Indoor Installation:

The following installation and service clearances

must be maintained from the heater to combustible

materials. See Figure 22.

*For installations in which the vent terminates

in a wall directly behind the heater, allow 23”

between the rear of the heater and the outside of

the wall. See Figure 23.

Connecting Special Gas Vent to the

Heater:

Attach the Special Gas Vent to the Vent Adapter

using the adhesive specified by the vent manufactur-

er. Do not drill holes or use screws to connect Vent to

Vent Adapter.

1. Apply a bead of adhesive, about 

1

8

” in diameter, 

completely around the male end of the vent section,

between 

1

4

” to 

3

8

” from the end of the section.

2. Fully insert the male section into the female fitting

of the Vent Adapter.

3. Secure vent section Vent Adapter by sliding the 

ring of the vent section over the tabs of the Vent 

Adapter and bending the tabs over the ring. See 

Figure 24.

11

Horizontal or Vertical Venting—Positive

Pressure:

The heater can be vented either horizontally or

vertically with positive pressure vent system if one of

the  Special Gas Vent Systems listed in Figure 17 is

used. Do not use a draft hood with this heater. The

vent system must be installed in accordance with the

National Gas Code ANSI Z223.1 or the CAN/CGA

B149 Installation Codes, Local Codes and the Vent

Manufacturer’s Instructions.

See Figure 17 for permissible vent diameters for

these heaters.

See Figure 18 for maximum permissible vent

lengths.

The Vent System must terminate with a Vent

Terminal approved for this Pool Heater. See figure 19

for a list of approved vent terminals.

A Special Gas Vent Adapter Kit must be installed

on heater before connecting the Special Gas Vent to

the Heater.

Special Gas Vent Adapter Kit

Installation:

A Special Gas Vent Adapter collar must be installed

to the heater exhaust outlet, and a drain plug and out-

let cover must be installed. These components are

contained in the Special Gas Vent Adapter Kit.

The installation of the kit is done as follows:
1.

Remove the 4 screws that fasten the vent 

cover to the internal vent assembly. Discard 

the vent cover. Install the vent adapter and

gasket over exhaust using 4 screws 

previously removed. See Figure 20.

2.

Install plug into drain outlet at rear of heater. 

Install drain outlet cover over the drain outlet 

using 2 screws. See Figure 21.

10

Special Gas Vent Adapter Installation 

Figure 20

Drain Outlet Cover Installation 

Figure 21

Clearance for Vent Termination in Wall

Directly Behind Heater

Figure 23

Attaching Vent to Vent Adapter

Figure 24

Indoor Installation

Figure 22  

Top - 36”
Front - Unobstructed
Back - 6”
Right side (Water side) - 12”
Left side - 6”
For use on combustible floors.
Do not install in a closet.

Summary of Contents for H250IDL2

Page 1: ...and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causi...

Page 2: ...ement see warranty certificate included in this manual CAUTION If the pool spa heater is damaged or destroyed by improper maintenance excessive water hardness incorrect water chemistry or freezing it...

Page 3: ...screws from left and right side access panels Remove panels 4 Remove the front panel 5 Disconnect high limit wires and reroute them to opposite side of heater Disconnect the thermistor leads from cont...

Page 4: ...test edition of the National Fuel Gas Code ANSI Z223 1 7 12 Lift out heat exchanger and rotate it 180 degrees horizontally DO NOT FLIP IT OVER This End Up sticker should be pointing up 13 Reinstall fr...

Page 5: ...upon the model of heater See section titled Indoor Installation and Venting for indoor installation and venting guidelines 8 Vent Collar Diameters Model Diameter H250IDL H350IDL H400IDL 6 inches 8 inc...

Page 6: ...23 1 or the CAN CGA B149 Installation Codes Local Codes and the Vent Manufacturer s Instructions See Figure 17 for permissible vent diameters for these heaters See Figure 18 for maximum permissible ve...

Page 7: ...ve the capacity to supply enough gas to the pool heater and any other gas appliances if they are on the same pipeline Example 225 meter 225 000 BTUH If doubt exists as to the meter size consult local...

Page 8: ...heater usage for very large pools with and without an external by pass balancing valve NOTE Improperly adjusted by pass valves may result in damage to the heater this damage is not covered under warr...

Page 9: ...is installed more than three 3 feet above the surface of pool spa water install a loop as shown on Figure 32 to prevent drainage of water in heater during filter change For installation below pool sp...

Page 10: ...internal thermostat to regulate the water temperature to the set point of the mode selected Bypass Operation Note the following information when setting up the IDL2 for Bypass Operation control via a...

Page 11: ...tem is filled with water and purged of all air prior to starting heater Gas line testing The appliance and its gas connection must be leak tested before placing the appliance in operation The heater a...

Page 12: ...directly into the skimmer High chemical concentra tions may result when the pump is not running High chemical concentrations will cause very rapid corro sion of the heat exchanger Such damage is not c...

Page 13: ...ress the MODE key to put the heater in the POOL or SPA mode The POOL LED will illuminate to indicate that the control is in the POOL mode and the water temperature is to be controlled to the pool setp...

Page 14: ...1 The control de energizes the gas valve after the 4 second ignition trial ends 2 The control operates the blower during a 30 second post purge period 3 The control monitors for open contacts at the b...

Page 15: ...ners are not blocked the valves in the piping are properly positioned and the time clocks are prop erly set WARNING Do not attempt to repair any compo nents of heater Do not modify heater in any manne...

Page 16: ...To remove fuse board 1 Disconnect all wires from fuse board 2 Detach from sheetmetal panel Reverse the above procedures for installation Vent Pressure switch The vent pressure switch will not allow th...

Page 17: ...urn water temperature To replace thermistor 1 Turn pump gas supply and heater power off 2 Drain heat exchanger of all water 3 Remove side access panels 4 Disconnect thermistor leads from circuit board...

Page 18: ...erse the above procedures Combustion blower The combustion blower provides the air that mixes with the gas from the main burners for the combus tion process On initial start up the blower operates for...

Page 19: ...ard This cable is not polarized and can be inserted upside down if it was removed when electrical was done Invert the cable on the connector pin and see if the display is now on The display may read C...

Page 20: ...IDL Heater Diagnostic Guide IDL Heater Diagnostic Guide Code Fault Diagnosis Step Remedy 1 Check for faulty wiring or connection Inspect vent pressure switch wiring Ensure wire harness terminals are...

Page 21: ...NER ORIFICE PROPANE H3501DPL2 14 HAXMAN1250 GAS MANIFOLD H250 14 HAXMAN1400 GAS MANIFOLD H350 400 15 IDXL2ICB1931 IGNITION BOARD ONLY 16A IDXL2PBA1250 PANEL BEZEL KEYPAD ASY H250IDL2 16A IDXL2PBA1400...

Page 22: ...ortation charges paid by the user Any replacement pool heater furnished under this warranty shall remain in warranty only for the unex pired portion of this warranty CONDITIONS AND EXCEPTIONS This war...

Page 23: ...l Products Inc 2875 Pomona Boulevard Pomona CA 91768 Hayward Pool Products Inc 2880 Plymouth Drive Oakville Ontario L6H 5R4 Hayward S A Zoming de Jumet B6040 Jumet Belgium 2004 Hayward Printed in U S...

Reviews: