Haws SP158B Installation, Operation And Maintenance Instructions Download Page 2

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

 

 

3/14 

      Model SP158B 

Page 2 of 5 

 

Valve Specifications: 

 

1)  The Haws Freeze Protection Valve monitors water temperature. When water temperature cools down 

to 36

F or below, the thermostat connects inlet to drain and valve starts bleeding. When water 

temperature rises to 42

F or above, valve will close completely.  

 

2).  The Freeze Protection Valve has 1/2 NPT (F) inlet, 1/2 NPT (F) outlet (in-line installation only), 1/2” 

NPT (F) drain connections. 

 

Do not install the valve

 

in-line for drench showers!

 It does not have the capacity to provide the 

necessary flow. 
 
3).  Minimum/Maximum operating pressure:  20 PSI/125 PSI. 
 

Minimum / Maximum ambient temperature:  0°F /130°F. 

 

Maximum water temperature 165°F. 

 

Valve features: 

 

 

Fully automatic operation. 

 

In-line installation for eyewash only. 

 

Dead-Leg application: valve can be used for eyewash, shower, or combination units. 

 

Contamination resistant seat design for drip free closing. 

 

Paraffin thermostat for industry leading response time and reliability. 

 

Valve Installation: 

 

In-line installation for eyewash only. 

 

For dead-leg installation the outlet should be plugged. 

 

Flow Capacity to Drain, water temperature 36

F or below.   

 

Dynamic line pressure 

Flow Rate

 

5 PSI 

10 PSI

20 PSI

30 PSI

40 PSI

45 PSI 

60 PSI 

0.9 

GPM 

1.2 

GPM 

1.6 

GPM 

1.9 

GPM 

2.2 

GPM 

2.3 

GPM 

2.7 

GPM 

 

In-line installation Flow Capacity through Valve, water temperature 85

F. 

 

Pressure Drop Across Valve 

Flow Rate

 

5 PSI 

10 PSI

20 PSI

30 PSI

40 PSI

45 PSI 

60 PSI 

7.8 

GPM 

12.3 

GPM 

17.4 

GPM 

24.6 

GPM 

30.1 

GPM 

34.8 

GPM 

42.6 

GPM 

 

 

IMPORTANT 

 

To ensure proper operation of the valve, it is essential that: 
 

 

Haws Freeze Protection Valve must be located next to the eyewash for eyewash or combination 
units.  

 

Freeze Protection bleed valve must be located at the dead-leg of drain shower only. 

 

In-line application: use to feed eyewash only. 

 

Dead-Leg application: valve can be used for eyewash, shower, or combination units. 

 

Failure to comply with installation instructions could result in ineffective freeze 
protection, or dangerous flow restriction to showers.

 