HB Products HBOC/C Quick Manual Download Page 1

HBOC/C and HBOR/C quick guide 001 EN 

December 2021 

 
 

Electrical connections 

 
HBOC/C and HBOR/C can supply a magnetic valve, or it can be connected to the central control via the 
sensor's control/alarm output. See the diagrams below for the two 
 
  
HBOC/C and HBOR/C - 

mk1

 

 (DC version 

 DC supply and DC output on cable) 

 

DC version 

 
 
 
 
 
 

 
 
 

 

 
 
HBOC/C and HBOR/C 

 

mk2

 

 (

AC version 

 AC/DC supply and AC/DC output on cable) 

 

AC version 

 

 
 
 
 
 
 

 
 
 

 
 
 

 
 
 
 
The sensor controls the valve independent of other parts of the system. The function starts to work when 
the supply is connected. The control function can be activated/deactivated via an external run signal with 
"Run in" (pin 5) or work continuously  

 
 

 

 
 
 
 
Quick guide for OIL MANAGEMENT SWITCHES 
 
Covers HBOC and HBOR both mk1 and mk2 versions.  
 

Setup information is available in the manual which is available under download on www.hbproduct.dk 

 

 

 

Introduction 

 

The sensors are designed for control of oil levels in 
gas 

HBOC

 and in Liquid ammonia 

HBOR

  

HBOR

 will also be useable for measuring water in 

oil. 
Both sensors can control a level based on a single 
switch. These sensors replace the common 
mechanical float and the two-switch solution 
where a minimum and maximum level switch is 
used for controlling the level. 
  
The difference between mk1 and mk2 is the 
output on the cable.  
 

 

HBOC/C and HBOR/C has 24 

VDC

 max 24 W output on the cable 

 

HBOC/C mk2 and HBOR/C mk2 has 24 V 

AC/DC

 max 24 W output on the cable 

 
Mk2 version are labeled mk2. Mk1 versions are not labeled mk1   

 
Installation  
 

The sensor is mounted either on a compressor or an oil separator. On a compressor, an adapter flange can 
be provided as an accessory. The sensor is sealed with Teflon tape or liquid gasket before installation. 
Dependent upon the thread type, the gasket consists of: 
 

 

NPT thread = Teflon tape or liquid gasket 

 

BSPP & UNEF = Aluminum washer/gasket 

 

Solenoid valve 
24 VDC or 24VAC 
Brown + 
White 

 

Grey not used 

1 Brown +24 VDC  
2 White   - common  
3 Blue      Alarm Output pot. free 1A 
4 Black    Alarm Output pot. free 1A 
5 Grey     DI Run-in signal 5-24 V DC 

Solenoid valve 
24 VDC 1A 
Brown + 
White 

 

Grey not used 

1 Brown +24 VDC or 24 V AC 
2 White   - common or 24 V AC 
3 Blue      not used 
4 Black   Digital out 24VDC 30 mA 
5 Grey    DI Run-in signal 5-24 V 
DC 