Hawker P7/I.S. Operating And Installation Instructions Download Page 1

 
 

 

OPERATING AND INSTALLATION INSTRUCTIONS 

 
 
 

 

Conductivity Operated Level Control System 

Having SIRA Approved Intrinsically Safe Electrode Circuits 

Conforming to the ATEX Directive 94/9/EC 

 
 
 
 

Controller type P7/I.S. Certificate No SIRA03ATEX2160X 

 

Electrode Holders Certificate No SIRA03ATEX2159X 

 

Conductivity Operated Level Control System 

Certificate No Ex03E2161

 

 

 
 
 
 
 
 
 
 
 
 

 

Hawker Electronics Limited                                                            O&M 73 

57 The Avenue,                                                                                  Issue E 
Rubery Industrial Estate,                                                                    FEB 2010 
Birmingham B45 9AL. 
Tel: +44(0)121-453-8911  Fax: +44(0)121-453-3777 
www.hawker-electronics.co.uk 
e-mail: 

[email protected]

 

 
 
 

 

 

 

Summary of Contents for P7/I.S.

Page 1: ...troller type P7 I S Certificate No SIRA03ATEX2160X Electrode Holders Certificate No SIRA03ATEX2159X Conductivity Operated Level Control System Certificate No Ex03E2161 Hawker Electronics Limited O M 7...

Page 2: ...4 2 3 Basic controller testing 10 4 3 Technical specification 12 5 0 Electrode Holders 13 5 1 Cat 1 Electrode holders 13 5 1 1 Type identification 13 5 1 2 Certification markings 14 5 1 3 Conditions o...

Page 3: ...ected the unit either de energises or energises its internal relay dependent on the fail safe setting providing the user with a set of volt free S P C O contacts The unit may be used for High or Low a...

Page 4: ...acing ventilation or cooling should be provided Ambient operating temperature ranges other than 20 C to 40 C will be indicated on the product label The equipment is intended to be used only in dry cle...

Page 5: ...se to a spread of additional risks in the event of a power failure it must be possible to maintain them in a safe state of operation independently of the rest of the installation this is the responsib...

Page 6: ...uipment shall only be carried out by the manufacturer or in accordance with the applicable code of practice 6 The certification of this equipment relies on the following materials used in its construc...

Page 7: ...rnal relay contacts These relay contacts must not switch more than 5A r m s or 250V r m s or 100 VA 4 1 4 Electrical connection and housing The electrical connections are made to the terminal blocks s...

Page 8: ...IS technical specifications for ordering information Always check to ensure the controller specifications are suited to the supply and its application before installing The input supply fail safe set...

Page 9: ...ded that this manual be used for optimum performance No attempt should be made to remove this trim Precautions before testing Before disconnecting any mains leads or control wiring at the controller o...

Page 10: ...erating cycle to ensure correct operation 4 2 3 Basic controller testing If necessary the controller can be tested without connecting to the electrode holders so its correct basic function and the use...

Page 11: ...e supply to the volt free contacts has been switched OFF and remove the wires from the terminal block Use an approved ohmmeter to measure the contact resistance Check with the Relay de energised Led O...

Page 12: ...cial low range to approx 7K Ohm Switching response 1s Operating Temp 20 C to 40 C Cable Typically 70m See drawing 2920 for maximum permitted Levels for intrinsic safety Capacitance max before sensitiv...

Page 13: ...gases that may attack metals or solvents that may affect polymeric materials Suitable precautions e g regular checks as part of routine inspections or establishing from the material s data sheet that...

Page 14: ...Sira 03ATEX2159X may be used in zones 0 1 and 2 with flammable gases and vapours with apparatus groups IIA IIB IIC and with temperature classes T1 T2 T3 T4 T5 and T6 The ambient temperature operating...

Page 15: ...recommended distance is 23cm Using plastic coated electrodes which are available from stock can eliminate bridging always bare at least 50mm of the coating and have the reference G electrode central...

Page 16: ...alculating cable capacitance and inductance follow 6 1 Cable inductance Example of calculating cable inductance Method A As the L R Ratio remains constant regardless of cable length this is the easies...

Page 17: ...ch as the HPE8 when mounted 230mm apart may be up to 18m in length before this figure is exceeded Light duty electrodes such as the HPE7 mounted 75mm apart may be up to 15m in length which is far beyo...

Page 18: ...ed except that it must not be supplied from nor contain under normal or abnormal conditions a source of potential with respect to earth ground in excess of 250V a c r m s or 250V d c and ii Controller...

Page 19: ...roller G terminals Where a multiple controller system uses a Holder Type 1G 0 HPE5 IS as a common G holder the maximum number of P1 P2 holders that may be fitted is five 7 4 Permissible interconnectin...

Page 20: ...Page 20 of 22...

Page 21: ...K Notified Body Sira Certification Service 0518 Rake Lane Eccleston Chester CH4 9JN Conformity has been demonstrated with reference to the following documentation EC type examination certificate Sira...

Page 22: ...Page 22 of 22...

Page 23: ...l 41 41 541 5877 Fax 41 41 541 5878 Email General Information Sales info kesn ch Accounts Department accounts kesn ch USA O ce 233 Rogue River Highway 425 Grants Pass Oregon 97527 5429 USA Tel 1 503 2...