Hawker EverSys Evolution ATEX Instructions For Use Download Page 3

potentially cause a spark in a zoned area. Should there be any 

corrosion of the metal container, scrape this off and neutralise 

the area with a solution of water and baking soda, or diluted 

ammonia, and protect the part from further corrosion by 

painting it with acid proof paint 

(III) Monthly:

•  Carry out end of charge voltage readings at C

5

/100, measure 

and record:

•  the voltage of the battery

•  the voltages of each cell

If significant changes from earlier measurements or 

differences between the cells or bloc batteries are found, 

please contact EnerSys

®

 Service.

•  If the discharge time of the battery is not sufficient, check: 

•  That the work required is compatible with the battery 

capacity 

•  The settings of the charger

•  The settings of the discharge limiter.

(IV) Annually:

Check with attention:

•  the state of the plugs :be sure to have a good contact 

between the plugs without trace of overheating.

•  the state of the output cables. If you check the torque 

loading, you must use a torque wrench with respect of 

recommended value : 25+2 Nm

In accordance with EN 1175-1 at least once per year, the 

insulation resistance of the truck and the battery must be 

checked by an electrical specialist. The tests on the insulation 

resistance of the battery must be conducted in accordance 

with EN 1987 part1. The insulation resistance of the battery 

thus determined must not be below a value of 50 Ω per Volt of 

nominal voltage, in compliance with EN 62485-3. For batteries 

up to 120 V nominal voltage the minimum value is 1000 Ω.

 7. Discharge 

Ventilation openings must not be sealed or covered. 

Electrical connections (e.g. plugs) must only be connected 

or disconnected in the open circuit condition. To achieve 

the optimum life for the battery, operating discharges of 

more than 80 % of the rated capacity must be avoided (deep 

discharge). They reduce the battery service life. To measure 

the state of discharge use only the battery manufacturer’s 

recommended discharge indicators (imperative presence of a 

discharge limiter with an energy cut-off at 1.83 vpc operating 

voltage at 80% DOD C

5

, when the recharging time is 12 hours, 

and 1.87 vpc at 60 % DOD C

5

 when the recharging time is 8 

hours). Discharged batteries must be recharged and never be 

left in a discharged state for a long time.

Hawker

®

 Evolution ATEX certified batteries can be used in 

normal duty applications one cycle per day at a max. DOD 80% 

C

5

 and a maximum 6 days per week.

Avoid applications where:

•  no rest time is available allowing the battery to cool

•  battery duty leads to a high increase of temperature during 

operation.

It is recommended that the battery is discharged evenly and 

the use of tappings across a part of the battery is discouraged. 

To overcome this problem a D.C.- D.C. converter must be 

used to allow auxiliary loads to be supplied from the whole 

battery.  NOTE: The D.C.-D.C. converter must be certified for 

use in a zoned area as well as the auxiliary equipment. Battery 

performance is directly related to temperature. Batteries are 

rated at 30ºC. Where the battery temperature is lower than 

this, the available performance is reduced. Additional capacity 

is therefore required when the batteries are to be used in areas 

of low ambient temperatures (e.g. cold stores).

 8. Recharge 

NOTE: NEVER RECHARGE A Ex BATTERY IN A ZONED AREA. 

A full charge shall be carried out every working day with a 

Hawker charger.

The charging time for a 80 % discharged battery shall be 

12 hours, or 8 hours for a 60% discharged battery with the 

appropriately assigned Hawker high frequency charger. After 

any changing of cables on the charger, our technician must 

visit the site to check the charger.

Hawker Evolution ATEX certified batteries have a low gas 

emission. Nevertheless, when charging, proper provision shall 

be made for venting of the charging gases (EN 62485-3). 

Battery container lids and the covers of battery compartments 

shall be opened or removed. With the charger switched off 

connect the battery, ensuring that the polarity is correct. 

(Positive to positive, negative to negative). Now switch on the 

charger. 

If the charger was not purchased together with the battery it 

is best to have its suitability checked by the manufacturers 

service department. When charging, proper provision must be 

made for venting of the charging gases.

PzV batteries (Hawker Evolution ATEX certified batteries) are 

low gas emission, so some charging gasses are evolved.

Battery container lids and the covers of battery compartments 

must be opened or removed. 

During the charge the battery must be removed from the 

closed battery compartment on the truck. The ventilation must 

comply to EN 62485-3 standard. 

The length of the D.C. cable between the charger and battery 

affects the voltage drop back to the control unit of the charger. 

The cable should not be extended without prior consultation 

with the charger manufacturer and supplier of your Ex battery. 

In situations where the battery is generally only very lightly 

discharged, it may be an option to recharge the battery at 

less frequent intervals, perhaps every second day. In such 

circumstances please seek the advice or your local service 

engineer. 

Do not disconnect battery until the charger has been switched 

off. 

Your local area service centre must approve any managing 

charging system otherwise the warranty may be invalidated. 

Equalizing 

Equalising charges are used to optimise the life of the battery 

and to maintain its capacity. A unique equalisation charge is 

automatically carried out weekly 8 hours after the end of the 

charge with a Hawker HF charger. 

But remember never charge an Ex battery in a zoned area at 

any time.

 9. Temperature

The temperature range of use for the battery is b5°C 

and + 35 °C. Any use outside of this range shall be approved by 

a EnerSys service technician. Optimal battery life is obtained 

for a battery temperature of 25-30°C High temperatures reduce 

battery life according to IEC 1431 technical report, lower 

temperatures reduce the capacity available. 

The temperature on surface must never exceed 80°C in 

explosive area. If electrolyte temperature reaches 55°C during 

the charge, wait for the cooling before to use the battery in 

the explosive area. If a hot battery is detected it should be 

taken out of the controlled zoned area and allowed to cool to 

ambient temperature. An investigation should be carried out 

into why the battery is getting hot before it is placed back into 

service. 

Possible reasons why the battery might be getting hot is 

that there might be a fault in the equipment that the battery 

is powering or a fault could have occurred within the cells of 

the battery. In the case of a suspected battery problem contact 

your local service centre.

 10. Surrounding area conditions

The apparatus is designed to cope with the intended 

surrounding area conditions.

 11. Effect of explosive atmosphere on materials

The materials selected are not known to react with any 

explosive atmospheres to which the apparatus may be 

subjected

 12. Protection against other hazards

The apparatus does not cause injury or harm when used as 

specified in the installation and operation manual.

 13. Hazards arising from different ignition sources 

The apparatus does not produce ignition capable electrical 

sparks or arcs. The apparatus has also been designed not 

to produce potential ignition sources from electromagnetic, 

acoustic, optical or other such external energy sources.

 14. Withstanding attack by aggressive substances

The individual cells contains sulphuric acid: These cells and 

enclosure which make up the apparatus are constructed from 

materials that are resistant to acid attack see manufactures 

data sheet. 

Reviews: