VPT10-H
HART
®
PRESSURE TRANSMITTER
INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
______________________________________________________________________________________________________________________________
14
Some examples of assemblies, showing the location of the transmitter relative to the taps, are shown in figure 2.5. The
location of the pressure taps and the relative position of the transmitter are shown in table 2.1.
Process Fluid
Taps Location
VPT10-H Location in relation to the Taps
Gas
Superior or Lateral
Above
Liquid
Lateral
Below or at same level
Steam
Lateral
Below using condensation chamber
Table 2.1 – Location of pressure taps.
Figure 2.5 – Examples for transmitter mounting, in relation to pressure taps.
2.2.
ELECTRICAL CONNECTION
To access the terminal block, remove the rear cover of VPT10-H. To do this, loosen the cover locking screw (see figure
2.6) by turning it clockwise.
Figure 2.6 – Rear cover lock.