Display Mode
Sultan
Acoustic Wave Series
27
Non-standard display modes
AvgMatrl
and
Diff O/P
are special operation modes which require two transducers connected to an amplifier
via a junction box. Avg Matrl calculates the average level measured by the two transducers and Diff O/P
calculates the difference in level between the two transducers. You will need to assign one transducer to ID2.
To do this connect only one of the transducers, enter ‘Quickset’ and change the display mode to AvgMatrl or
Diff O/P. Scroll down until you see 1:Sen Add 1 option, press CAL, select ‘1’ for current transducer and press
CAL again. The menu then proceeds to Tx Add:, press CAL to edit, pres UP to scroll from 1 to 2 and press
CAL to save. The currently connected transducer is now on ID2 - you can now connect the other transducer
to the junction box which will be ID1 to complete the measurement pair required for Average & Differential
measurement..
The
Flow
option can be used for basic open channel flow applications with a known Exponent value of
the flume/channel/weir and the known max flow rate. Low & High level need to be set to represent the
distance from the transducer face of 0-100% possible flow of the application. For more comprehensive flow
measurement please see the dedicated flow measurement unit the Sultan Flow.
*Press RUN twice at any time to revert to normal operation
Flow Unit
Flow Exp
Flow Max
Lo Cut Off
liters
k liters
m liters
Cube mtr
Cube ft
Adjust to required exponent
Adjust to maximum
Flow rate value
CAL
Flow
CAL
CAL
CAL
Adjust Low cut off point
Can be used to stop unit measuring
stagnant liqud level as flow.
Sensors
Select number of sensors 1 or 2
CAL
AvgMatrl
LoLevel2
Specify 2nd sensor low level
CAL
Diff O/P
HiLevel2
CAL
Specify 2nd sensor high level