Commissioning
The DA2510 has been preset at the factory so that the P2V can be directly
operated. The internal S1 - S4 jumpers will not be changed.
•
Jumper S2 remains removed (factory setting) for 24 V transducer excitation
•
Jumper S2 remains removed (factory setting) for key release
•
Jumper S3 remains inserted (factory setting) for maximum value display
•
Jumper S4 remains removed (factory setting) for calibration
4.1 Setting up the measurement device
1. Select input signal:
- Key
MENU
”inP” flashes
•
Press the
TARE
key until the required display appears: ”0-10” (for P2VA1
with voltage output)
•
Press the
MENU
key, ”Stor” appears briefly
2. Select decimal point position:
•
Press the
MENU
key, until ”dEc.P” appears briefly
•
Press the
TARE
key until the required position is reached:
”FFF.F” for 200 bar and 500 bar
”FFFF” for 1000 bar to 5000 bar
•
Press the
MENU
key, ”Stor” appears briefly