HB-THERM M8098 Assembly Instructions Manual Download Page 2

 

 

 

Assembly Instructions M8098-EN 

 

M8098-EN   2018-03 

 

2/6

 

 

  

 

1.

 

Proceed as follows in order to cool down the unit and empty 
the mould (mould evacuation) 

  Display menu page 

Functions

  Select the function 

Cooling

 and activate with the 

 key. 

  Select the function 

Mould evacuation

 and activate with the 

 

key. 

 The activated function is indicated with the 

 symbol. 

 

 

2.

 

Main switch off, remove the plug from the mains and empty 
the unit. 

 

 

3.

 

Remove control cable to ext. flow rate meter Flow-5. 

 

4.

 

Detach the hexagon screw and remove ext. flow rate meter 
Flow-5. 

  

 

 

Fig. 1: Front side of the evaluation unit 

 

Fig. 2: Rear side of the evaluation unit 

 

5. 

Proceed as follows in order to remove the cover of the 
evaluation unit: 

 

Remove screws (Label 1 

 Fig. 1). 

 

Detach screws (Label 2 

 Fig. 2). 

 

Lift the cover with the keyboard and pull out the ribbon cable. 

 

Remove the cover with the keyboard. 

 

   

 

1

2

Summary of Contents for M8098

Page 1: ...outconversion work on the unit Procedure DANGER Danger to life caused by electric current Touching conductive parts causes a direct danger to life Therefore For all work on the electrical system for maintenance cleaning or repair work disconnect from the mains or disconnect all phases of the external power supply and secure them against being switched on again Check unit is isolated from power sup...

Page 2: ...cated with the symbol 2 Main switch off remove the plug from the mains and empty the unit 3 Remove control cable to ext flow rate meter Flow 5 4 Detach the hexagon screw and remove ext flow rate meter Flow 5 Fig 1 Front side of the evaluation unit Fig 2 Rear side of the evaluation unit 5 Proceed as follows in order to remove the cover of the evaluation unit Remove screws Label 1 Fig 1 Detach screw...

Page 3: ...placement temperature sensor return line BT 2 x Disassemble screws Label 6 Fig 4 and remove cover 7 Replace temperature sensor main line BT 1 or return line BT 2 x while proceeding as follows Fig 5 Flow 5 side view from the right Disconnect temperature sensor BT 1 BT 2 x at the flow rate measuring board DFM 51 A 9 x Disassemble temperature sensor BT 1 BT 2 x Fig 5 Transfer label of temperature sen...

Page 4: ...er to attach the covers Fig 8 Flow 5 with ball valve Fig 9 Flow 5 view from below Attach insulation and cover plate mount screws Label 5 Fig 8 Attach insulation and cover plate mount screws Label 4 Fig 8 If present install shut off valve OUT 1 and 4 Label 3 Fig 8 Only in the event of a replacement temperature sensor return line BT 2 x Attach cover plate and mount screws Label 6 Fig 9 10 Connect co...

Page 5: ... sensor return line ext Proceed as follows in order to calibrate 1 8 if necessary the temperature sensor With a constant deviation set parameter Sensor offset under Service Calibration Temperature With a linear deviation set parameter Sensor asc cor under Service Calibration Temperature Fig 11 Sensor calibration during modular operation Operation Modular 16 Proceed as follows if necessary calibrat...

Page 6: ... EN M8098 EN 2018 03 6 6 Parts list Pos Description O ID Pcs 01 Heat sensor Pt 1000 0 53 m T24888 1 02 Assembly instructions German M8099 DE 1 03 Assembly instructions English M8099 EN 1 04 Assembly instructions French M8099 FR 1 ...

Reviews: