section 3 for individual decorative barrier front dimensions as installed on appliance Flush M...

Page 50: ...irebox The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before finishing work on the whole hearth is complete Splatter guards may be factory installed or accompany the door of the unit depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalli...

Page 51: ... the shoulder screw on the burner top Locate the bottom left hole on Log 1 with the tab on the pilot hood See Figure 3 Log 2 SRV2355 702 LOGS 3732 and LOGS DV4236 Locate the bottom hole on Log 2 with the shoulder screw on the left front side of the base pan See Figure 4 Log 3 SRV2355 703 LOGS 3732 and LOGS DV4236 Locate the bottom hole on Log 3 with the shoulder screw on the right front side of th...

Page 52: ... pan resting it on the return bend Then place the top end of the log on the flat spot on the left side of Log 1 Figure 6 Figure 7 1 2 3 1 2 3 4 4 5 Figure 8 LOGS DV4236 Installed 1 2 3 4 5 6 LOGS DV4236 ONLY Log 6 SRV2391 711 LOGS DV4236 Place the right end of Log 6 on the base pan and the left end onto Logs 1 and 3 so that one limb is touching each log as shown in Figure 8 Log 5 SRV2033 710 Place...

Page 53: ...ce the dime size ember pieces near the port holes in the burner top see Figure 11 1 Failure to follow this pro cedure will likely cause lighting and sooting problems Save the remaining ember materials for use during appli ance servicing The embers provided should be enough for 3 to 5 applications Figure 11 1 Placement of Embers NO EMBERS IN SHADED AREA WARNING RISK OF EXPLOSION Place lava rock acc...

Page 54: ...ppliance by inserting into the two hood clips See Figure 11 5 F Install Decorative Front Hood Figure 11 5 Install Decorative Front and Hood GLASS ASSEMBLY LATCHES BOTH BOTTOM AND TOP Figure 11 4 Fixed Glass Assembly E Fixed Glass Assembly Removing Fixed Glass Assembly WARNING Risk of Asphyxiation Handle fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the gla...

Page 55: ...n 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm DVP WS Wall Shield Firestop Finishe...

Page 56: ... of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield 5 in 127 mm Center of the horizontal vent pipe to the vertical measuring surface Term Cap Minimum Effective Le...

Page 57: ...of Flashing Multi pak 31 in 787 mm 24 5 8 in 625 mm 13 1 4 in 337 mm RF12 Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield ...

Page 58: ...d 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap DVP TB1 Basement Vent Cap 12 in 305 mm 1 1 2 in 38 mm 7 3 8 in 187 mm 14 in 356 mm 17 3 4 in 451 mm 6 in 152 mm Figure 12 4 DVP Ven...

Page 59: ...8 3 8 in 213 mm DVP HRC SS DVP HRC ZC SS HORIZONTAL TERMINATION CAP Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical vent section is required before installing first elbow Figure 12 5 DVP Vent Co...

Page 60: ...SLP6A 2 6 51 152 SLP12A 2 12 51 305 8 3 4 in 222 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 6 in 152 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 9 7 8 in 251 mm 6 1 2 in 165 mm 9 1 4 in 235 mm SLP45 45 Elbow SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in ...

Page 61: ...mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 in 367 mm 2 5 16 in 59 mm 3 15 16 in 101 mm 6 11 16 i...

Page 62: ...mm 12 in 305 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLP TVHW Vertical Termination Cap DVP FBHT Horizontal Termination Cap SLK SNKD Snorkel Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm 4 3 4 in 121 mm 4 1 8 in 105 mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basement Vent Cap 6 IN 152 mm Figure 12 9 SLP Ser...

Page 63: ...nstructions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and will void the warranty Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the con...

Reviews: