HB Products HBCP Quick Manual Download Page 2

 

 

 

HB Products A/S – 

www.hbproducts.dk

 – 

[email protected]

 – tel.: +4587476200 

 

                                 Quick guide – HBCP – rev. 001-2013 

Mechanical installation 

 

Electrical installation 

Configuration of sensor 

 

 

 

Sensor is factory programmed for compressor protection. In order to change the 
control parameters the HB configuration tool is needed.

 

 
Mechanical specifications: 

Ambient temperature: -40…+60°C 
Liquid temperature: -50…+70°C 
Max. pressure: 100 bar 
Material, mechanical: AISI304/PTFE 
Thread connection: see packaging. 
Refrigerant: NH3 & CO2 
 

 
Electrical specifications: 

Supply: 24 V AC/DC 
Power consumption: 0,5 W 
Alarm output: Transistor PNP, max 1A 
Contact function: NC/NO 
Alarms: Low & High 
Cable: M12-5 m 
Plug: DIN 0627 – M12/5 pins 
Enclosure: IP65 
Material, electronics: Nylon 6 (PA). 

 
Download of software: 

The tool can be downloaded for free. Request access to download the tool by 
sending an email to 

[email protected]

 
NOTE! To be able to change the control parameters, it is necessary to have a special 
USB/M12 configuration cable as well as the configuration tool installed on a PC. 

Installation guide:  

HBCP can be mounted on a pipe bending. It should be 
placed close to the compressor. 

 

 

LED activation: 

1) Green LED indicates 24 V supply; it blinks during operation.  
2) Yellow LED indicates liquid hammering (low alarm).  
3) Red LED indicates liquid hammering (high alarm). 

Caution

! In case of welding work on the unit, the electronic 

part must be removed. Welding work can damage the 
electronics. The mechanical part of the sensor must 

not

 be 

installed in the pipe socket during welding. 

Note

! All terminals are protected against improper termination 

with a supply voltage up to 40 V. If the supply voltage is greater 
than 40 V the electronics will be damaged.   

Caution! 

Factory settings do not guarantee safe operation, since the configuration 

parameters depend on the system design.

 

Note

! Fault detection on the electronic function can be carried out without releasing 

pressure from the system or disassembling the mechanical part of the sensor. 

 

0-2 mm 

gab 