Screen 27
Miscellaneous. outputs
This screen lets the viewer see the display status of the miscellaneous outputs. This is
new in NP18
,
where in programming you can set up the outputs if needed as
Supervisory
Bell, Trouble Bell
, or
Auxiliary Power
.
Note:
When the output is set up as Supervisory or Trouble Bell, they will sound when
that condition is present. By pressing the
Acknowledge will
silence the circuit
.
When setting up the output circuit as an Auxiliary Power Circuit, this turns on the
Output continuously to supply power for auxiliary devices, such as annunciators. If a
Duration
time is given for the Auxiliary Power circuit, the circuit will be powered off for
that number of seconds (from 1 to 30) when the panel
Reset
key is pressed with neither of
its LED’s flashing. This allows for the reset of 4 wire detectors. A duration time of 0
prevents this operation. Auxiliary Power circuits will be turned off by the panel while it
is in its power up cycle.