Hawker EnerSys LifeSpeed IQ Safety And Use Instructions Download Page 2

DESCRIPTION  & USE

INTRODUCTION

The LifeSpeed IQ

TM

range of chargers is designed to recharge

24 V, 36 V, 48 V, 72V or 80 V batteries with 3-phase mains
supply. The micro processor-controlled unit automatically
recognises the battery (voltage, capacity, charge level, etc.)
and very effectively analyses its condition for optimum
handling. Several charging profiles are available (vented
lead/acid batteries, Hawker

®

XFC

TM 

batteries, gel batteries 

or Water Less

®

/Water Less

®

20 batteries) depending on the

configuration selected by the user. The capability for 
desulphation, equalisation and refresh charging is also
included.

EXTERNAL COMPONENTS

Presented below:

Ref.

Function

1.

Control Panel with LCD display

2.

USB port

3.

Navigation button

4.

Modules

5.

Input cable

6.

Connectors for options:
Ethernet, Electrovalve, Lifenetwork IQ

7.

Output cables 

8.

Output cables (dual harness only) 

9.

Ventilation panels

Figure 1: 

Principal components of the charger.

CONTROL PANEL

Incorporates LCD Display, USB port and navigation button. 

LCD Display

The display is fitted with 5 different colours indicating the
status of the charger: 

Navigation button

Functions of the keys

The keys offer the following general functions:

Key

Function

Navigation in the menu. 
Start/End of list (Press 2 seconds)   

The central button is equipped with 
a two-coloured LED Green/Red 
(Green: charger is waiting, Red charger 
operating)

GREEN/RED

Stop or Start of charge

Selection of active menu or validation 
of value stored

Cancel the value stored 
(Press 2 seconds) 

Start an equalisation charge.
Access to a sub-menu.

Access to the menus (press 3 seconds)
Close the window.

UNPACKING

The charger is delivered with the following:

2 m AC mains cable.

3 m DC battery cable.

This technical manual.

MECHANICAL INSTALLATION

The charger is intended to be floor standing and must be
installed in the vertical orientation. The distance between 
2 adjacent chargers should be at least 0.3 m. 

See paragraph 

Recommendations and avoid areas where

the chargers may be splashed with water, or saline 
environments.

ELECTRICAL CONNECTIONS

3-phase input

Connection to the mains supply is 400V AC 3-phase and
must be connected using a suitable plug and adequately
sized circuit breaker (not included). Current requirements in
Amps are indicated on the charger information plate.

Battery output

It is essential to ensure correct polarity. However, reversed
polarity will result in blowing the output fuse, inability to
charge and the fault code 

DF2

will be displayed. 

See Fault

Codes.

Connection to the battery should be done using the cables
supplied:

RED cable: battery POSITIVE.

BLACK cable: battery NEGATIVE.

FACTORY SETUP

The charger is delivered with a factory setup as follows:

Profile: As 

ordered

Output DC cable length: 

3 m

Configuration: As 

ordered

Automatic equalisation: 

No

Delayed start enabled:

No

FUNCTION

Waiting status until battery connected

Battery on charge

Alternating, on charge indicating a pump
defect, overdischarge, thermal fault or
module failure

Battery charged

Charger faults DF1, DF2, DF3, TH,
WRG MOD

Alternating, battery charged with pump
defect, overdischarge or module failure 

COLOUR

Dark blue

Light blue

Light blue  Orange

Green

Red

Green        Orange

1

2

3

5

4

6

7

8
9

Summary of Contents for EnerSys LifeSpeed IQ

Page 1: ... requirements must be observed Safety devices installed on the electrical supply to the chargers must be of the proper type and rating It is important to ensure that only fuses of the proper capacity should be used if they need to be replaced The equipment must be totally disconnected from all power sources mains supply and battery before it can be opened for inspection or servicing The battery ca...

Page 2: ...econds Start an equalisation charge Access to a sub menu Access to the menus press 3 seconds Close the window UNPACKING The charger is delivered with the following 2 m AC mains cable 3 m DC battery cable This technical manual MECHANICAL INSTALLATION The charger is intended to be floor standing and must be installed in the vertical orientation The distance between 2 adjacent chargers should be at l...

Page 3: ...ows information relative to the connected battery and counts down the time remaining until the effective charge begins Ref Without Wi IQ With Wi IQ 1 Charger status CHARGE AVAIL DEFAULT EQUAL possible pump fault or DF4 2 Alternating display of battery voltage voltage per cell Ah restored charging time remaining charging time percentage of battery charge 3 Set up operating battery Battery temperatu...

Page 4: ...ion charge is indicated by the message EQUAL During the equalisation charge the charger displays the current ref 4 and alternating the battery voltage voltage per cell remaining time ref 2 2 The battery will be available as soon as the screen becomes green Automatic start If the equalisation charge has been programmed Configuration Equalisation menu the equalisation charge is initiated automatical...

Page 5: ...e BAT TEMP DF MOD WRG MOD IQ SCAN IQ LINK T NO Wi IQ Critical battery temperature One or more modules are not working correctly One or more modules are not the correct specification Looking for presence of Wi IQ Set the link Wi IQ Charger Low electrolyte level Default of balance voltage detected by the Wi IQ Too high battery temperature Preventive maintenance indicator The Wi IQ on the battery is ...