![Hauck BBG BETA Series Instruction Manual Download Page 3](http://html.mh-extra.com/html/hauck/bbg-beta-series/bbg-beta-series_instruction-manual_2107566003.webp)
Page 3
BBG-9
C. BURNER CAPACITIES
SPECIFICATIONS
BURNER MODEL
xx04
xx06
xx08
xx10
Capacity
(MMBTU/hr)
3.1 6.1 12.0 19.1
(kW)
820
1,610
3,170
5,050
Air Capacity
(scfh) 32,000
63,500
124,500
198,000
(nm
3
/hr)
857
1,701
3,335
5,304
Air Inlet Pressure
(in.w.c.) 27.7
27.7
27.7 27.7
(mbar)
68.9
68.9
68.9
68.9
Gas Inlet Pressure
(in.w.c.) 1.5
11.6
12.0 3.7
(mbar)
3.7
28.9
29.9
9.2
Flame Length
(ft) 5.8
8.0
10.0
12.0
(m)
1.8
2.4
3.0
3.7
Flame Diameter
(ft) 1.5
2.0
3.0
4.0
(m)
0.5
0.6
0.9
1.2
SPECIFICATIONS
BURNER MODEL
xx12
xx14
xx18
xx24
Capacity
(MMBTU/hr)
25.6 38.3 64.7 123.0
(kW)
6,770
10,130
17,110
32,530
Air Capacity
(scfh) 265,000
397,000 670,000 1,275,000
(nm
3
/hr)
7,099
10,635
17,948
34,155
Air Inlet Pressure
(in.w.c.) 27.7
27.7
27.7 27.7
(mbar)
68.9
68.9
68.9
68.9
Gas Inlet Pressure
(in.w.c.) 5.8 1.5
11.8 2.9
(mbar)
14.4
3.7
29.4
7.1
Flame Length
(ft) 14.0
15.0
17.0
25.0
(m)
4.3
4.6
5.2
7.6
Flame Diameter
(ft) 4.0
4.5
5.0
5.0
(m)
1.2
1.4
1.5
1.5
NOTES:
1. Capacities based on Natural Gas with HHV of 1034 Btu/ft
3
, (Standard), and LHV of 10.21 kWh/nm
3
(Metric)
0.59 S.G., and a stoichiometric ratio of 9.74:1 with burner firing into chamber under no pressure at 10% excess
air.
2. Air and fuel flows based on STP operating conditions at sea level and industry standard air and gas piping
practices.
3. Gas inlet pressure given for reference only and should not be used for measuring fuel flow to the burner.
4. Flame lengths measured from end of the combustion tile.
5. Burner is suitable for use on gaseous fuels other than Natural Gas and with combustion air other than ambient
temperature, consult Hauck.
Table 1. Burner Capacities