HB Products HBDF-MK2 Installation And Calibration Manual Download Page 2

 

HBDF mk2 instruction manual 15 EN 

                  June - 2021                WWW.HBPRODUCTS.DK 

2 / 12

 

 

Table of Contents 

Intoduction ............................................................................................................. 1 
Table of Contents ................................................................................................... 1 
Safety Instructions .................................................................................................. 2 
Installation .............................................................................................................. 3 
Wiring the sensor .................................................................................................... 5 
Sensor configuration ............................................................................................... 6 
Operating modes ..................................................................................................... 6 
Sensor setup ............................................................................................................ 7 
Calibration of sensor ............................................................................................. 11 
Technical data ....................................................................................................... 12 
Sensor Repair ....................................................................................................... 12 
Spare Parts ............................................................................................................ 12 

 
Safety Instructions 

 
CAUTION! Always read the operational guidelines before commencing work!  Read all warnings Installation of HBDF 
requires technical knowledge of both refrigeration and electronics. Only qualified personnel should work with the 
product. The technician must be aware of the consequences of an improperly installed sensor and must be committed to 
adhering to the applicable local legislation.   
 
If changes are made to type-approved equipment, this type of approval becomes void. The product's input and output, as 
well as its accessories, may only be connected as shown in this guide. HB Products assumes no responsibility for 
damages resulting from not adhering to the above.  
 
Explanation of the symbol for safety instructions. In this guide, the symbol below is used to point out important safety 
instructions for the user. It will always be found in places in the chapters where the information is relevant. The safety 
instructions and the warnings must always be read and adhered to.  
 

 

CAUTION! Refers to a possible limitation of functionality or risk in usage. 
NOTE!  Contains important additional information about the product and provides further tips.   
The person responsible for operation must commit to adhering to all the legislative requirements, 
preventing accidents, and doing everything to avoid damage to people and materials. 

 
Intended use, terms of use. The HBDF defrosting sensor is designed for measuring ice formation on evaporators. If the 
HBDF is to be used in a different way and if the operation of the product in this function is determined to be 
problematic, prior approval must be obtained from HB Products. 
 
Defrosting with hot gas must be performed in a safe way to ensure that there is no risk for liquid hammering and 
leakage of refrigerant.  
Preventing collateral damage: Make sure that qualified personnel assess any faults and take necessary precautions 
before attempting to make replacements or repairs, to avoid collateral damage. Disposal instructions: HBDF is 
constructed so that the modules can easily be removed and sorted for disposal. 
 
 
 
 
 

 

Summary of Contents for HBDF-MK2

Page 1: ...outputs Simple analog Provide a simple analog signal 4 20 mA linear to the ice thickness for a PLC Smart analog Provide an analog signal when the specified ice thickness is reached and when defrost ca...

Page 2: ...point out important safety instructions for the user It will always be found in places in the chapters where the information is relevant The safety instructions and the warnings must always be read an...

Page 3: ...The wire must be between the fins where ice will built up It can be on the inlet side on the outlet side or in the middle of the evaporator If you have the overview of where ice is building up you do...

Page 4: ...d from the evaporator Use the terminal connector delivered together with the wire HBDF snap on Clip can be used for securing the wire but passing behind the pipes provide a better and more secure fast...

Page 5: ...formed and place both wires and temperature sensor there Sensor wire is passed in out through the evaporator from the inlet side to the outlet side as shown The second picture show ice on the air outl...

Page 6: ...2 plug for communication and setup The sensor needs power connection to be setup and to have the correct function of the relays Wiring the HBDF Mk2 When the wire ground cable and temperature sensor is...

Page 7: ...HBDF mk2 instruction manual 15 EN June 2021 WWW HBPRODUCTS DK 7 12 Simple defrost with electric heater...

Page 8: ...that indicates you have changed something and need to store the data in the sensor The sensor has three different operation modes The sensor mode is selected in the basic settings Simple analog In th...

Page 9: ...for a period defined by a parameter When the time has passed the evaporator should be dry and free from ice ready for a new cycle Parameters used for controlling the output Filter time constant avera...

Page 10: ...period sensor delay time This Relay2 can be used for initiating the fan to blow the water out of the evaporator or to prevent the fan from blowing the water out During the defrost time and sensor dela...

Page 11: ...on in the box Press the green button until the red LED turn off Press the green button once and the calibration is done Using the HB tool Connect power supply to the box Connect the HB tool to the box...

Page 12: ...nd of the wire is outside the evaporator and use the terminal connector If that doesn t solve the problem the wire has to be replaced No analog output or Relay contact activation There may be bad grou...