3

Maximum Boiler Temperature

“Maximum  Boiler  Temperature”  is  used  in  the 

outdoor reset design calculation, and also serves as 

the maximum setting for the boiler.  

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

Minimum Boiler Temperature

Reduces the risk of condensing flue gases. It can run 

with both condensing, and non-condensing boilers. 

Setup as per boiler manufacturers recommendation.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

Outdoor Design Temperature

The  “Outdoor  Design  Temperature”  option  should 

be set to reflect your specific city or region. It factors 

into the outdoor reset curve calculation.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

Differential

A differential of 10° is 5° above setpoint and 5° 

below setpoint.

 Range from 2°F to 60°F.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

Warm Weather Shutdown

“Warm  Weather  Shutdown”  is  the  outdoor 

temperature that must be reached for the control to 

enter an energy-saving hibernation mode.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

 

Domestic Hot Water Priority

This option will allow the DHW demand to override 

the heating system for a max of 60mins in order 

to satisfy the DHW demand. Once the control 

switches to DHW priority, the DHW target will be the 

Maximum  Boiler  Temperature.  If  after  the  60mins 

there is still an unsatisfied heat demand, the ORC-

0100 will automatically switch the system pump 

back on to accommodate the call for heat. Once 

the control switches to heat mode, the heat target 

will be calculated based on the actual outside 

temperature.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

Refer to diagram #4 Outdoor Reset Curve

Refer to diagram #4 Outdoor Reset Curve

Summary of Contents for ORC-0100

Page 1: ...HBX Control Systems Inc Installation Manual ORC 0100 Version 1 02 ORC 0100 ...

Page 2: ...ted in accordance with the codes and practices applicable to the jurisdiction for the actual installation SAFETY SYMBOLS AND WARNINGS Drawing Reference Refer to the specified electrical drawing at the back of the manual Precaution A measure taken in advance to prevent dangerous or an unpleasant event TABLE OF CONTENTS Introduction Index Safety Symbols and Warnings Index Receipt and Inspection 1 De...

Page 3: ...outside air temperature and re adjust the heating system water to a minimum water temperature to satisfy the heat loss of the home or building Some features of the ORC 0100 are Backlit graphic display Push button keypad control User friendly programming features Includes external sensor Integrated 2 Amp dry contacts Technical Data 3 x Contact Output 120VAC 2 Amp Max 2 x External Thermistor Input 1...

Page 4: ...row to the left of your chosen option will turn black when you have selected a specific step then the and buttons to adjust the value Special Features 1 System pump pre purge 30 seconds This will allow any residual heat to be taken out of the boiler before firing the boiler This feature is designed to reduce short cycling 2 System Pump Post Purge 60 seconds After the heat demand has been satisfied...

Page 5: ... from 2 F to 60 F BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 6 F 5 WWSD 72 F Warm Weather Shutdown Warm Weather Shutdown is the outdoor temperature that must be reached for the control to enter an energy saving hibernation mode BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 6 F 5 WWSD 72 F Domestic Hot Water Priority This op...

Page 6: ...ry 120VAC 2A max rating Larger loads must use an external relay L N 120 V AC Jumper Wire Pump Enable Pump enable has a 30 second pre purge and 60 second post purge Boiler Enable Outdoor Sensor Boiler Sensor THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 ORC 0100 ...

Page 7: ...hermostat Transformer ORC 0100 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 L N 120 V AC A 8 4 1 5 9 12 14 13 DHW PUMP BOILER PUMP TH AquaStat C R 2 Domestic Hot Water ...

Page 8: ...ating Larger loads must use an external relay THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 L N 120 V AC Pump Enable Pump enable has a 30 second pre purge and 60 second post purge Boiler Enable Outdoor Sensor Boiler Sensor ORC 0100 ...

Page 9: ...l reach this temperature when the outdoor temperature is equal to or lower than the design outdoor temperature 105 F HD ON BOILER OUTDOOR 38 F TARGET 160 F BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 6 F 5 WWSD 72 F BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 6 F 5 WWSD 72 F ...

Page 10: ...________________ _________________________________________________________________________________________________ _________________________________________________________________________________________________ _________________________________________________________________________________________________ _________________________________________________________________________________________...

Page 11: ...on repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise including warranties of merchantability and fitness for a particular purpose application HBX neither assumes nor authorizes any other person to assume for it any other liability in connection with the sale...

Page 12: ... HBX Control Systems Inc 2017 HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2 Toll Free Technical Support 1 855 554 6629 V1 021 ...

Reviews: