USING THE FACT-1

CAUTION:

Steps 1 through 6 should he performed with the feeder "grounded".

1. Make sure test cable assembly is NOT connected to the FACT-1.

2. Plug the FACT-1into a 120V, 60Hz, 3-prong outlet. The outlet should be rated for

a minimum of 15 Amps. Press the Red POWER switch to turn on the unit. The
POWER switch should illuminate and the fan located in the cord cavity should start.

IMPORTANT:

The FACT-1 is not designed to work with any type of GFCI protection device.

In a situation where a ground is left connected to the feeder, the FACT-1 will output current
on the corresponding phase however, the return current will be on the neutral/sheath of
the feeder and/or earth ground. Therefore the GFCI device will detect the large differential
in current and open the circuit, prohibiting the unit from operating.

3. Perform a "Self-Test" of the unit prior to normal operation (see "Diagnostics"). 

IMPORTANT: 

The test cable assembly should NOT be connected to the FACT-1

during the Self-Test or the results may be incorrect and the test leads will become
energized with 120V.

4. Turn off the power to the unit by pressing the POWER switch again. The POWER switch

should no longer be illuminated and the fan will stop.

CAUTION:

Assure that the feeder cable being connected to the FACT-1 is not energized.

The Feeder Ammeter Clear Test Set is not designed to be used or connected in the presence
of voltages greater than 300V.

5. Connect the test cable assembly to the FACT-1. Connect the appropriate test leads to

the A, B and C phase of the cables under test. Connect the ground lead to the neutral.

6. Turn the power on to the unit by pressing the POWER button.

NOTE:

If for some reason the 3rd prong safety ground is not connected properly, a

message will be displayed on the LCD to repair the 3rd prong ground before operating.

CAUTION: 

The Feeder grounds need to be removed at this point. Assure there is no back

feed condition or voltage being applied to the feeder prior to the removal of the grounds.

IMPORTANT:

The FACT-1 has been designed to also operate in situations where the polarity

of the 120 VA C outlet is "reversed". When the polarity is reversed, the output post that
becomes "live" when the AMMETER CLEAR button is pressed is also reversed. This will
be indicated on the LCD so that the operator does not have to remember; he simply
rotates the selector knob until the phase he wishes to test is indicated on the display.
The table below describes the internal logic:

Summary of Contents for FACT-1

Page 1: ...uction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E W A U K E G A N I L L I N O I S 6 0 0 8 5 U S A PHONE 847 473 4980 FAX 847 473 4981 website www HDElectricCompany com FACT 1 FEEDER AMMETER CLEARTEST ...

Page 2: ... grills in the cord storage compartment Never attempt to close the cover while the unit is operating or while any cables are connected Do not connect the FACT 1 unit to a GFI protected circuit Before connecting the FACT to any circuit test and ground that circuit to verify it is both de energized and discharged DO NOT use the FACT 1 if any chance of a back feed exists The FACT 1 contains sensitive...

Page 3: ...by an internal 24 ohm power resistor In the primary phase to phase fault scenario the LCD ammeter display will also indicate a fault current of approximately 5 Amps with a nominal line voltage of 120V In the secondary side fault scenario a short circuit fault from a feeder transformer secondary conductor to ground occurs This allows more current to flow through the primary windings of this transfo...

Page 4: ...he Feeder All ClearTest Set the self test mode to assure proper operation The test cable assembly must be removed during the self test 5 POWER This button is the master power switch for the Feeder Ammeter ClearTest Set It is a latching pushbutton type Pressing this button powers up all the electronics and fan for operation 6 AMMETER CLEAR Pressing this button provides 120V AC to the selected bindi...

Page 5: ...itch again The POWER switch should no longer be illuminated and the fan will stop CAUTION Assure that the feeder cable being connected to the FACT 1 is not energized The Feeder Ammeter ClearTest Set is not designed to be used or connected in the presence of voltages greater than 300V 5 Connect the test cable assembly to the FACT 1 Connect the appropriate test leads to the A B and C phase of the ca...

Page 6: ...ge will be displayed A ALIVE NO FAULT DETECTED Depending on the number of transformers connected to the network feeder during the test some small current 0 3Amp could be detectable due to the excitation currents of the transformers If the FACT 1 detects maximum current flow in the live selected phase only a phase to ground fault exists and is displayed A ALIVE PHASE A TO GND FAULT If the FACT 1 de...

Page 7: ... the SELF TEST button momentarily to clear the notice NOTICE LINE CORD POLARITY IS REVERSED PRESS SELF TESTTO CONTINUE DIAGNOSTICS The FACT 1 has built in comprehensive diagnostics to assure that the FACT 1 is operating correctly The test cable assembly should NOT be connected to the FACT 1 during the Self Test The SelfTest mode is entered by pressing the SELF TEST button If at any time you wish t...

Page 8: ...ny determines is defective HD Electric will at its option either 1 repair or authorize the repair of the Productor 2 replacetheProduct subjecttothefollowing TheProductsaremadeusingpartssourcedfromavarietyofmanufacturers Duetotherapidly changing technology environment parts may become obsolete unavailable over time end of life In the event that a Product cannot be repaired or replaced due to unavai...

Reviews: