Hawk 2000-RANGE-VALVE Series Instruction Manual Download Page 4

4

Overview

WARNING:

BEFORE OPENING THE VALVE, MAKE SURE THE TRANSMITTER IS LOCKED.
BE SURE THE VALVE IS CLOSED WHEN HE TRANSMITTER IS RETRACTED FROM VALVE.
THIS IS EXTREMELY IMPORTANT OTHERWISE THE TRANSMITTER WILL PUSH OUT OF THE PROCESS.

Installing Transmitter 2000-RANGE-VALVE

The position of the valve depends on the welding position of the weld-on nipple. Before welding, locate weld-on nipple so that the 
valve is in the right position.

* DO NOT DAMAGE THE THREAD.*

Mounting Position

When the transmitter is mounted horizontally, the cable gland MUST be pointed downwards.

Mounting Position Effect

All transmitters are calibrated in vertical position.
If the transmitter is mounted in a different position, there will be a little zero shift.
If the transmitter is mounted up, there is a zero shift (e.g. 4,03 mA instead of 4mA). If the transmitter is mounted down, there is a zero 
shift (e.g. 3.97 mA instead of 4mA). 

After installation of the transmitter the zero must be set to 4.00 mA with “P103” in the programming mode. This will not 
affect the span.

Calibration

All transmitters are fully calibrated at the factory, to the conditions stipulated in users order. When the buyer has not requested 
calibration, the transmitter will be calibrated at the highest span. It is advised to re-calibrate the transmitter after shipment.

Under the cover (3) you will find the terminal board.
The push buttons “Zero”, “Span” and “Prog” are under the other 
cover (1).
External loads must be placed in the negative leg of the 2-wire 
loop.
The figure left shows the wiring connection of the transmitter. The 
2-wires must be connected to 3(-) and 4 (+) of the terminal board.
The signal wiring must be shielded and twisted pairs yield best 
results. Do NOT run signal wiring in open trays with power wiring, 
or near “heavy” electrical equipment (E.g.: Frequency controller or 
heavy pumps).
Shielding must always be connected at the side of the power 
supply.  In case the mounting position is already connected 
to earth (e.g. via the tank or pipe line) 

DO NOT

 connect the 

instrument to earth. 

Please ensure that the instrument is not 

connected to earth twice to prevent the occurrence of an 
‘earth loop’

. In applications with synthetic mounting positions the 

case ground terminal (internal or external) must be connected to 
earth.

 

SERIES  2000-RANGE-VALVE                                                      

Summary of Contents for 2000-RANGE-VALVE Series

Page 1: ...erview Gladiator Acoustic Switch Series A Higher Level of Performance Instruction Manual www hawkmeasurement com For more information please visit SERIES 2000 RANGE VALVE Pressure and Level Transmitte...

Page 2: ...nting PA 5 PG9 cable gland 6 Electronics housing AISI 304 7 Hexagon nut SW 41 AISI 304 8 Stop AISI 316 9 O ring 2x VITON 10 Nipple SW 41 1 BSP M 2x AISI 316 11 Safety Lock AISI 304 12 M4 Bolt AISI 304...

Page 3: ...sing the auxiliary tool to ensure the parts are in line Use silicone grease 2 Tighten the valve bolts 18 4x 3 3 Remove the auxiliary tool and make sure the valve and be closed and opened easily 4 Make...

Page 4: ...libration All transmitters are fully calibrated at the factory to the conditions stipulated in users order When the buyer has not requested calibration the transmitter will be calibrated at the highes...

Page 5: ...supply is based on the total circuit resistance The maximum permissible load Ri max in case of 24 Vdc is 600 Ohm By increasing the power supply the external load can be increased to 1200 Ohm 36 Vdc s...

Page 6: ...bar is supplied to the transmitter the button must be held until the word SPAN appears on the display The transmitter is adjusted at 20 mA now The span can also be adjusted without test pressure see P...

Page 7: ...See Conversiontable P105 4 20 mA 20 4 mA Reverse output P106 Adjustment damping 0 to 25 sec P107 Indication of process temp Read out on display P108 0 C 1 F P109 Read out on display Curr 0 current 4...

Page 8: ...pressure P101 Span Adjustment 20 mA Without Test Pressure Before adjusting the span take care the right pressure unit is selected See also P104 and P109 Example Adjustment of the span at 0 2 bar First...

Page 9: ...smitters working with software revision 1 will direct process cancel mounting position P103 Adjustment Pressure Unit On Display See Conversion Table P104 104 Conversion Factor Display 1 1 000 mH2 O mW...

Page 10: ...on P107 until the actual pressure appears on the display again P107 Temperature In o C OR o F The temperature of the transmitter is standard adjusted at o C DEGR When pushing at h in P108 this will c...

Page 11: ...simulation Pressure simulation Unit To perform a pressure simulation follow the next steps 1 Push PROG until 100 is shown on the display 2 Push 10 times at h SPAN till 110 appears on the display 3 Con...

Page 12: ...rizontal tank Cilindric Push PROG until 100 is shown on the display 2 Push 11 x at h SPAN till 111 appears Confirm with PROG 3 Push h once Confirm with PROG 4 Enter the height H1 of the tank in meters...

Page 13: ...the length L of the tank For a ball or cone shaped tank take the cylindrical length plus the length of 1 ball cone Confirm with PROG 7 Enter H3 in meters if the transmitter is installed like in the le...

Page 14: ...al Cone From Software Revision 3 1 Push PROG till 100 appears on the display 2 Push 11 times at h till 111 appears Confirm with PROG 3 Push three times at h Confirm with PROG 4 Enter height H1 of the...

Page 15: ...confirm Lo Pr appears on the display 4 Push h i for adjusting to ON or OFF 5 Push PROG to confirm Adjustment Communication Protection 1 Push PROG till 100 appears on the display 2 Push h SPAN 13 times...

Page 16: ...H HART DTM This DTM is developed to make configuration changes of HAWK Series 2000 RANGE VALVE option H HART transmitters easy This DTM can be used with almost every FDT container To be able to insta...

Page 17: ...his is very important to prevent distortion of the weld spud The diaphragm of the SERIES 2000 RANGE VALVE is protected with a special protection cap Protect the diaphragm until installation takes plac...

Reviews: