Setup Procedure
12
Centurion
Guided Radar
Setting Advanced Parameters
The
Advanced
menu parameters are for adjusting primary Sensitivity, echo controls/filters, communications
and output settings.
2. Advanced Parameters
Parameter
Description
Options
Comms
Adjust communication protocol settings.
• Device ID
• Baud Rate
Digitize
Perform auto-Digitization of Sensitivity based on mounting and
Dielectric of material touching the probe (see Setup Procedure A)
• Execute
• Disable
• Cancel
Sensitivity
Manual adjustment of Sensitivity. This value will also be
automatically adjusted by other calibration routines. Sensitivity is
the primary adjustment for the units ability to detect media
• 0-100
Blanking
Blanking is a non-measurable zone. This can be increased to
‘Blank’ out high level false echoes caused by mounting
• Adjustable
Cal Mount
Performs a digital mapping routine of a user selected span. Used
when there is signal interference at high level or mounting.
Use Digit Bias to adjust bias (cal sensitivity) of mapping range
• Cal Start
• Cal End
Analogue
Adjust and tune 4-20mA settings
• 4-20
• 20-4
• 4mA tuning
• 20mA tuning
• Park 4mA
• Park 8mA
• Park 12mA
Factry Reset
Restore unit to factory defaults
• Yes
• No
Device Info
Display device information
Lock Code
Adjust the peak Sensitivity cap. This value will be automatically
adjusted by other calibration routines
• Disable
• Enable