Harman TL300 Installation & Operating Manual Download Page 20

20

Harman TL300

The chimney System

creosote 

When  wood  is  burned  slowly,  it  produces  tar 

and other organic vapors, as well as soot, which 

combine with expelled moisture to form creosote. 

The  creosote  vapors  condense  in  the  relatively 

cool chimney flue (associated with a slow burning 

fire). As a result, creosote accumulates on the flue 

lining. When ignited, this creosote can result in an 

extremely hot fire.

The  FireDome

 

on  the TL300  cuts  creosote  to 

almost nothing 

when properly burned with dry 

seasoned wood.

The chimney should be inspected at least once 

every two months during the heating season to see if 

any creosote build-up has occurred. Checking your 

chimney and chimney connector more frequently, 

especially while you are getting used to your stove, 

is recommended.  To inspect this system, let the 

stove cool. Using a flashlight and mirror, check the 

interior of the chimney connector, and the chimney 

itself. If a significant layer of creosote or soot has 

accumulated (1/8" or 3 mm) it should be removed 

to reduce the risk of a chimney fire.

To  clean  deposits  from  the  surface  of  the 

connector, use a stiff wire brush after dismantling 

the  connector  assembly.   To  clean  the  chimney, 

use  a  specially  designed  brush  sized  to  fit  your 

particular  flue  opening,  or  call  an  established 

chimney cleaning service.

At  the  end  of  the  heating  season,  perform  a 

thorough examination of your chimney system, and 

have it repaired if necessary.

Maintenance

d

amper ramp adjustment

After the stove has been in operation for awhile, 

the damper gasket may compress and allow the 

damper handle to move from the open to the closed 

position without the added ramp tension needed 

to keep the damper held in the closed position.

To adjust the ramp, the stove MuST be allowed 

to go out and cool down. 

• After the stove has cooled off, remove the stove 

pipe from the stove collar and close the damper.

•  Using  a  flashlight,  look  into  the  collar. About 

midpoint of the damper plate on the backside you 

will see the adjustment bolt for the ramp tension. 

(See figure on right.)

• You will need (2) 7/16 " wrenches. Use one to hold 

the bolt still while using the other to loosen the nut.

• Turn the bolt inward (clockwise facing the head) 

approximately 1/4 turn and retighten the locknut.

• Now open and close the damper to check for 

proper tension on the damper lever while moving 

into the closed direction. 

• If the tension is incorrect, readjust the bolt.         

gaskets

Gaskets  are  used  at  strategic  positions  when 

building  the  Harman  TL300  for  controlling  the 

path  that  incoming  and  outgoing  air  and  gases 

take  through  the  stove. You  must  check  these 

gaskets from time to time and replace them when 

necessary. The  gaskets  are  made  of  fiberglass 

of different sizes (obtainable from your Harman 

dealer) and some are fixed in place with a high 

temperature stove gasket cement.  To change a 

gasket, first remove the worn fiberglass and clean 

the area with a wire brush.  Also clean any other 

surfaces that come into contact with the gasket. 

Place a small bead of cement in the area under the 

gasket if required, then press new gasket material 

into the channel; do not overlap the ends. Seat the 

gasket firmly by applying pressure when possible; 

for example, after changing the door gasket, close 

the  door. Allow  the  cement  to  dry  before  using 

your stove.

Gaskets are located:

•  On the doors to provide airtight closure.

•  Between the damper and the damper frame.

•  Rear cover

•  Rear housing

Loosen nut

Turn bolt inward 1/4 

turn.

Summary of Contents for TL300

Page 1: ...table for installation in a mobile home us only IF THIS wood burning STOVE IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FI...

Page 2: ...2 Harman TL300...

Page 3: ...e to follow instructions may result in property damage bodily injury or even death Index Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 U S A Introduction 4 Specifications 5 Ins...

Page 4: ...50 mm 775mm 600 mm 450 mm 675 mm CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA CONSULTEX LES ADMINISTRATIONS ET ORGANISMES COMPETENTS POUR LA CON...

Page 5: ...ax Heating Capacity 1 500 3 000 sq ft Average Emissions 1 1 Grams Per Hr Emissons on Low 0 8 Grams Per Hr Outside Air Size 3 or 4 Inch SAFETY NOTICE IF THIS STOVE IS NOT PROPERLY INSTALLED A HOUSE FIR...

Page 6: ...6 Harman TL300 Specifications Andirons Grate Air Control Front Load Door Top Load Door Handle Ash Door Ash Door Latch Front Load Door Latch Top Load Door Top Load Opening...

Page 7: ...ed to rain or extremely damp conditions Hardwoods are favored because they are heavier and contain more heating capacity BTU s per load than do softwoods Wood should be split and stored under cover fo...

Page 8: ...U S and 60 1524 mm in Canada Due to excessive heat build up at the wall passthrough using double wall pipe horizontal venting is only approved into a masonry chimney See Detailed Clearances on Page 9...

Page 9: ...vent vented out back wall with 90o elbow Masonry Chim ney Only 21 15 11 2 28 Top vent ceiling and sidewall clearances 28 17 Single Wall Pipe Top Vent Parallel Installation 20 Double Wall Pipe Parallel...

Page 10: ...of the flue collar opening Do not use makeshift components No part of the chimney connector may pass through an attic or roof space closet or other concealed space or through a floor or ceiling Whene...

Page 11: ...point at which they exit from the roof Then the chimney must extend 2 ft 6 m above the highest point within a 10 ft 3 m radius Thus the 3 foot 2 foot 10 foot rule 3ft Above roof exit point 2ft Higher...

Page 12: ...masonry chimney several provisions are standard First whether the chimney connector is vented to the chimney through a thimble or a breech pipe neither must pass beyond the inner surface of the chimn...

Page 13: ...13 Harman TL300 Venting Standard Ceiling Installation with Factory Built Chimney Cathedral Ceiling Installation with Factory Built Chimney...

Page 14: ...inimum of three Sheet Metal Screws per Joint of Chimney Connector Mantel and Trim Protection Floor Protection in Accordance with Solid Fuel Appliance Listing Airtight insulated Clean out Chimney Breac...

Page 15: ...bly 1 Clearance for Exterior Chimney or 2 Clearance for Interior Chimney and 2 Clearance for NFPA 211 Type Approved Thimbles Floor Protecion in Accordance with Solid Fuel Appliance Listing Check with...

Page 16: ...urned This represents most of the wood s heating capacity The final stage is the charcoal stage where the charcoal burns the remaining heat content out of the fuel Ash remains after the burning is com...

Page 17: ...o not have the proper coal bed Open the bypass damper and continue with the process until a significant coal bed is formed To regulate the speed of the optional convection blower adjust the variable s...

Page 18: ...until all cinders have thoroughly cooled This could take days Never use the ash disposal container for other trash Wood ash can be added to your garden or compost g Avoid overfiring your stove Overfi...

Page 19: ...refractory lining material grates and casting If any bricks have been damaged replace them with Harman replacement parts Be sure that all air holes in the refractory are open The Firedome combustion p...

Page 20: ...t the added ramp tension needed to keep the damper held in the closed position To adjust the ramp the stove MUST be allowed to go out and cool down After the stove has cooled off remove the stove pipe...

Page 21: ...n outside air duct less than 5 1525 mm long may be 3 80mm in diameter and be made of masonry tile 26 gauge 0 019 galvanized steel or other approved noncombustible material it should have a 1 25 mm cle...

Page 22: ...00 3 goldenfire ending Manufacturing date june 2011 1 90 06900 4 Metallic blue ending Manufacturing date jan 2010 beginning Manufacturing date aug 2007 ending Manufacturing date active 1 90 06900 1 bl...

Page 23: ...2019 15 Top Load Door Gasket Plate 1 10 40020 Y Gasket Top Load Door 1 00 10050 Y Hinge Spacer Qty 2 req 2 00 40021L Lid Hinge Set Bottom 1 00 40022 Y Nut Zinc Plated Acron Pkg of 50 3 30 8014 50 Y 8...

Page 24: ...8 3 Damper Linkage Arm Weldment w Hardware 1 10 06937W Y 18 4 Damper Pivot Gear Pkg of 2 2 00 06924 2 18 5 Damper Idler Gear 2 00 06923L 18 6 Damper Arm Gear Weldment 1 10 06916W Y 18 7 Damper Shaft C...

Page 25: ...ick Bracket Pkg of 2 1 00 06945 Y 19 7 Fire Brick 6 x 12 Qty 4 req Pre 551 4 40 86125 Y Post 551 3 40 86125 Y 19 8 Brick Insulation Qty 2 req 3 40 06944 Y 19 9 Grate 2 00 06925B Y 19 10 Inlet Brick Ri...

Page 26: ...26 Harman TL300 This page intentionally left blank...

Page 27: ...truction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlie...

Page 28: ...t of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enamel...

Page 29: ...29 Harman TL300 Notes...

Page 30: ...30 Harman TL300 Notes...

Page 31: ......

Page 32: ...Proudly Printed On 100 Recycled Paper...

Reviews: