MARCH, 2022

HD 235

PAGE 3 OF 16

HD FIRE PROTECT

PVT. LTD.

TRIM TYPES

The trims are designated as following:
W =Wet Pilot trim  D = Dry Pilot Trim

a)  Type ET-W and ET-D

  This type of trim is basic trim required to 

 

 

 

operate the deluge valve. A solenoid  valve for   

 

electric remote actuation and pressure switch  

 

for sensing & annunciation are optional.

b)  Type ETW-D and ETD-D

 

This  trim type is a combination of  components 

 

of  the ET trim along with the drip and drain 

 

trim. A solenoid valve for electric remote actuation 

 

and pressure switch for sensing & annunciation 

 

are optional.

c)  Type ETW-T and ETD-T

 

This trim type is a combination of components of 

 

the ET trims along with the test & alarm trim. 

 

A solenoid valve for electric remote actuation 

 

and pressure switch for sensing & annunciation 

 

are optional.

d)  Type NT-W and NT-D

 

This  trim type is a combination of components of  

 

the ET trim along with the test and alarm trim  

 

as well as the drip and drain trim. A solenoid valve  

 

for electric remote actuation and pressure switch  

 

for sensing & annunciation are optional.

RESETTING PROCEDURE  

A.  When priming connection is below the upstream 

valve (Stop Valve)

(i)  Close the upstream side stop valve provided below 

the deluge valve to cease the flow of water. 

(ii)  Open both the drain valves/ drain plugs and close 

when the flow of water has ceased. 

(iii) Close the release device/replace the Sprinkler if 

release was through Sprinkler/ QB Detector. 

(iv) Inspect and restore/ replace/ repair if required,  

the section of the detection system subjected to 

“Fire condition”. 

(v)  In case of dry pilot detection system, open the 

air supply valve to build-up air pressure. Open the 

priming valve fully. When top chamber pressure is 

more than 50% of the inlet pressure, open the 

upstream side of the stop valve provided below 

the Deluge valve. No water should flow into the 

system. 

(vi)  When priming shut off valve (optional) is provided 

for resetting, then the water need to be drained 

from upstream side of valve. 

B.  When priming connection is from the inlet of  

Deluge Valve (Auto resetting)  

(i)  The deluge valve will reset automatically when 

releasing devices which were responsible for 

deluge valve opening  are closed or restored 

back to their original status (i.e closing of ERS 

or replacing the damaged Sprinkler if release 

was through Sprinkler/ QB Detector or  closing 

of Solenoid valve). The reset time may be long or 

cause vibration while closing depending upon the 

system back pressure at the outlet of the valve.

CAUTION

(a)  Do not close the priming valve, downstream and  

 

upstream stop valves, while system is in service

(b)  The releasing device must be maintained in the 

 

open position, when actuated, to prevent the 

 

deluge valve from closure if anti shut off valve is 

 

not provided

(c)  While using a deluge valve in the wet pilot system 

  the height and the length of the wet pilot 

 

  detection line is to be limited as shown in 

 

 

the wet pilot sprinkler height limitation graph

(d)  Do not connect the Sprinkler Alarm outlet drain 

 

line to close a common drain as it may create  

 

back pressure & Sprinkler Alarm may not  function

(e)  Deluge valve must have support to absorb sudden 

 

opening or closing vibration shock to the piping

(f)  To avoid water damage, take precautions when 

 

opening the water supply main control valve, since 

 

water will flow from all open system valves

(g)  The responsibility of maintenance of the protection  

 

system and devices in proper operating condition 

 

lies with the owner of the system.

(h)  Deluge Valve &  its trim  shall be  maintained at a  

 

minimum temperature of 4

o

C. Heat tracing is not  

 

permitted.  

(i)  Deluge Valve must be used in pressurised system.

SYSTEM TESTING PROCEDURE

(i)  Keep the upstream side of the stop valve partially 

 

open. To avoid water flow to system side, close the 

 

system side stop valve. This valve is to be kept in 

 

open position after the testing is completed.

(ii)  Let any of the release devices to trip. This will 

 

result in a sudden drop of water pressure in 

 

the deluge valve top chamber which in turn will 

 

open the deluge valve. Close the upstream side 

 

stop valve immediately.

(iii) Reset the valve as per the procedure given 

 

 

under heading “RESETTING PROCEDURE FOR THE 

 

DELUGE VALVE”

Summary of Contents for H3

Page 1: ... 165 1mm REQUIREMENT SPECIFY IN ORDER DESCRIPTION Deluge Valve is known as a system control valve in a deluge system used for fast application of water in a spray system Deluge valve protects areas such as power transformer installation storage tank conveyor protection and other industrial application etc With the addition of foaming agent deluge valve can be used to protect aircraft hanger and in...

Page 2: ...lve drops and the Deluge valve opens c ELECTRIC RELEASE TRIM To actuate a Deluge valve electrically a solenoid valve is provided to drain the water from the top chamber of the Deluge valve A pressure switch is provided to activate an electric alarm to shut down the desired equipment or to give Tripped indication of the Deluge valve In addition to this a pressure switch can also monitor Low air pre...

Page 3: ...g connection is from the inlet of Deluge Valve Auto resetting i The deluge valve will reset automatically when releasing devices which were responsible for deluge valve opening are closed or restored back to their original status i e closing of ERS or replacing the damaged Sprinkler if release was through Sprinkler QB Detector or closing of Solenoid valve The reset time may be long or cause vibrat...

Page 4: ... valve knob Significant accumulation indicates a possible seat leakage d Conduct the water flow test as per the system testing procedure at least once a month iv PERIODIC CHECK Conduct the water flow test by actuating few of the release devices provided in the system Clean all strainer s and line restriction nipple This test is to be carried out at least once in three months ABNORMAL CONDITION i A...

Page 5: ...MARCH 2022 HD 235 PAGE 5 OF 16 HD FIRE PROTECT PVT LTD DELUGE VALVE MODEL H3 SIZE 200 150 100 80 50 NB 2 4 5 6 7 8 9 10 12 13 14 15 16 17 19 11 18 20 21 3 1 Groove x Groove Flange x Flange ...

Page 6: ...1 STAINLESS STEEL 4 9151 9112 9112 BOLT 8 4 4 STAINLESS STEEL 5 3546 3545 3544 3543 3543 RUBBER CLAMP 1 1 1 1 DUCTILE IRON 6 117466 117465 117464 117463 117463 RUBBER SEAT 1 1 1 1 EPDM 7 4034 3990 4011 4041 4041 CLAPPER 1 1 1 1 DUCTILE IRON 8 117462 117461 117460 117459 117459 DIAPHRAGM 1 1 1 1 EPDM 9 3542 3541 3540 3539 3539 CLAMP RING 1 1 1 1 DUCTILE IRON 10 8806 9151 9151 9151 9151 BOLT 12 8 8 ...

Page 7: ...E GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL FLANGE X FLANGE GROOVE X GROOVE FLANGE X FLANGE GROOVE X GROOVE PG M OD INLET OUTLET OD DV PS2 PG DPA RN LINE TO DETECTION OD AIR SUPPLY PS1 PG NRV SV PG M OD INLET OUTLET OD DV PS2...

Page 8: ...NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL PG M OD INLET OUTLET OD DV G OD TO DETECTION LINE PG NRV PS2 SV PG M OD INLET OUTLET OD DV G OD TO DETECTION LINE PG NRV PS2 SV PG M OD ...

Page 9: ...SE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE OPTIONAL PG M OD INLET PG OUTLET OD DV DR V OD OD OD TO DETECTION LINE PS2 SV PG M OD INLET PG OUTLET OD DV DR V OD OD OD TO DETECTION LINE P...

Page 10: ...D NRV TO DETECTION LINE PS2 SV PG M OD INLET PG OUTLET OD DV SV G OD PS2 PG DR V DPA RN LINE TO DETECTION OD OD OD OD AIR SUPPLY NRV PS1 NRV PG M OD INLET PG OUTLET OD DV G OD PG DR V DPA RN LINE TO DETECTION OD OD OD OD AIR SUPPLY NRV NRV SV PS2 PS1 ABBREVIATION SYMBOLS DV DELUGE VALVE G SPRINKLER ALARM WMG NRV WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RES...

Page 11: ... WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL INLET PG OUTLET PG OD M OD DV TO DETECTION LINE SV PS2 INLET PG OUTLET PG OD M OD DV TO DETECTION LINE SV PS2 INLE...

Page 12: ...EX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL INLET PG OUTLET PG OD M OD DV G OD TO DETECTION LINE NRV SV PS2 INLET PG OUTLET PG OD M OD DV G OD TO DETECTION LINE NRV SV PS2 INLET...

Page 13: ... PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE OPTIONAL INLET PG OUTLET PG OD M OD DV OD OD DR V OD TO DETECTION LINE SV PS2 INLET PG OUTLET PG OD M OD DV OD OD DR V OD TO DETECTION LINE SV PS2 INLE...

Page 14: ...TO DETECTION LINE G OD NRV PS2 SV ABBREVIATION SYMBOLS DV DELUGE VALVE G SPRINKLER ALARM WMG NRV WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE...

Page 15: ...VALENT LENGTH BASED ON 1 2 SCHEDULE 40 PIPE WITH C 120 KG SQ CM METERS MAXIMUM PILOT LINE HEIGHT FT 60 20 20 40 120 80 100 140 5 10 15 20 25 30 35 40 40 2 4 6 8 10 12 160 180 200 14 16 18 45 50 55 60 50 100 150 200 250 0 220 65 25 FEET 250 FEET 500 FEET 60 20 20 40 120 80 100 140 5 10 15 20 25 30 35 40 40 2 4 6 8 10 12 160 180 200 14 16 18 45 50 55 60 50 100 150 200 250 0 220 65 25 FEET 250 FEET 5...

Page 16: ...including but not limited to any implied warranties or merchantability or fitness for a particular purpose All such other warranties and representations are hereby cancelled NOTICE The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherev...

Reviews: