Section 4:
Operating Features & Functions
Copyright © 2011 Haskris Company
23
www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
5)
Head Pressure Display B
Indicates refrigerant head B pressure set value (SV) and current head B pressure
process value (PV).
6)
Pump Only Mode – Standby – Normal Operation
This 3 position switch determines the operation mode of the R1600.
Right –Powers display panel and pump only. (Pump Only Mode - Service)
Center – Powers display panel only. (Standby)
Left – Switch is in this position during magnet operation. (Normal Operation
Mode)
7)
Fill LED
LED is lit when tank is at the maximum operating level.
8)
Low liquid LED
Liquid level latch. If this light is on the compressor and pump will not operate, more
glycol must be added to system. Power must be off. (See page 29)
9)
I/O Switch
Energizes or De-energizes entire R1600 system with exception to the crankcase
heater. Crankcase heater is energized when main power is supplied to the R1600
and is not controlled by R1600 I/O switch.
4
4
4
4.1
.1
.1
.1 Temperature Control
Temperature Control
Temperature Control
Temperature Control
4.1.1 Notes
1.
Temperature is Factory Pre-Set
Haskris has pre-set the glycol solution temperature to 14°C (57.2°F). On
initial start-up, apply the actual heat load and wait 30-40 minutes for the
temperature to stabilize.
2.
Allowable Adjustments:
The following procedures are intended for glycol solution temperature
adjustments only. All other control parameters are factory set for optimum
performance and should not be adjusted. If it appears that “tuning” is
required, please contact Haskris for further information.