HBX CPU-0500 Quick Start Up Manual Download Page 2

Outlined fields indicate a mandatory set up.

Design Boiler Temperature

This is the design boiler temperature. It is 

used in the outdoor reset design calculation 

and is also the maximum setting for the 

boiler.

(50°F to 200°F) Default: 190°F

Design Room Temperature

This is the design room temperature. It is 

used in the outdoor reset design 

calculation. Set it to the approximate 

desired room temperature.

(50°F to 120°F) Default: 70°F

Design Outdoor Temperature

This is the design outdoor temperature. It is 

used in the outdoor reset design 

calculation. Set the maximum temperature 

you would like the control to be at.

(-50°F to 150°F) Default: -10°F

Minimum Boiler Temperature

This is the minimum boiler temperature. This 

setting will vary depending on the type of 

boiler you are running. This is boiler supply 

temperature so keep that in mind when 

selecting this feature.

If the minimum boiler temperature is set to 

OFF then the boiler demand will always be 

ON when a heat demand is present.

(OFF / 51°F to 200°F) Default: OFF

Warm Weather Shut Down (WWSD)

This setting is used to set the temperature at 

which the CPU-0500 will go into WWSD. 

Above this temperature the system will be 

shut off.

(20°F to 150°F) Default: 75°F

DHW Target

This setting is used to set the desired DHW 

tank temperature.

(OFF/1°F to 200°F) Default: 130 °F 

DHW Differential

This is the differential for the DHW tank. Set 

this setting to the desired differential for the 

DHW tank.

(2°F to 60°F) Default: 6°F

Eg.) 6°F differential would be 3°F 

above and 3°F below.

DHW Boiler Setpoint

This setting is used to set the desired boiler 

setpoint when there is a DHW demand. This 

can be triggered from either a thermistor or 

an aquastat.

(50°F to 200°F) Default: 180°F

When stage 2 is selected this can 

only be triggered by an aquastat.

DHW Priority

This setting is used to set the DHW priority. If 

set to ON then the System Pump will shut off 

when there is a DHW call. The priority time is 

60 minutes. In Mixing mode the injection 

device will shut off in a priority situation.

(ON/OFF) Default: OFF

Heat Demand

1) ON: This setting indicates that the 

CPU-0500 is in a permanent heat demand. 

Use instead of attaching a thermostat.

2) OFF

(ON/OFF) Default: OFF

Celsius & Fahrenheit

Use this setting to change the display format 

from °C to °F.

(°C/°F) Default: °F

Boiler Selection

This setting is used to select what boiler(s) 

are connected to the control.

Selection Types:

1: Single Stage ON/OFF Boiler

2RT: 2 Stages of ON/OFF Boiler with Rotation

2: 2 Stage Boiler with No Rotation

MOD: Modulating Boiler

Default:1

Minimum Modulation Percentage

This setting is used to set the lowest 

modulation level the boiler can go down to.

(10% to 60%) Default: 20%

Modulating Step Time & Staging 

Lag Time

When the boiler is set to MOD mode this 

setting sets the time between the steps 

when the boiler needs to increase or 

decrease the firing rate.

(1s to 300s) Default: 10s

Boiler Pump Selection

1) ON: This setting is used to setup the boiler 

pump contact. If this setting is on, then the 

boiler pump contact will come on only if the 

boiler is being enabled. This setting also 

works for modulating boilers.

2) OFF: If this setting is off the boiler pump 

contact will come on with the demand.                     

    Default: OFF

The setting can be used as a boiler 

enable signal for modulating boilers.