HS-3644 Installation and Operating Manual
10
6.0 Operating the HS-3644
6.1 Displays
•
When the system is normal and AC power is present, the AC ON light is on and all other
lights are off.
•
The Alarm, Supervisory, Trouble, Monitor and Ground Fault lights will turn on and off as
the corresponding conditions occur and restore.
•
The LCD will show active events identical to the Fire Alarm Control Panel's display.
•
The display's backlighting will be on when the annunciator is in use. It will time out after 1
minute without a keypress when AC is present on the system, and after 15 seconds if the
system is running on standby batteries.
6.2 Controls
•
The keyswitch enables the Silence and Reset keys. All other keys are available with or
without the key in place.
•
The ALM, SUP, TBL and MON scroll keys can be used to view all active events in the
corresponding categories. If there is no event in the category of the key being pressed, it
will scroll through the top level system status screen.
•
The ACK key is used to acknowledge and silence Trouble or Supervisory conditions.
•
The SILENCE key is used to silence the system's Notification Appliances.
•
The RESET key is used to reset the system following off-normal conditions.
•
The LAMP TEST key is used to test the annunciator. Pressing this key will cause all lights
to flash and the display to show a test message.
•
The user is warned of an illegal entry or function by three quick beeps.
6.3 Miscellaneous
•
For more information on detailed menus, refer to the installation/operating guide for the
applicable Fire Alarm Control Panel.
•
The main display/keypad of the Fire Alarm Control Panel always takes priority over the
remote annunciator. If the main display/keypad is in use, and a user presses a key at the
annunciator, the remote display will read "System Busy, Please Wait". This will occur until
15 seconds after the last keypress at the main panel.
ALARM
ALM
SUP
TBL
MON
ACK
SILENCE
RESET
LAMP
TEST
SUPERVISORY
TROUBLE
MONITOR
AC ON
GROUND FAULT
HS-3644