Harman R11 Installation & Operating Manual Download Page 11

Harman Oakwood 

11

Floor Protection Requirements

The Oakwood must be installed on a non-combustible 

floor or a non-combustible floor protector. Floor protection, 

when not using the optional bottom heat shield, must be 

a minimum 3/4" (19mm) thickness of material having an 

insulating value equal to or better than 0.84k/in. (The lower 

the k value, the better the protection.)

Another method for calculating floor protection is in R 

value. This requirement would be for an R value of 0.89 or 

higher. (The higher the R value, the better the protection).

In all installations, the area under and around the stove 

must be protected from falling ash and live coals. 

The area 

under a horizontal run of chimney connector must also be 
protected, extending two (2) inches beyond the measurement 
of the horizontal connector.

 

Further guidelines for floor protection are as follows: 

In the U.S. the floor protector must be completely under 

the stove, and extending 16" in front of the door opening, 

8" to each side and 8" to the back.

In Canada, the floor protection must extend 18" (457mm) 

in front of the door opening, 8" (203mm) to each side and 

extend to the wall behind the stove. 

Clearances

Clearance is the empty space required between the stove 

or chimney connector and the nearest combustible surface or 

object, such as walls, ceilings, floors, or furniture.  Clearance 

distances may only be reduced by using methods approved 

by either the CAN/CSA B365 standard (Canada) or NFPA 

211 (U.S.)  Contact your building authority for information 

if you are interested in reducing clearance distances other 
than those presented here.

Parallel versus Corner Installations

A parallel installation is one in which the back and sides 

of the stove are parallel to the walls behind and to the side 
of the stove.  A corner installation is one in which the back 
of the stove is positioned diagonally across a corner of the 
room. Each installation requires its own set of clearances.

InStallatIOn

For  parallel  installations,  the  required  clearance  dis-

tances from the stove are:  (see next pages for more details, 

including the use of double walled pipe and optional heat 
shields)

1) to the side wall, 26" (661 mm); 

2) to the back wall, 28" (712 mm).  

3) From the flue connector to the wall, 33" (839mm) 

4) Horizontal pipe to the ceiling, 15"(381 mm).  

NOTE:  For a vertical chimney connector in a parallel 

installation the distance of the connector to the side wall must 

be 32"(813 mm), due to the required side clearance of the 

stove itself.  Fireplace installations must meet these same 

clearance requirements; specifically follow these guidelines 

for mantel and trim clearances.

For corner installations, the clearance distances from the 

stove are 24"(609 mm) from each corner of the stove mea

-

sured straight back to the nearest combustible material, and 

32" (813 mm) from the chimney connector to the walls.

From  the  front  of  the  stove,  clearance  to  combustible 

materials such as furniture, curtains, fuel, etc., is:  48"(1220 

mm) in the 

U.S

. and 60"(1524 mm) in 

Canada.

Summary of Contents for R11

Page 1: ...E IN THE U S AND CANADA The Oakwood is not approved for mobile home installation IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS C...

Page 2: ......

Page 3: ...tions may result in property damage bodily injury or even death Harman Home Heating 352 Mountain House Road Halifax PA 17032 U S A INDEX INDEX Introduction 4 Specifications 5 Operation Building a Fire...

Page 4: ...catalytic stoves Top loading makes adding wood easier and allows you to view your beautiful fire through the extra large glass door The glass stays cleaner because of specially coated glass and the e...

Page 5: ...n limits for wood heaters sold after July 1 1990 Weight 440 lbs Flue Size 6 inch Log Length Recommended 21 Max Heating Capacity 2 000 sq ft Average Emissions 2 32 Grams Per Hr Emissions on Low 0 8 Gra...

Page 6: ...Harman Oakwood Andirons Grate Top Load Opening Air Control Front Load Door Top Load Door Bypass Damper Control Handle Ash Door Ash Door Latch Front Load Door Latch SPECIFICATIONS Optional Cooking Gril...

Page 7: ...y passing a poker back and forth across the grate The andirons keep the fuel from coming into direct con tact with the glass and keep hot coals and embers from spilling out while reloading Never build...

Page 8: ...ges The initial or evaporation stage is where the moisture in the wood is driven off in the form of steam A second stage is where the volatile gases contained in the wood are released and burned This...

Page 9: ...etting all the way to the right Be sure the ash pan door is closed and latched Start with a bed of crumpled paper and kindling sized about finger width place several 1 2 25mm 50mm splitpiecesofdrywood...

Page 10: ...bypass before taking the ashes outside for safe disposal Ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a noncombustible floor o...

Page 11: ...pproved by either the CAN CSA B365 standard Canada or NFPA 211 U S Contact your building authority for information if you are interested in reducing clearance distances other than those presented here...

Page 12: ...12 Harman Oakwood INSTALLATION CLEARANCES See NFPA 211 for more installation clearance reductions when using USM wall protection etc 21 25...

Page 13: ...Harman Oakwood 13 INSTALLATION CLEARANCES See NFPA 211 for more installation clearance reductions when using USM wall protection etc...

Page 14: ...14 Harman Oakwood installation clearances See NFPA 211 for more installation clearance reductions when using USM wall protection etc...

Page 15: ...rth weight limitations The Oakwood should not be installed into a factory built fireplace unless the hearth area is designed to take the maximum weight of the stove The Oakwood loaded with wood weighs...

Page 16: ...loset or other concealed space or through a floor or ceiling Whenever possible avoid passing the connector through a combustible wall if you must use an approved wall pass through described later in t...

Page 17: ...200 mm may be used For square or rectangular masonry chimneys nominal sizes of 8 x 8 or 8 x 12 200 mm x 200 mm 200 mm x 300 mm may be used Codes require that solid fuel chimneys extend 3 ft 0 9 m abo...

Page 18: ...e of the chimney liner and both must be firmly cemented in place with refractory cement Athimble is a masonry pipe which is inserted through the chimney wall and is frequently the preferred method a b...

Page 19: ...id fuels are burned completely they pro duce water and carbon dioxide However in long slow burns a substantial amount of carbon monoxide may be produced If allowed to build up carbon monoxide which is...

Page 20: ...Chimney Support Standard Ceiling Installation with Factory Built Chimney Chimney Cap Factory Built Metal Chimney Sealed Storm Collar Finishing Col lar Chimney Connector Cathedral Ceiling Installation...

Page 21: ...Space Three Sheet Metal Screws per Joint of Chimney Connector Mantel and Trim Pro tection Floor Protection in Accordance with Solid Fuel Appliance Listing Airtight insulated Clean out Chimney Breach F...

Page 22: ...Extend to Flue Liner Minimum 8 Masonry Thickness in Front of Smoke Chamber Use Damper Adapter or Seal with Non Combustible Material Floor Protection in Accordance with Solid Fuel Appliance Listing Ai...

Page 23: ...ace Trim Protection for Reduced Clearance UL1777 Stainless Steel Liner System or Other approved lining system Follow liner manufacturer s instructions on insulation and support Floor Protection in Acc...

Page 24: ...Clearance for Complex ity Exterior Chimney or 2 Clearance for Interior Chimney and 2 Clear ance for NFPA 211 Type Approved Thimbles Floor Protection in Accordance with Solid Fuel Appliance Listing Ch...

Page 25: ...work the controls back and forth several times during the summer or any prolonged period when you are not using your stove The Fire Chamber The inside of the fire chamber should be examined for damag...

Page 26: ...check these gaskets from time to time and replace them when necessary The gaskets are made of fiberglass of different sizes obtainable from your Harman dealer and some are fixed in place with a high...

Page 27: ...n the smoke deflec tor may not be needed on the top vent models The Cozy Screen can be used from the start of a fire or can be used with an existing one When starting a fire with the Cozy Screen smoke...

Page 28: ...ck 1 90 02490 2 Charcoal 1 90 02490 3 goldenfire 1 90 02490 4 Metallic blue 1 90 02490 5 Honey glo 1 90 02490 10 Mojave red 1 90 02490 12 Forest green 1 2 3 4 6 8 9 10 15 16 17 18 21 22 23 24 25 26 27...

Page 29: ...Top 4 00 249105P 11 Top Load Door 3 00 249115P 12 Top Load Handle 2 00 249148 13 Left Side Panel 4 00 249103D 14 Inner Front 4 00 249111S 15 Andiron Qty 2 Req 3 00 249101P Y 16 Front Load Door 4 00 24...

Page 30: ...31 2 Inlet Brick Right 3 40 00104 Y 31 3 Logo Brick 3 40 00101 Y 31 4 Inlet Brick Left 3 40 00103 Y 31 5 Upper Brick Clip Pkg of 2 1 00 249172 Y 31 6 Rear Brick Clip Pkg of 2 1 00 249153 Y 31 7 Cast L...

Page 31: ...2494 32 4 Bottom Heat Shield Kit 1 00 02491 Hardware Packages Bolt 5 16 18 x 2 Zinc Plated Carriage Pkg of 25 3 30 4001 25 Y Bushing 3 8 OD X 1 4 OAL Pkg of 5 3 50 00058 5 Y Nut 1 4 20 Zinc Plated Fin...

Page 32: ...32 Harman Oakwood...

Page 33: ...Harman Oakwood 33...

Page 34: ...34 Harman Oakwood notes...

Page 35: ......

Page 36: ...Proudly Printed On 100 Recycled Paper...

Reviews: