HB Products HBOC/C Quick Manual Download Page 2

HBOC/C and HBOR/C quick guide 001 EN 

December 2021 

 

 

 
LED indication: 

1)

 

3 x green LEDs indicate oil level 

2)

 

Green Power LED constant light indicate sensor is standby 

 not controlling 

Green Power LED flashes when the sensor is in control operation.  

3)

 

Yellow LED indicates supply is open to magnetic valve 

4)

 

Red LED indicates ALARM  

 

LED 
signal 

ON/OFF/Frequency 

Functionality 

Green 
(3x) 

ON 

Oil detected 

Flash 

Turbulence in the compressor housing  

OFF 

Oil is not detected 

Green 
POWER 

ON 

Standby power connected 

Flash 

In operation or when the sensor is 
connected to HB Tool. (Red and yellow LED 
also flashes) 

OFF 

No supply   

Yellow  

ON 

Activation/supply to the magnetic valve 

OFF 

Magnetic valve is not being supplied 

Red 

ON 

Alarm. Activated automatically according to 
a calculated time span if oil has not been 
detected (oil cycle x alarm counter = Time 
before alarm goes off). Output relay (pin 3 & 
4) is activated. 

OFF 

Oil level reached in accordance with the 
calculated time span / number of oil cycles. 

 

Flash 

Sensor is faulty 

 

Calibration: 

HBOR

 is pre-calibrated upon delivery and ready for use in ammonia systems only. If the sensor is used in 

other systems/applications, please contact HB products 
 

HBOC

 is pre-calibrated upon delivery and ready for use in refrigeration systems using conventional mineral 

and PAO oils. If the 

HBOC

 is used in other oil types a calibration might be needed. This calibration is done 

by using the HB tool connected via an USB cable.  
 
Calibration instructions:  
 
Both a calibration in gas an oil must be done: 
 
A zero calibration is performed when the switch is in gas. The calibration is done by clicking on the zero-
calibration button in the tool.  
 
A span/max calibration is done when the switch is covered with oil. The calibration is done by clicking on 
the span-calibration button in the tool. 

 

 

 
 
 
 
 

Fault Detection 

 

Fault 

Reason 

Correction of fault 

No LED is on. 

No supply to the sensor or 
defective cable/plug 

Check and find 
faults in the power 
supply. Change the 
supply cable. 

Sensor does not 
trigger even 
though there is oil.   

Quality/type of oil is different from 
that used during factory 
calibration. 

Recalibrate the 
sensor. 

Red alarm 

Oil level has not been attained 
during the specified number of oil 
cycles.  

Check system oil 
return. Check oil 
filter and magnetic 
valve if necessary.   

3 x green flash                                                                                                                                                                         

There is oil turbulence in the 
compressor housing. 

Change "filter 
func/time cons" to 
a higher value. 

No output (3 x 
green LED are on, 
but the output 
signal is not active)  

Check the setup of the 
parameters/which contact 
function has been selected, NC or 
NO (Normally closed/Normally 
open) 

Change the setup 
using the tool.  

Delay in sensor 
activation 

May be caused by gas and foam 
bubbles in the system.  

Check if the sensor 
is placed optimally. 

No detection 

Fault in the electronics 

Send the sensor to 
be repaired. 

Red LED flash 

Sensor is faulty 

Contact supplier 

 

 
 

More information 

For further information please download the full instruction manual from our homepage: 

www.hbproducts.dk

You find it under downloads and then instruction manuals 

 
 
 
 
 
 